GSM modem dataloggers

 

Summary of Contents for AR003954

Page 1: ...www guilcor com User s Guide AR006087 AR005892 AR004525 AR006092 AR006088 AR006089 AR006090 AR003954 AR006779 AR006091 AR006093 AR005348 GSM modem dataloggers...

Page 2: ...ent of Guilcor All rights reserved The Guilcor company is continuously developing and improving its product Guilcor reserves the right to carry out technical changes in equipment or product without an...

Page 3: ...ns of a program 27 The device setup from a program Configuration 27 APPLICATION NOTES 37 RECOMMENDATIONS FOR OPERATION AND MAINTENANCE 40 TECHNICAL PARAMETERS 43 Power supply 43 USB communication inte...

Page 4: ...es will be overwritten by fresh ones after the memory unit getting filled up to set up two alarm signalling limits for each quantity to be measured The alarm signalling can be realised visually option...

Page 5: ...5 Datalogger AR004525 model...

Page 6: ...to chemicals or mechanical shocks Use soft tissue for cleaning Do not apply solvents or similar aggressive agents Battery damage Should the battery casing get damaged or should the whole device get de...

Page 7: ...ity and safety of the message delivery For some tariffs the message delivery may be stopped when a certain number of messages or amount of transferred data is exceeded or when a given time period has...

Page 8: ...connection Installing the datalogger placing the probes Choose a suitable location for installing the device bear in mind that the environmental conditions should be concordant with the Operating cond...

Page 9: ...ou can fix the device on the wall with the aid of a lockable holder AR004252 optional accessory Probe installation and cable routing observe the installation instructions realize the recommended opera...

Page 10: ...over between individual channels and the display mode Current minimum maximum values by means of the keys By pressing a certain key combination you will enter a menu in which you will be able to switc...

Page 11: ...ay of the device usually within 6 hours Maintenance and regular checks for a reliable functioning of the device it is advisable to perform its regular check ups For more details refer to RECOMMENDATIO...

Page 12: ...ptical and acoustic signalling sending SMS messages The memory occupancy is about 75 the device is in the non cyclic recording mode i e the recording will be stopped as soon as the memory capacity is...

Page 13: ...hing OFF It can be preset in the device configuration whether and in what manner these Min Max values will be displayed by the device Remember that the Min Max in question are different from those bei...

Page 14: ...battery is fully charged and the charger can be disconnected A failure has been detected during charging and the charging process has been broken off Try to remove the failure by disconnecting and rec...

Page 15: ...e screens automatically in for about 5 sec interval The cycle can be interrupted by pressing a key If you do not want to use the keypad you can disable it in the device settings Display warnings Displ...

Page 16: ...he menu will close automatically Menu items Deactivation of the optical LED diode and or acoustic the intermittent tone alarm signalling The option Mute optical and or acoustic signalling are controll...

Page 17: ...temperature jump The device is placed directly in the measured space During the charging period the measurement accuracy may be affected by up to 1 C due to parasitic heat AR005892 Two channel thermo...

Page 18: ...characterized by a simple and compact design and a relatively long response to a temperature and humidity jump compare to model with external probes The sensors are located under the grid on the fron...

Page 19: ...ote areas the maximum probe line wire must not exceed 15 m The Digi E series probes provide calibrated measurement values Hence they may be replaced without having to modify the device setup AR006090...

Page 20: ...down Precise reading takes many times longer time than with the open rear lid The maximum length of each probe lead should not exceed 15 m It is recommended to use shielded cables To maintain the IP r...

Page 21: ...his device is not suitable for dusty or water borne areas AR005348 Compact CO2 concentration meter This model is designed to measure concentration of CO2 in the air by internal sensors No additional p...

Page 22: ...ary inputs of this device are not able to capture connected disconnected voltage status Input signals are connected to a connecting block The response to a temperature jump depends on the probe design...

Page 23: ...signals coming from a voltage free contact The binary input changes are registered immediately irrespectively of the recording interval setting To safe record the input status the signal must be prese...

Page 24: ...red with current inputs without any problems Binary input serves to monitor voltage signals or signals coming from a voltage free contact The binary input changes are registered immediately irrespecti...

Page 25: ...AR006092 model binary inputs can capture connected disconnected voltage status The counter states are recorded according to the set Record interval Input signals are connected to a connecting block Th...

Page 26: ...d data user defined online display export into a database etc The starting point for the program control is the menu situated in the left optionally right portion of the utility software and containin...

Page 27: ...guration button The device configuration will be downloaded you will be able to view it If you change the setup of some item the SW will pass over into the editing mode The other users access to the d...

Page 28: ...ogger local current time is running according to your setting By means of the UTC Offset choice you can fix its relation to the UTC This information will be available for all time data provided by the...

Page 29: ...ce every time at integer multiples of the pre set interval For example if you switch the device on at 5 05 and the recording interval has been set to 1 hour the first data will be recorded at 6 00 the...

Page 30: ...0 C Lower point A Input value 4 will be shown as 30 Upper point B Input value 20 will be shown as 80 In a channel for external Pt 1000 probes there exists the possibility to enter the probe parameters...

Page 31: ...sed to be sent out on alarm generation and on alarm disappearance too In both cases add a custom text description of the status that the recipient will see in the message Alarm events ________________...

Page 32: ...cases it is desirable for the user to be informed of an alarm that has occurred during his absence If you enable the Latched alarms choice in the device setting then every alarm occurring in the devic...

Page 33: ...by sending a warning SMS message up to as 4 selected recipients Alarm events System failure _______________________ These panel choices make it possible to set the so called system alarms which indic...

Page 34: ...nding a message the daily limit value will be ascertained Should the limit value be reached the respective recipient will receive a message indicating that the daily limit of the outgoing messages has...

Page 35: ...e is that larger reports can be divided into several messages These messages will not be sent out if no recipient has been chosen Determine which recipients the informative Keep alive text messages wi...

Page 36: ...an then extend this trial period by purchasing a Top Up Voucher for Cloud code SLU503 If the user wants to realize his own collection system the manufacturer can offer php scripts for message processi...

Page 37: ...ce frequently then its keypad and both functions i e device switching on and off from the keypad must be enabled in the device settings Another option is to set the date and time when you want the dev...

Page 38: ...__ For communication with a computer a cable should be used that is not longer than 5 m Check that all connectors are properly seated It is especially the USB C connector that must be properly pushed...

Page 39: ...nterconnection of internal component parts If the blue LED flashes quickly but it does not pass over to a slower frequency then the modem probably failed to be registered in the network Find out if th...

Page 40: ...ning Adhere to principles and procedures mentioned in this manual Try to choose such a place to position the device where the negative influence caused by environment is as low as possible When perfor...

Page 41: ...application and the user s internal regulations In fixed installations following checks are recommended to be performed Metrological verification Regular checks fixed by the user Judgement of all prob...

Page 42: ...Engineering support and service activities are provided by the device distributor His contact person s address is given in the Certificate of warranty included with the product WARNING Unskilled inter...

Page 43: ...rge battery if necessary Battery charger ___________________________________ Recommended charger type Commonly used chargers such as mobile phone chargers with a USB type C connector such as Sunny SYS...

Page 44: ...only runs when the internal temperature ranges between 0 C and 40 C USB communication interface Compatibility USB1 1 USB 2 0 USB3 0 Connector USB C Measurement data storage and real time circuitry Mea...

Page 45: ...band 850 900 1800 1900MHz GPRS Mobile Station Class B Compliant to GSM Phase2 2 Class 4 2W 850 900MHz Class 1 1W 1800 1900MHz Aerial input Connector SMA female Impedance 50 Aerial gain 3 dBi max Aeri...

Page 46: ...x temperature sensed by an external Guilcor Pt1000 E series probe Temperature range 200 to 260 C Pt1000 3850 ppm sensor Measuring current ca 0 5 mA with pulses of ca 60 ms length Input accuracy withou...

Page 47: ...thout probes 0 2 C in a range of 200 to 100 C 0 2 of the measurement value in a range of 100 to 260 C The accuracy of the device with a temperature probe connected to it is determined by the above inp...

Page 48: ...rity 1 RH temperature error 0 05 RH C 0 C to 60 C Dew point temperature 1 5 C at an ambient temperature of T 25 C and RH 30 For details see diagrams in Annex 3 Response time air streaming velocity app...

Page 49: ...according to the connected probe AR006090 ________________________________________ Measured values Internal temperature relative humidity 1x External temperature measured by an external Guilcor Pt100...

Page 50: ...to 15 m not longer than 30 m It is recommended to use shielded cables Response time air streaming velocity approx 1 m s 2 Internal temperature t63 2 min t90 8 min temperature jump 20 C Relative humid...

Page 51: ...ured value Dew point temperature 1 5 C at an ambient temperature of T 25 C and RH 30 For details see diagrams in Annex 3 Response time air streaming velocity approx 1 m s 2 Temperature t63 2 min t90 8...

Page 52: ...hing the L level must factually be applied Should the input be disconnected the device will sense the H level Parameters of the voltage free contact Contact resistance in switched on state 10 k Contac...

Page 53: ...inary input configured for voltage measurements Input voltage for the L level 0 8 V Input voltage for the H level 2 V Minimum applicable voltage 0 V Maximum applicable voltage 30 V DC When the input i...

Page 54: ...voltage measurements Input voltage for the L level 0 8 V Input voltage for the H level 2 V Minimum applicable voltage 0 V Maximum applicable voltage 30 V DC When the input is disconnected the device...

Page 55: ...Maximum applicable voltage 30 V DC When the input is disconnected the device will measure the L level Binary or counter input configured for a voltage free contact or an open collector transistor Con...

Page 56: ...tration in the air according to the set CO2 measurement interval 2 min 10 min 1 Important information is provided in the chapter Manufactured models AR003954 Display resolution CO2 concentration in ai...

Page 57: ...ectronics temperature and rel humidity sensor AR006087 AR005892 AR004525 AR006089 IP67 AR006088 AR006090 IP67 IP30 AR003954 IP20 IP20 AR006092 AR006779 AR006091 AR006093 AR005348 IP20 To reach this in...

Page 58: ...Declaration of conformity This datalogger is in compliance with the requirements of Directive 2014 35 EU The original Declaration of Conformity can be found on the manufacturer s website www guilcor c...

Page 59: ...59 Dimensions AR006087 AR005348 AR005892...

Page 60: ...60 AR004525 AR006088 AR003954...

Page 61: ...61 AR006089 AR006090...

Page 62: ...62 AR006092 AR006779 AR006091...

Page 63: ...ble Error 11 No valid data of the counter batteries missing in the device Reset the counter content by means of the SW repeat the measurement Error 13 Error 14 Error 15 CO2 concentration sensor is not...

Page 64: ...hange the setting for the overflow limit Error 50 Error 52 Error 55 Device configuration failure corrupted configuration Read the configuration into the SW check for the correct setting of all items s...

Page 65: ...crewdriver corresponding to the size insert a screwdriver into the connecting block s angular opening situated above the circular opening Open the connector by turning the screwdriver moderately inser...

Page 66: ...gth then they will be divided into multiple messages Format of alarm SMS message from measured value Description of the device DescDev max 32 chars enter Name of the measured location max 16 chars ent...

Page 67: ...I chars Space 1 ASCII char Memory occupation 1 byte i e 2 ASCII chars Space 1 ASCII char Alarm I states on all chan 1 byte i e 2 ASCII chars Space 1 ASCII char Alarm II states on all chan 1 byte i e 2...

Page 68: ...tion CR LF 2 chars information about the state of the battery CR LF 2 chars information about the level of the GSM signal CR LF 2 chars inserts the current time of the device CR LF 2 chars Watching th...

Page 69: ...connection attempt is increased dynamically It means modem after unsuccessful mobile network signal detection will try to connect again after 10 s 30 s 1 min 5 min 10 min 30 min 1 hour 3 hours 6 hours...

Page 70: ...you want to set time stamps for received data by server s receiving time it is recommended to use Delete unsent data option It will ensure that received data is close to their original time without bi...