Summary of Contents for I-9602LW

Page 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru...

Page 2: ...WWW HOMBI RU CONTENTS I Description 1 II Connection Wiring 1 III Installation 2 IV Application 5 V Maintenance 6 VI Caution 7 VII Specification 8 VIII Limited Warranty 9 HTTP GSTRU RU E MAIL hombi hom...

Page 3: ...2 Connecting with non polarized 24VDC power cable Z1 Z2 Connecting with loop non polarized V V Connecting with pipe solenoid valve There is a forward 12V pulse between these two terminals if the detec...

Page 4: ...ector is suitable for the installation that cables are hidden behind it Please pull out the cables from the electric box through the hole on the center of the base then install the base onto the elect...

Page 5: ...and the position of stove But there are some general rules to follow The detector should be placed in the same room with the stove The vertical distance from the detector to the gas source or stove sh...

Page 6: ...r from the stove Where near strong airflow such as air inlets fans doors etc Where near bathroom or places with a lot of vapor Rooms for boiling water and places where power is cut at night Where temp...

Page 7: ...ling Detector Kitchen Ventilator Floor Stove Fig 3 IV Application 1 Applying power supply to the detector after wiring and checking the green LED will flash for 3 to 6 minutes for warm up and then it...

Page 8: ...on the detector to test if the LEDs and buzzer works normally Pressing the Self Test button the LEDs flash once in turn and the buzzer sounds three times V Maintenance 1 The detector should be tested...

Page 9: ...ar kitchen ventilator Keep environment around the detector clean 3 The detector can only work with the JJ or FCR series solenoid coming with the detector If other models are to be used please consult...

Page 10: ...onsumption 3W Type of Gas Natural gas Alarm Threshold 6 LEL methane Life of the Sensor 5 years Ingress Protection IP30 Temperature 10 50 Relative Humidity 95 non condensing Material and Color ABS ivor...

Page 11: ...t apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product Anybody including the agents distributors or...

Page 12: ...st com cn www gst com cn GST UK Global System Technology PLC Enterprise Glade Bath Lane Moira South Derbyshire England DE12 6BD Tel 44 0 1283 225 478 Fax 44 0 1283 220 690 GST Dubai Global System Tech...