background image

 

30306067                                                                                                                                                                    Issue 1.02

 

                                       

 

Features 

 

Used as the base of detectors or as the sounder.   

Description 

C-9402  Conventional  Base  Mount  Sounder  (the 
sounder)  is  an audible  signal  appliance in  field,  used 
together with I-9308 module. When there is a fire, the 
sounder gives alarming sound to warn people. 

Connection and Cabling 

Fig. 1 shows terminals of the sounder. 

A

B

Mounting Hole

 

Fig. 1 

Refer to 

Application

 for connection. 

Recommended Cabling   

1.0mm

2

 or above fire cable, subject to local codes.   

Installation 

Warning: 

Before 

installing 

the 

sounder, 

disconnect the power from loop and verify that all 
the  bases  are  securely  installed  and  that  the 
cabling is correct on each base. 

1  Before  installation,  first  check  the  enclosure 
without  scrapes  and  distortion,  the  labels  should  be 
complete. 
2  Mounting of the sounder is shown in Fig. 2. 

Back Cover

Base

Sounder

Top Cover 
or Detector

Back Box

 

Fig.2   

 
 

 

 

 

 

3  Fix the sounder to the back box with screws. 
4  Align the orientation mark of the top cover to mark 
A (refer to Fig.1), rotate the sounder to align the mark 
with mark  B,  the top  cover  is installed. If it's  used  as 
detector base, take down the top cover and install the 
detector on it in the same method as mounting the top 
cover. 

Application 

The  sounder  can  be  used  as  a  base  to  install 
intelligent  heat  or  smoke  detectors  to  combine 
detection and alarm. It can also be used as a sounder. 

The audible control part of the sounder has two wires. 
Used  as  the  sounder,  it  needs  separate  wiring  to 
connect with detectors.

 

 

The sounder can be directly connected to I-9308 

module,  which  occupies  two  consecutive  address 
points. When there is fire alarm message, it activates 
low  address  to  give  pre-alarm  sound,  activates  high 
address  to  give  fire  alarm  sound.  System  wiring  is 
shown in Fig. 3. 

Sounder

Sounder

24VDC

Fi

re Al

arm

 Contro

Pa

ne

l

4

6

3

5

4

6

5

2

3

2

I-9308

D2

D1

Z1

L+

1

1

L-

Z2

 

Ω

 

Resistor

Fig. 3 

"5" of the sounder connects to "L+" of I-9308 module. 

"6" of the sounder connects to "L-" of I-9308 module. 
The  "5"  and  "6"  of  the  last  sounder  in  the  system 
should be connected with a 4.7k

Ω   terminal resistor.   

 

The sounder can also be used as detector base 

to mount different detectors, which can both detect fire 
and  give  audible  alarm  signal  to  realize  combined 
function.  Remove  the  top  cover  and  mount  the 
intelligent or conventional detector. 

 

 

C-9402

 

Conventional Base Mount Sounder 

 

All manuals and user guides at all-guides.com

all-guides.com

Reviews: