background image

* Dimensions furnished approximately 1/8 in. (3mm) undersize.

D*

Model SEFSDR-511 meets the requirements for fire 

dampers, smoke dampers and combination fire smoke 

dampers established by:

National Fire Protection Association 

    NFPA Standards 80, 90A, 92A, 92B 101 & 105

IBC  International Building Codes
New York City 

(MEA listing #260-91-M)

 

California State Fire Marshall
    

Listing #: 3225-0981:112 (fire)

     Listing #: 3230-0981:113 (smoke)

Application

Model SEFSDR-511 is a severe environment 316SS combination fire 

smoke damper with round style blade. The SEFSDR-511 has been 

qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for operation 

and dynamic closure in emergency fire smoke situations. Model  

SEFSDR-511 may be installed vertically (with blades running 

horizontal) or horizontally and is rated for airflow and leakage in 

either direction.

Ratings

UL 555 Fire Resistance Rating

 

 

Fire Rating:  1 1/2 Hour 

Dynamic Closure Rating: Actual ratings are size dependant 
 

Maximum Velocity:  3000 fpm (15.2 m/s) 

 

Maximum Pressure:  4 in. wg (1 kPa)

UL 555S Leakage Rating

 

 

Leakage Class:  I 

 

Operational Rating:  Actual ratings are actuator dependant 

 

Maximum Velocity:

 

3000 fpm (15.2 m/s) 

 

Maximum Pressure:  4 in. wg (1 kPa)

 

 

 

Maximum Temperature:  350º F (177°C) —Depending on actuator

Standard Construction
 

Frame/Sleeve: 

20 ga. (1mm) 316 stainless steel integral 

 

  sleeve 

 

Blade:

  Double skin 316 stainless steel (14 ga. 

 

  [2mm] equivalent) round style blade 

 

Seal:

  Extruded silicone rubber blade seal 

 

Axle:

  1/2 in. (13mm) dia. 316 stainless steel 

 

Bearing: 

316 stainless steel sleeve type 

 

Fusible Link: 

UL listed 165ºF (74ºC) -not 316SS

Size Limitations

 

Minimum Size:

  6 in. (152mm) diameter 

 

Maximum Size:

  24 in. (610mm) diameter

Optional Features

• OCI (Open closed indication switches) -not 316SS
• 165ºF (74°C), 212ºF (100°C), and 350ºF (177°C) RRL - not 316SS.
• TOR (remote override of 165º F (74°C) closure allows damper to 

perform smoke management functions during a fire emergency) -not 
316SS.

• Electric or pneumatic actuators to accomplish smoke management 

and system functions.

 

• One retainer plate required, additional retainer plate available
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve

SEFSDR-511

Combination Fire Smoke Dampers

Round Stainless Steel Blade

UL 555S Leakage Class I

UL555 1 1/2 Hour Fire Resistance Rating

“UL CLASSIFIED (see complete marking on 

product)”

“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”

 

Standard 555 (Listing #R13317)  

 

 

Standard 555S (Listing #R13447)

O 2 in.  Min.

1.00 in. Min. Typ.

Fasteners

Clamping

Screw

Nut

Retaining

Plate Assembly

Clamping Screw

Minimum Wall/Floor Opening

 = Nominal Dia. + 7/8 in. 

O 2 in.  Min.

1.00 in. Min. Typ.

Fasteners

Clamping

Screw

Nut

Retaining

Plate Assembly

Clamping Screw

Minimum Wall/Floor Opening

 = Nominal Dia. + 7/8 in. 

Installation instructions available at www.greenheck.com.