ZEOS C

FIRE ALARM DETECTOR

MANUAL 211109

MADE IN PORTUGAL - EU

GLOBAL FIRE EQUIPMENT S.A.

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL  | Tel: +351 289 896 560

Mail[email protected]  | Technical Support: [email protected]  | www.globalfire-equipment.com

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE

10V to 30V DC

CURRENT - QUIESCENT

Heat: 7 uA / Smoke: 33 uA / Smoke & Heat: 35 uA

CURRENT - DEVICE IN ALARM

24mA - Alarm LED illuminated

SENSITIVITY

According to EN54-5 or/and EN54-7

CABLE SIZE

0.5-2.5 mm²

RESET/START-UP TIMES

20 seconds max.

COLOUR / CASE MATERIAL / MAX. HUMIDITY

White / ABS / 95% RH Non-Condensing

NORMAL / TRANSIENT OPER. TEMPERATURE

0°C to 50°C / -10°C to 85°C

DIMENSIONS / WEIGHT

100 (D) x 50 (H) mm included base / 144 g inc. base

COMPATIBILITY

ORION, ORION MINI, ORION EX, ORION-PLUS, QUAD-ZMU and ZMU

ORDER CODE

DESCRIPTION

CERTIFICATE

ZEOS-C-S

PHOTOELECTRIC SMOKE DETECTOR

1328-CPR-0705

ZEOS-C-H

FIXED TEMPERATURE/HEAT DETECTOR

1328-CPR-0706

ZEOS-C-SH

MULTISENSOR SMOKE & HEAT DETECTOR

1328-CPR-0704

MECHANICAL SPECIFICATION

INSTALLATION

INSTALLING THE BASE
To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against terminals and fastening the
wires away from connector terminals. The detector base can be mounted directly onto most standard electrical junction boxes.

INSTALLING THE HEAD
Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on base. Fit the detector head onto
the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and activate the detection loop. Test the detectors as described
below.

TESTING
All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing.

SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When sufficient smoke has entered, the
detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear smoke out of the chamber before resetting in order to
keep the detector at its current sensitivity setting.

HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be met by some domestic hair
dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several cms, direct the airflow at the guard protecting the
thermistor. The detector should alarm within 60 seconds. Upon alarm immediately remove the heat source and check that the Red LEDs of the detector are illuminated.
If a detector fails to activate within 60 seconds, confirm connections and programming. If necessary, replace the unit.
NOTE: After testing, check that the system is returned to normal operation. Notify the appropriate authorities that the testing procedure has been completed and the
system is active again.

MAINTENANCE
The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power vacuum cleaner.

DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR.