The Ethernet Interface Module, IC695ETM001, connects a 

PACSystems RX3i controller to an Ethernet network. It enables 

the RX3i controller to communicate with other PACSystems 

equipment and with Series 90 and VersaMax controllers. The 

Ethernet Interface provides Transmission Control Protocol and 

Internet Protocol (TCP/IP) communications with other control 

systems, host computers running the Host Communications 

Toolkit or programmer software, and computers running the 

TCP/IP version of the programming software. These 

communications use the Service Request Transport Protocol 

(SRTP), Modbus TCP, and Ethernet Global Data (EGD) protocols 

over a four-layer TCP/IP (Internet) stack.  

Features of the RX3i Ethernet Interface include: 

▪ 

Full programming and configuration services. Firmware 

upgrades from the RX3i CPU using the WinLoader 

software utility, which is supplied with updates to the 

Ethernet Interface software. 

▪ 

Periodic data exchange using Ethernet Global Data (EGD). 

▪ 

EGD Commands to read and write controller and EGD 

exchange memory over the network. 

▪ 

TCP/IP communication services using SRTP. 

▪ 

Support for SRTP Channels, Modbus/TCP Server, and 

Modbus/TCP Client  

▪ 

Built-in Station Manager for on-line supervisory access to 

the Ethernet Interface. Dedicated Station Manager port. 

▪ 

Two auto-sensing 10Base T / 100Base TX RJ-45 shielded 

twisted-pair Ethernet ports for direct connection to either 

a 10BaseT or 100BaseTX IEEE 802.3 network without an external transceiver. There is only one interface to the 

network (only one Ethernet MAC address and only one IP address). 

▪ 

Internal network switch with Auto negotiate, Sense, Speed, and crossover detection. 

▪ 

Recessed Ethernet Restart pushbutton permits manually restarting the Ethernet firmware without power cycling 

the system. 

▪ 

LEDs: Ethernet OK, LAN OK, Log Empty, individual port activity and speed LEDs. 

▪ 

Configurable stand-alone Redundant IP addressing, which allows a single IP address to be assigned to 

corresponding Ethernet modules in two different controllers. The Redundant IP address is configured in 

addition to the normal unique IP address of each Ethernet module. Under application logic control, only the 

Ethernet module in the active unit can use the Redundant IP address. 

▪ 

Time synchronization to SNTP Time Server on Ethernet network (when used with Release 5.00 or later CPU 

module). 

*  Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their 

respective owners. 

Copyright © 2013-

 

2016 by General Electric Company. All Rights Reserved 

Summary of Contents for IC695ETM001-HW

Page 1: ...Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded twisted pair Ethernet ports for direct connection to either a 10BaseT or 100BaseTX IEEE 802 3 network without an external transceiver There is only one interface to the network only one Ethernet MAC address...

Page 2: ...on Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redundant...

Page 3: ... ETHERNET OK LAN OK LOG EMPTY Blink error code Off Off Hardware failure See chapter 11 for blink code definitions ETHERNET OK LAN OK LOG EMPTY Slow Blink Slow Blink Slow Blink All LEDs blink in unison pattern same while awaiting or performing load Firmware Update Field Wiring Station Manager RS 232 Port Pin Assignment Pin No Signal Direction Description 1 DCD IN Data Carrier Detect 2 TX OUT Transm...

Page 4: ...e enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of ...

Page 5: ...ule to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket into threaded holes in the bottom of the backplate and screw them several turns using a 1 Phillips screwdriver Tighten to 0 7 N m 6 in lbs Related Documents For additional information about the Ethernet Interface Module refer to the following publications GFK 2314 PACSystems RX3...

Page 6: ...ace module IC693CMM321 not supported by RX3i The Series 90 30 LAN Interface Module IC693CMM321 is not supported by the RX3i and should not be placed in an RX3i rack Series 90 30 CPUs with embedded LAN Interface IC693CPU364 and IC693CPU374 like any Series 90 30 CPU should not be placed in an RX3i rack Modbus TCP support Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channe...

Page 7: ...was made to prevent the module from becoming unresponsive and requiring a power cycle if it was subjected to heavy network storm traffic Reference GE Security Advisory is GE15 09 titled Network Storm Denial of Service In addition to the enhancement there were issues resolved Please refer to the Problems Resolved by This Release section above for more details IC695ETM001 HU 6 31 Nov 2015 Firmware r...

Page 8: ...hange to the module s firmware or functionality IC695ETM001 ES 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled IC695ETM001 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 7 IC695ETM001 EP 6 14 Jul 2012 Resolves an issue with a spurio...

Page 9: ...e connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is...

Page 10: ...ult can be safely ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout err...

Page 11: ...ference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink c...

Page 12: ... the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir1 and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4 ...

Page 13: ... is disabled until the station manager password is changed to other than the default password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K Changing the default Station Manager password is strongly recommended GE Intelligent Platforms strongly recommends...

Page 14: ...ess from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ethern...

Page 15: ...tain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeou...

Page 16: ...et interface time via the CHTIME command does not affect the timestamp value within EGD exchanges produced from this Ethernet interface The EGD timestamp value reflects the current CPU time In Series 90 70 products and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run Mode Store of EGD In a large PPS system r...

Reviews: