Installation Instructions for Models:

CR 135-2, CF 135-2, CR 165-2, CF 165-2, CR 200-2, CF200-2, CF 285-2

Description:

The “-2” series of heat detectors are described as alarm initiating devices, double circuit with

two

sets of Normally Open contacts.

The Model Number prefix “CR” indicates that the detector is a combination Rate-of-Rise and
Fixed Temperature, often referred to as “Dual-action”.  The Rate-of-Rise function allows the
detector

to close both sets

of its contacts when the temperature at the ceiling increases at a rate

of 8.4 Celsius degrees (15 Fahrenheit degrees) per minute. In most cases, the closure of one
set of contacts initiates the Fire Alarm sequence. The second set of contacts is commonly used
to initiate an ancillary function. The Fixed Temperature portion consists of a spring-loaded
plunger held in place by a eutectic solder that will fuse at the specific temperature (in F degrees)
as indicated by the Model Number i.e. 135,165,200 and 285 degrees.

The Model Number prefix “CF” indicates that the detector is Fixed Temperature Only, and will
therefore

not

respond to a rate of temperature increase but will operate when the detector fuses

at the prescribed temperature as indicated by the model number. This detector is referred to as
“Fixed Temperature Only, non-restorable”.

Location:

The “CR” series detectors are installed in areas where rapid increases in ceiling temperature

are not

expected. Such locations include dwelling units, storage cupboards, electrical closets,

material storage rooms, shafts (other than stairwells), transformer vaults, electrical rooms, and
sprinkler rooms.

The “CF” series detectors are installed in areas where rapid increases in ceiling temperature

are

expected.  Such locations include boiler rooms, industrial kitchens, commercial laundry

rooms, janitor closets, change rooms with shower facilities, and saunas.

It is important to consider ambient temperature conditions when selecting the detector’s fusing
temperature.  See Engineering Specification (below).

Engineering Specification

: Models CR 135-2, CR 165-2 and CR 200-2 detectors are

dual-action

type,

that will respond to a rate of temperature increase at the ceiling of 15 Fahrenheit degrees per minute
(8.4 Celsius degrees per minute).  These detectors will also respond when the fixed temperature (non-
restorable) threshold is exceeded.  Dual-action detectors are installed in areas where rapid fluctuations
in  ceiling  temperature  are

not

expected. In  areas  where  sudden  increases  in  ceiling  temperature  are

normal,  specify

Fixed  Temperature  Only

units  i.e.  CF 135-2, CF 165-2,  CF 200-2 or CF 285-2.

Detectors  shall  be  installed  in  areas  where  environmental  conditions  including  dust,  vapours,  insects,
etc., would cause an ionization or photoelectric type detector to initiate a false alarm.

*

assumes a flat, uninterrupted ceiling at a height not exceeding 10ft / 3m.

Model #

Function Type

Release Temp.

Temp. Rating
Range

Max. Installation
Temp

Color dot on fin

Spacing between
detectors*

CR 135-2

Dual-action

135

F / 57

C

Ordinary

100˚F / 37.8˚C

None

70ft / 21m

CR 165-2

Dual-action

165

F / 71

C

Ordinary

100˚F / 37.8˚C

Grey

70ft / 21m

CR 200-2

Dual-action

200

F / 93

C

Intermediate

150˚F / 65.6˚C

White

70ft / 21m

CF 135-2

Fixed Temp.

Only

135

F / 57

C

Ordinary

100˚F / 37.8˚C

Black

40ft / 12m

CF 165-2

Fixed Temp.

Only

165

F / 71

C

Ordinary

100˚F / 37.8˚C

Black and Grey

25ft / 7.5m

CF 200-2

Fixed Temp,

Only

200

F / 93

C

Intermediate

150˚F / 65.6˚C

Black and White

25ft / 7.5m

CF 285-2

Fixed Temp.

Only

285

F / 140

C

High

225˚F / 107.2˚C

Black and Blue

25ft / 7.5m