Installation Guide #06-128

                                      Rev. No.1  10/2001

20-040 and 20-046 COUNTDOWN TIMER

PRODUCT INFORMATION

Description

The Fike 20-040 & 20-046 Countdown Timers are accessory
units for use with Fike Fire Suppression Systems.  They are
designed to provide a visual representation of time prior to
release of the agent.  They require input from the Fike UL
listed control panel at the start of the pre-discharge state to
initiate their countdown sequence.  This countdown can
either be a polarity reversal signal or relay activation,
depending upon the wiring option selected. The countdown
sequence does not reflect abort conditions at the panel. The
timers are sold with manual release switches and/or abort
switches. They are provided with back box of appropriate
size.

SPECIFICATIONS

Input Voltage

24 VDC

Current Consumption

0 mA In Stand-by
160 mA  In Pre-discharge

Circuit Limitations

Class A or  B

Dimensions

See drawing

Weight

20-040        0.752 lbs  280.6 grams
20-046        1.128 lbs. 421.6 grams

Operating
Temperature

32

°

F to 120

°

F

0

°

C   to 49

°

C

Operating Humidity

10%  to  85% RH, non –
condensing

Installation Method

Assembly mounts to back-box
supplied with the individual unit.

Listings and
Approvals

U.L listed     S3217
F.M. Approved     OY4A4.AY
C.S.F.M.     6760-0900:103
M.E.A.     163-95-E

20-040 COUNTDOWN TIMER

WITH ABORT SWITCH

20-046 COUNTDOWN TIMER

WITH ABORT SWITCH & MANUAL RELEASE

INSTALLATION & CHECKOUT

1)  Disable the Control Panel Agent Release Circuit.
2)  Remove all power from the control panel.
3)  Connect the field wiring to the countdown timer

terminals according to the wiring diagram provided.(see
reverse side)

4)  Adjust the Countdown Timer ten’s and units settings for

the proper time that corresponds to the panel pre-
discharge countdown time.

5)  Terminate field wiring on the abort and/or manual

release switch(s).

6)  Apply power to the control panel. With the system

disarmed, test the system and verify the proper
operation of the timer. Make adjustment to timer units
settings to reflect accurate timing as per the control
panel. Test the operation of the abort and/or manual
release switch(s).

7)  Install the switch plate to the back-box.

OPERATIONS

When the control panel enters the pre-discharge state it
initiates the signal to start the Countdown Timer.  The timer
displays the countdown time as determined by the rotary
switch settings. After the time has elapsed, the L.E.D.
display will indicate ‘0’ until power is removed (silenced or
reset) thus resetting the timer.
The operation and installation of the Abort and/or Manual
Release Switch(s) is described in Installation Guide 06-230.

SAFETY NOTICES

Read all of the following warnings and

cautions before attempting to

install or use this device.

Personal injury or accidental

release of the suppression

system may result if these

warnings and cautions are not followed.

CAUTION

The Countdown Timer contains static sensitive

components.  Handle the timer by the edges only and avoid
touching the integrated components.  Keep the timer in the
protective static bag it was shipped in until time of
installation.  To prevent damage from static discharge,
always ground yourself with a proper wrist strap before
handling the Countdown Timer.

7 3/8"

( 18.73cm )

8 3/16"

( 20.80cm )

3 3/4"

( 9.53cm )

2 1/2"

( 6.35cm )

( 11.43cm )

4 1/2"

11 13/16"

( 28.42cm )

( 27 94cm )

11.0"

3 3/4"

( 9 53cm )

( 6.35cm )

2 1/2"

4 1/2"

( 11.43cm ) 