background image

 

 

SIGA2-HRS Intelligent Fixed-Temperature and 

Rate-of-Rise Heat Detector Installation Sheet 

 

 

Description

The Signature Series model SIGA2-HRS Intelligent Fixed-

Temperature and Rate-of-Rise Heat Detector is an intelligent 

device that contains a rate-of-rise and fixed-temperature heat 

sensor to detect fire. The heat sensor monitors the 

temperature of the surrounding air and the detector analyzes 

the data from the sensor to determine whether to initiate an 

alarm. The rate-of-rise heat function quickly detects a fast, 

flaming fire. The fixed-temperature heat function detects fire 

when the air temperature near the detector exceeds the alarm 

point. 

LED indicator. 

The LED indicator (see Figure 1 below) 

displays the following states: 

 

Normal: Green LED indicator flashes, no action. 

 

Alarm/active: Red LED indicator flashes, evacuate the 

area. 

 

Stand-alone alarm: Red LED indicator turns on, evacuate 

the area.

Figure 1: SIGA2-HRS features 

3

1

2

 

1.  Tamper-resist lever arm on base 

2.  Access slot for tamper-resist mechanism 

3.  LED indicator 

Installation  

Notes

 

 

This detector does not operate without electrical power. As 

fires frequently cause power interruption, discuss further 

safeguards with the local fire protection specialist. 

 

This detector does not sense fires in areas where heat 

cannot reach the detector. Heat from fires in walls, roofs, 

or on the opposite side of closed doors may not reach the 

detector. 

 

This heat detector by itself does not provide life safety 

protection. Use this detector with ionization or 

photoelectric smoke detectors, or both. 

 

This detector does not detect oxygen levels, smoke, toxic 

gases, or flames. Use this device as part of a broad-based 

life safety program which includes a variety of information 

sources pertaining to heat and smoke levels, 

extinguishment systems, visual and audible devices, and 

other safety measures. 

 

Independent studies indicate that heat detectors should 

only be used when property protection alone is involved. 

Never rely on heat detectors as the sole means of fire 

protection. 

 

To ensure proper operation, store the detector within the 

recommended ranges. Allow the detector to stabilize to 

room temperature before applying power. 

 

The dust cover (supplied) must remain on the detector 

during installation and be removed prior to commissioning 

and service. The dust cover is not a substitute for 

removing the detector during new construction or heavy 

remodeling. 

 

In Canada, install according to CAN/ULC-S524 

Standard 

for the Installation of Fire Alarm Systems,

 CSA C22.1 

Canadian Electrical Code

, and the local authority having 

jurisdiction. 

 

To permanently disable the tamper-resist mechanism prior 

to placing the detector in difficult to reach locations, break 

and remove the plastic lever arm from the base. See 

Figure 1, item 1. 

1 / 2 

© 2015 Griya Teknik Fire & Security. All rights reserved. 

Reviews: