background image

  Q U I C K

  I N S T A L L  

G U I D E

 

PREPARATION

A )  Download the Enphase Installer Toolkit mobile app and 

open it to log in to your Enlighten account. With this app, 

you can connect to the Envoy-S to track system installa-

tion progress. To download, go to 

enphase.com/toolkit

 or 

scan the QR code at right.

B)  Check the box for the following items:

• 

Enphase AC Combiner Box with Envoy-S

• 

Ferrite bead to attach to your Ethernet Cable, if used

• 

Enphase AC Combiner Box Quick Install Guide

 (this document)

C )  Make sure you have the following 

required

 items:

• 

Plan to use screwdriver, pliers, and torque wrench.

• 

Provide overcurrent protection in the load center in accordance with 

NFPA 70, §705.12.

• 

Provide suitable mounting hardware: use screws that are long 

enough to secure the unit to the vertical mounting surface

• 

Use copper conductors rated for wet locations and sized to meet 

local code requirements and voltage drop/rise considerations. 

(Breakers are rated for 14-6 AWG copper, and output lugs are rated 

for 14-4 AWG copper).

• 

Use only UL Listed rain-tight or wet location hubs for wire entry into 

the enclosure.

D )  If you plan to do consumption metering:

• 

Make sure you have two split-core consumption metering CTs (order 

CT-200-SPLIT).

• 

Check that there is enough space in the load center to install CTs. 

Do not install the CTs in a panel where they exceed 75% of the wiring 

space of any cross-sectional area within the load center.

E )  Decide how to connect the Envoy-S to the Internet: Use Wi-Fi, an En-

phase Mobile Connect modem, or Ethernet. Then, make sure you have 

the following optional items, if needed:

• 

Enphase Mobile Connect modem [order CELLMODEM-01 (3G) or 

CELLMODEM-03 (4G)]

• 

Ethernet over power line communication (PLC) bridge with Ethernet 

cables (order EPLC-01)

• 

Ethernet cable: 802.3, Cat5E or Cat6, unshielded twisted pair (UTP). 

Do not use shielded twisted pair (STP) cable.

F )   Create a paper installation map to record device serial numbers and 

positions in the array. You will scan this map later using Installer Tool-

kit and your mobile device.

• 

Peel the removable serial number label from each device and affix it 

to the respective location on the paper installation map. 

• 

Write the Envoy-S serial number on the paper installation map. Later, 

you will need to enter this number in Installer Toolkit. You can type it 

in manually or scan the label on the inside of the AC Combiner door.

• 

Always keep a copy of the installation map for your records and to 

upload to Enlighten later.

G )  

Note that installation of the Combiner has two parts.  

To ensure successful device detection, complete Part 2 after install-

ing any Enphase Microinverters and/or Enphase AC Battery(ies).

Note

If needed, you can find an installation map at the back of any 

Enphase Microinverter Quick Install Guide.

IMPORTANT: This guide is for model XAM1-120-B / 880-00834 ONLY. Check model 
number on unit. Wiring instructions differ depending on the model number. 

Envoy-S Display and Controls

Network Communications LED 

Green when Envoy-S is connected  

to Enlighten.

AP Mode LED

Green when Envoy’s AP Wi-Fi network  

is available.

AP Mode Button

Press to enable Envoy’s AP Mode  

for connecting with a mobile device.  

Hold for 5 seconds to start WPS  

connection to a router. 

Power Production LED 

Green when microinverters are  

producing power.

Device Communications LED

Green when devices are  

communicating with Envoy-S.

Device Scan Button

Press to start/stop 15 minute scan for  

devices over the power line.

Track system installation progress with the Enphase Installer Toolkit mobile app. 

The LEDs on the Envoy-S are solid green when a function is enabled or performing  

as expected, flashing when an operation is in progress, or solid amber when  

troubleshooting with Installer Toolkit is required. For a legend of all LED states,  

see Troubleshooting

a

.

Enphase Installer 

Toolkit mobile app

How It Works

POWER LINE  

COMMUNICATIONS

NETWORK  

COMMUNICATIONS

M-Series or S-Series 

Microinverters

AC Combiner  

with Envoy-S

Load

Center

Router

Enphase 

Enlighten™

To Internet

Installing the 

Enphase AC Combiner Box

The Enphase AC Combiner Box™ combines up to three AC branch circuits of Enphase AC Batteries, M-Series Microinverters and/or S-Series Microinverters. To 

install the Enphase AC Combiner Box, read and follow all warnings and instructions in this Guide and in the 

Enphase Envoy-S Installation and Operation Manual

 

at: 

enphase.com/support

. Safety warnings are listed on the back of this guide. If you do not fully understand any of the concepts, terminology, or hazards out-

lined in these instructions, refer installation to a qualified electrician or installer. These instructions are not meant to be a complete explanation of a renewable 

energy system. All installations must comply with national and local electrical codes. Professional installation is recommended.
The AC Combiner Box is an outdoor-rated, NRTL-certified NEMA type 3R, polycarbonate enclosure containing an Enphase

 

Envoy-S™, circuit breakers, and wiring 

for Envoy-S connections. 

Enphase AC Batteries

Summary of Contents for AC Combiner Box

Page 1: ...allation map for your records and to upload to Enlighten later G Note that installation of the Combiner has two parts To ensure successful device detection complete Part 2 after install ing any Enphase Microinverters and or Enphase AC Battery ies Note If needed you can find an installation map at the back of any Enphase Microinverter Quick Install Guide IMPORTANT This guide is for model XAM1 120 B...

Page 2: ...he dead front over the location of the removed breaker K Use a screwdriver and the two provided screws to secure the plate into place 3 Locking tabs INSTALLATION Part 1 You can complete Installation Part 1 before or after installing the PV system Choose a location for the AC Combiner Box A Install the AC Combiner Box in a readily accessible location The best practice is to install at least four fe...

Page 3: ...nto consideration the voltage drop rise and upstream breaker or fuse B The two DIN rail terminal blocks above the circuit breakers are the output connections Install the black wire into the lower terminal block and the red into the upper terminal block C Torque to 14 in lbs 1 6 Nm D Connect the neutral white to the neutral busbar E Connect the ground green or green yellow to the Ground busbar and ...

Page 4: ... do this you must create a protected route using conduit for the CT wires from the main load center to the Envoy S If you need to extend the wires refer to the Enphase Envoy S Installation and Operation Manual at enphase com support 7 Note Because of variance in load center design and main power feed there may not always be enough space to install consumption metering CTs DANGER Risk of electrocut...

Page 5: ... Device Communications LED flashes green while scanning solid green when all the devices you installed are communicating or solid amber if any devices are not communicating With both methods If the Device Communications LED remains solid amber see Troubleshooting b Verify System Configuration While still connected to the Envoy S with Installer Toolkit check the Over view screen for the following A...

Page 6: ...r network from the list of available networks If the wireless router does not support WPS you may be prompted to enter a password The Network Communica tions LED begins flashing green Within three minutes the Network Communications LED lights solid green indicating a successful connection to Enlighten If the Network Communications LED remains off or lights solid amber see Troubleshooting d Method ...

Page 7: ... steps Make sure that the broadband router is operational by checking that other devices at the site can access the network Be aware that metal enclosures or obstructions impede wireless communication If you cannot see your router or access point in the list on the Envoy or cannot maintain a connection it may be necessary to add a wireless repeater to extend the network range If you are using Wi F...

Page 8: ... Combiner Box read all instructions and cautionary markings in the technical description and on the equipment WARNING Use the circuit breakers in the Enphase AC Combiner Box only for serving Enphase equipment No other loads are allowed FCC Statement This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are ...