TX-Series

 

Quick Start Guide

 

Certifications and Specifications

 

Wiring Diagram

 

Installation Notes

 

TX-Series products can be used on both linear and rotary valve automation 

applications. Always use sound mechanical practices when mounting. When 
fastening the 

TopWorx™ 

Switchbox to the bracket on the actuator, torque t he 

fasteners to 8 ft·lbs (10.8 N·m) after cycling the valve a couple of times. This 
allows the shaft to self-center in the pinion slot, or coupler. Be cautious not t o 
allow undue axial (thrust) load on the shaft.

 

This  product  comes  shipped  with  conduit  covers  in  an  effort  to 
protect  the  internal  components  from debris during shipment and 
handling.  It  is  the  responsibility  of  the  receiving  and/or  installing 
personnel  to  provide  appropriate  permanent  sealing  devices  to 
prevent the intrusion of debris, or moisture, when stored outdoors or 
when installed. 

It  is  the responsibility of  the installer, or  end  user, to  install t his  
product in accordance with the National Electrical Code (NFPA 70), 
or  any other national or regional code defining proper practices.

 

Factory Preset

 

All 

TopWorx™

  products  are  factory  set  for  90°  rotation  on  normal  acting 

actuators. The switch at full clockwise is for process valve closed 

and uses 

the  red  striker.  When  changing  orientation,  the  target  disk  will  must  be 
relocated for your application. The target is designed to be adjusted on 90° 
increments allowing the 

TopWorx™

 unit to be rotated 90°, 180°, or 270° from 

standard. On reverse acting units, the switch function will be transposed.

 

Clockwise for open will become clockwise for closed. On units with indicator 
domes, the dome cover with mask must be rotated to 

give proper indication.

 

Switch Calibration Procedure

 

Never  perform  the  switch  calibration procedure while in an area 
that  could  be  hazardous. 

On  Intrinsically  Safe  models,  the unit 

must be wired  in  accordance  with  the  control  drawing  included 
with  t

he product.

 

For  Options  D,  S,  L,  M,  K,  T,  P,  R,  AS,  &  PB,  calibration  may  be  performed 
using a Volt-Ohm meter by using the Ohm setting across COM and NO. When 
switch  is  active,  the  meter  will  read  <1.0  Ohms,  or  the  Diode  setting  may  be 
used 

simply to indicate c

ontinuity. If a  direct power source is being used, an 

appropriately  sized  resistor  must  be  used  in  series  with  the  contacts,  or 
permanent damage will occur.

 

For all INDUCTIVE sensor options, a power source and resistors will be required 
for calibration. (Refer to the product nameplate for current limitations.)

 

Setting Switches

 

GO™

  Switch,  Mechanical  Switches,  Reed  Switches, AS-i, Profibus, & ALL 

threaded, cylindrical inductive sensor options (except the D & S options).

 

Each  TX-Series  unit  is  equipped  with  2  or  4  adjustable  targets  with  a  usable 
range between 45° and 90°. For normal acting applications, the targets are color 
coded red for closed and green for open. The color code would be reversed for 
reverse  acting units. After installing the unit on the actuator or valve assembly, 
the targets must be set.

 

Normal Acting Actuator:

 

Step 1:  Rotate the valve full clockwise to the closed position. 

 

Step 2:  Unlock/push/twist the target as required to engage the switch and 

lock target, if applicable.

 

Step 3:  Rotate the valve full counterclockwise to the open position.

 

Step 4:  Unlock/ push/twist the target as required to engage the switch and lock 

target if, applicable.

 

Reverse Acting Actuator:

 

Step 1:  Rotate the valve full clockwise to the open position.

 

Step 2:  Unlock/push/twist the target as required to engage the switch and

  lock target, if applicable.

 

Step 3:  Rotate the valve or push and move the target a full counterclockwise to

  the closed position.

 

Step 4:  Unlock/push/twist the target as required to engage the switch and 

lock target if, applicable

.

 

For Switching Angle Under 45° (not applicable for D & S options): 

When the switch box is mounted to a linear

 

actuator or when the actuator strokes 

less than 45°, we recommend the 
following:

 

Step 1:  Remove shaft from

 

Switchbox by removing

 

the circlip underneath the 

Switchbox.

 

Step 2:  Remove the circlip underneath the cam, if equipped, then push the

cam  down the shaft by 3-4mm and turn it 90°.

 

Step 3:  Push the cam back up, you will see the flats fit snugly between the

  locating lugs inside the hub.

 

Step 4:  Replace the circli

p

.

 

Step 5:  Remove the closed switch from the bracket and install it on the inside of 

the bracket next to the open switch

.

 

To Re-Assemble (not applicable for D & S options):

 

Step 1:  Replace the screws with M3 X 25mm long screws (insert through both 

switches and bracket and fasten with the nut on the inside closest to the 
switch box bearing).

 

Step 2:  Remove the Closed striker assembly (red) by removing the circlip or 

screw on top and install it on the inner rack.

 

Step 3:  Unlock target and twist the green striker to the other end of the 

cam’s

 

rack and lock target. (The red striker assembly should be twisted to 
the  other end of the inner rack).

 

Step 4:  Re-install the shaft in the switch box and fit the s/s washer and circlip to 

the underside of the switchbox.

 

Step 5:  The switches can now be set anywhere between 0°& 45°.

 