background image

 

 

Specification for SiteGate-E

 

 

 

 

 

DESCRIPTION: 

The SiteGate-E provides communications between a SiteScan workstation and a control 

module network (ARC156) consisting of up to 32 control modules. The SiteGate-E provides one Ethernet 

Console Port and one serial port for direct connection. The Ethernet port is designated meets the IEEE 

802.3 standard.  The serial console ports are switch selectable for baud rates up to 38.4k bps.  

Communication between the SiteGate-E and the ARC156 network is provided through an EIA-485 port.

 

 

DIMENSIONS: 

  

Module: 

7 1/8" H x 6 1/4" W X 1 5/8” D 

 

 

18.10cm H x 15.88cm W X 4.13cm D 

 

 

Enclosure:  

12”H x 14.25" W x 2.85" D 

 

(painted steel) 

419.1mm x 301.3mm x 78.6mm 

 
 

See Enclosure Diagrams for mounting options. 

 

POWER:  

 

24 VAC ±10%, 50-60 Hz, 7.2 VA.

 

 

ENVIRONMENTAL  
OPERATING RANGE:

  0 to 130°F (-17.8 to 54.4°C); 10 to 90% relative humidity, non-condensing. 

For UUKL Smoke Control Systems, 32°-120.2°F (0°-49°C); 10 to 85% relative 

humidity, non-condensing. 

  

Liebert Corporation

 

Page 1 of 8 

SL-27314 Rev. 4: 7/03 

Summary of Contents for SiteGate-E ARC156

Page 1: ...baud rates up to 38 4k bps Communication between the SiteGate E and the ARC156 network is provided through an EIA 485 port DIMENSIONS Module 7 1 8 H x 6 1 4 W X 1 5 8 D 18 10cm H x 15 88cm W X 4 13cm D Enclosure 12 H x 14 25 W x 2 85 D painted steel 419 1mm x 301 3mm x 78 6mm See Enclosure Diagrams for mounting options POWER 24 VAC 10 50 60 Hz 7 2 VA ENVIRONMENTAL OPERATING RANGE 0 to 130 F 17 8 t...

Page 2: ...s Switch selectable baud rates ARC156 9600 or 38 4bps Recommended wire is MAGNUM Cable pn A3 ARC 156 2 MEMORY 1 MB flash 1 MB RAM BATTERY Seven year lithium battery provides a minimum of 10 000 hours of data retention during power outages FAULT DETECTION Hardware watchdog timer PROTECTION Built in surge and transient protection circuitry Liebert Corporation Page 2 of 8 SL 27314 Rev 4 7 03 ...

Page 3: ...its data over ARC156 network CMnet Receive lights when SiteGate E receives data from the ARC156 network Console Transmit TX lights when the Console port transmits data Console 2 Receives RX lights when the Console port receives data Link lights when the Ethernet port is connected Lan lights when the Ethernet port is active MODULE DIMENSIONS AND LAYOUT Liebert Corporation Page 3 of 8 SL 27314 Rev 4...

Page 4: ...on for SiteGate E COMMUNICATIONS WIRING DIAGRAM 18 24 ga Twisted Pair Shielded Low Impedance Low Capacitance Recommended wire is Magnum Cable A3 ARC 156 2 24VAC Liebert Corporation Page 4 of 8 SL 27314 Rev 4 7 03 ...

Page 5: ...Specification for SiteGate E Liebert Corporation Page 5 of 8 SL 27314 Rev 4 7 03 POWER WIRING DIAGRAMS ...

Page 6: ...Specification for SiteGate E ENCLOSURE DIMENSIONS Liebert Corporation Page 6 of 8 SL 27314 Rev 4 7 03 ...

Page 7: ...Specification for SiteGate E Enclosure Wall Mounting Liebert Corporation Page 7 of 8 SL 27314 Rev 4 7 03 ...

Page 8: ...Specification for SiteGate E Enclosure Floor Mounting Liebert Corporation Page 8 of 8 SL 27314 Rev 4 7 03 ...

Reviews: