Operating instruction 

Pressure Controls Series CS1 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

  

Date: 06.03.2020

 

Am Borsigturm 31 I 13507 Berlin I Germany 

CS1_OI_EN_DE_FR_ES_IT_RU_0320_R03_866914.docx 

G e n e r a l   i nf o r ma t i o n : 

For application in refrigeration systems in compliance 

with standard EN 378. 

A professional and appropriate storage and allocation 

of the devices is mandatory. 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure 

to comply can result in device failure, system 

damage or personal injury. 

 

According to EN 13313 it is intended for use by 

persons having the appropriate knowledge and 

skill.  

 

Before opening any system make sure pressure in 

system is brought to and remains at atmospheric 

pressure.  

 

Before installation or service disconnect all 

voltages from system and device.  

 

Do not exceed the specified maximum ratings for 

pressure, temperature, voltage and current.  

 
F u n c t i o n : 

 

CS1 Pressure switches are equipped with SPDT snap 

action contacts switching from 1-2 to 1-4 on rising 

and from 1-4 to 1-2 on falling pressure. Reaching the 

preset switch point on rising pressure, contact 1-2 

opens while contact 1-4 closes and vice versa on 

falling pressure. 

 

Fig.1  

 

 
M o u n t i n g   d i r e c ti o n : 

 

Any direction except upside down. 

 

I n s t a l l a t i o n   ( Fi g . 2 &4 ) :  

 

CS1 may be installed by using a mounting plate or as 

a wall-mounted device against a flat surface. 

 

Use universal thread M4 or UNC8-32 mounting 

holes for installation via mounting plate. 

 

Use the standard mounting holes at the backside for 

wall mounting. 

 

Use mounting screws supplied with control. 

 

Mounting screws must not penetrate control backside 

by more than 8 mm to ensure proper operation. 

 

Do not use CS1 in pulsating operating conditions! 

Minimize vibrations in the piping lines by 

appropriate solutions. 

 

In order to achieve protection class  IP33, the 

following instructions must be observed: 

Cover must be closed and cover screw fastened. 

Control must be mounted against a flat surface so 

that all openings on the housing backside are fully 

covered. 

Cable grommet (Fig.4, No.5) is sealing the cable 

entry to the housing 

 

P r e s s ur e   c o n ne c t i o n   ( Fi g . 3 ) :    

 

Do not apply torsional load to pressure connector; 

use second spanner to counter-balance torque when 

tightening pressure connection. High pressure 

versions are equipped with a snubber to dampen 

pulsations.  

 

When connecting CS1 to the hot gas line of a 

refrigeration system, a pipe or high-pressure hose of 

at least 80 mm shall be used to allow sufficient 

temperature drop between refrigeration line and 

pressure switch bellows. 

P r e s s ur e   t e s t :  

After completion of installation, a test pressure must be 

carried out as follows: 

according to EN378 for systems which must comply 

with European pressure equipment directive 

2014/68/EU 

to maximum working pressure of system for regions 

out of Europe 

Warning: 

 

Failure to do so could result in loss of refrigerant 

and personal injury. 

 

The pressure test must be conducted by skilled 

persons with due respect regarding the danger 

related to pressure. 

 
T i g h t n e s s   t e s t : 

Conduct a tightness test according to EN 378-2 with 

appropriate equipment and method to identify leakages 

of external joints. The allowable leakage rate must be 

according system manufacturer’s specification. 

 

E l e c t r i c a l   c o n ne c t i o n : 

 

Entire electrical connections have to comply with 

local regulations.  

 

Wire size must match the electrical load 

connected to the switch contacts. 

 

Feed cables through rubber grommet at switch 

bottom (Fig.4, No.5). 

 

Optionally, the rubber grommet may be replaced by 

a standard PG 13.5 cable gland. 

 

Connect wires to terminals (Fig.4, No.3) by taking 

into account switch functions as shown in Fig.1 

 

Fasten terminal screws with torque 1.2 Nm max. 

 

Warning: CS1 might not be suitable for 

connection to electronic controllers with low 

electrical loads (voltage <24 V  and  current 

<50 mA). 

 
S e t p o i n t   a d j u s t me n t   ( F i g . 4 & 5 ) : 

 

CS1 pressure switches come with individually 

adjustable range and differential depending on the 

exact model. 

 

Use a flat screw driver or a ¼” refrigeration (square) 

wrench to adjust setpoints as described below. 

 

Adjust upper setpoint using the range spindle (Fig.4, 

No.1). 

 

Adjust lower setpoint by turning the differential 

spindle (Fig.4, No.2). 

Upper setpoint – Differential = Lower setpoint 

Fig.5a/5b 

(1) Upper setpoint 

(5) Upper setpoint 

(2) Lower setpoint 

(6) Lower setpoint 

(3) Differential 

(7) Differential = variable 

(8) Turning range spindle

 

(9) Turning differential spindle 

 

A separate accurate gauge must be used for exact 

adjustment of the setpoints. The integrated display 

scale can only be used for obtaining approximate 

settings. Maximum cut-out level must be as follows: 

System with single protection device: At PS of 

system minus tolerances. 

System with two individual protection devices: At 

0.9*PS of system. 

 

When changing the upper setpoint the lower setpoint 

must be re-checked. 

 

Refer to the Technical Bulletin for standard factory 

settings.  

C h e c k- o u t   l e v e r   ( F i g . 4 ,   N o . 4 ) : 

 

Use the check-out lever to manually override the 

electrical contact position for testing out the system. 

 

S e r v i c e   /   Ma i n t e na n c e : 

 

Defective CS1 must be replaced, they cannot be 

repaired. 

 

T e c h ni c a l   d a ta :   

Protection class 

(IEC 529/EN 60529) 

IP33 

 

Ambient temperature 

(housing) 

-25°C…+70°C 

Max. relative humidity 

95% non-condensing 

Storage / transportation 

temperature 

-50°C…+70°C 

Medium temperature TS 

-25°C…+150°C 

 

Vibration resistance 

(acc. EN12263) 

1g (10...150 Hz) 

Electrical rating 

Resistive load (AC1) 

Inductive load (AC15) 

Inductive load (DC13) 

 

 

24A / 230V AC 

10A / 230V AC 

0.1A / 230V DC 

144A / 120 / 240 VAC  

24A / 120 / 240 VAC 

Use proper fuse for short circuit case by considering 

above voltages/currents 

Medium compatibility 

R744, R410A 

Standards:

 

 

EN 12263 

 

PED 2014/68/EU, Category IV for all devices 

with TÜV approval under EN12263 

 

LVD 2014/35/EU, EN 60947-1, EN 60947-5-1 

Marking: 

 

 0035 marking for devices under PED

 

 

 marking for devices under LVD

 

 

T y pe   c o d e : 

      CS1– 

 

 

 

e.g.

CS1-  W  6  A 

 

Function 

 

W = High Pressure limiter, automatic,  

 

        TÜV/ EN12263 approval (PSH) 

 

Pressure range

 

Pressure setting  

range

 

Max. allowable 

Pressure (PS)

 

Test Pressure 

(PT)

 

6 = 10…45 bar

 

70 bar

 

77 bar

 

7 = 15…65 bar

 

70 bar

 

77 bar

 

 

Pressures are relative (gauge pressure). 

 

Pressure connection (Fig. 3) 

 

A=7/16”-20 UNF male  

 

 

 

Summary of Contents for Alco Controls CS1 Series

Page 1: ...ue respect regarding the danger related to pressure T ig htne ss te st Conduct a tightness test according to EN 378 2 with appropriate equipment and method to identify leakages of external joints The allowable leakage rate must be according system manufacturer s specification E l ec tri ca l c o nne c tio n Entire electrical connections have to comply with local regulations Wire size must match th...

Page 2: ...ng ist mit geeignetem Gerät und Methode gemäß EN 378 2 so durchzuführen dass Leckstellen sicher entdeckt werden E l e ktr i sc he r Ansc hl uss Für den gesamten elektrischen Anschluss sind die länderspezifischen Vorschriften einzuhalten Kabel verwenden das für den Strom des am CS1 angeschlossenen Gerätes geeignet ist Kabel durch Öffnung in das Gehäuseinnere führen Fig 4 Nr 5 Installation mit PG13 ...

Page 3: ...ipement et une méthode appropriée pour identifier les fuites de joints externes Le taux de fuite admissible doit être conforme aux spécifications du fabricant du système Co nne xio n él ec tr i que Le raccordement électrique doit être conforme aux normes électriques locales La sélection des conducteurs doit être adaptée à l intensité du circuit Passer les câbles par le passe fils caoutchouc au bas...

Page 4: ... La prueba de presión debe ser llevada a cabo por personal capacitado y consciente de los peligros que implica este tipo de operaciones T e st de f uga Realice un test de estanqueidad según determina la EN 378 2 con el apropiado equipo para identificar fugas en las diferentes uniones El ratio máximo de fuga debe ser establecido por el fabricante del sistema Co ne xió n el éc tr ic a Las conexiones...

Page 5: ...alla EN 378 2 utilizzando attrezzature e modalità idonee per identificare perdite dalle giunzioni Il tasso di perdita ammissibile deve essere in accordo alle specifiche del costruttore del sistema Co l leg a me nti e le ttr ic i I cablaggi elettrici devono essere conformi alle normative locali La sezione dei cavi deve essere in funzione della corrente delle apparecchiature collegate al CS1 Nella p...

Page 6: ...ным персоналом при этом необходимо принимать во внимание опасность высокого давления Испытание на герметичность Для определения наличия утечек необходимо провести испытание на герметичность в соответствии с требованиями EN 378 2 Допустимый уровень утечек должен соответствовать спецификации изготовителя системы Эл е кт рич е ски е п од кл ючен и я Электрические подключения необходимо производить в ...

Page 7: ...imate Technologies GmbH www climate emerson com en gb Date 06 03 2020 Am Borsigturm 31 I 13507 Berlin I Germany CS1_OI_EN_DE_FR_ES_IT_RU_0320_R03_866914 docx Fig 2 Fig 3 Fig 4 1 2 3 4 5 Fig 5a Fig 5b 1 8 2 6 7 5 3 9 ...

Reviews: