1. SAFETY REGULATIONS AND NOTES

Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.

1.1 Levels of hazard warnings

1

1.1 Levels of hazard warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.

WARNING

Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualification

1

1.2 Staff qualification

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by qualified, trained and authorised
technical staff.
Only authorised specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:

;

Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.

1.4 Electrical voltage

1

1.4 Electrical voltage

;

Check the electrical equipment of the device at regular intervals, refer
to chapter 5.2 Safety test.

;

Replace loose connections and defective cables immediately.

DANGER
Electrical load on the device

Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically

charged device.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

2

1.5 Safety and protective functions

2

1.6 Electromagnetic radiation

2

1.7 Mechanical movement

2

1.8 Emission

2

1.9 Hot surface

2

1.10 Transport

2

1.11 Storage

2

1.12 Disposal

3

2. PROPER USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Technical features

5

3.4 Mounting data

5

3.5 Transport and storage conditions

6

4. CONNECTION AND START-UP

6

4.1 Connecting the mechanical system

6

4.2 Connecting the electrical system

6

4.3 Connection of the cables

8

4.4 Connection screen

9

4.5 Checking the connections

9

4.6 Switch on device

9

4.7 Switching off the device

9

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE

CAUSES AND REMEDIES

10

5.1 Cleaning

10

5.2 Safety test

Item no. 11280-5-9970 · Revision 82623 · Release 2014-05-08 · Page 1 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R4E450-AB09-06

Страница 1: ...uthorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Страница 2: ...t DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all p...

Страница 3: ...use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasi...

Страница 4: ...5 mm 6 x brass lead tips crimped 2 Accessory part inlet nozzle 63045 2 4013 not included in the standard scope of delivery other inlet nozzles on request 3 Depth of screw max 12 mm Item no 11280 5 997...

Страница 5: ...tor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor protection Thermal overload protector TOP brought out Cable exit Variable Protection class I if prot...

Страница 6: ...the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accorda...

Страница 7: ...ipped with thermal overload protectors to protect the devices Check to make sure that the thermal overload protector is correctly connected before each operation Failure to connect up the thermal over...

Страница 8: ...ns 4 4 Connection screen TOP 2 x grey U1 blue Z brown U2 black PE green yellow Item no 11280 5 9970 Revision 82623 Release 2014 05 08 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfi...

Страница 9: ...e minutes after disconnecting the voltage at all poles before opening the device CAUTION Electrical load on the capacitor after device is switched off Electric shock risk of injury Discharge the capac...

Страница 10: ...be tested How to test Frequency Which measure Check the protective casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or rep...