 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1848

Champ LED Floodlight

NFMVA20L/25L LED Fixtures

Installation & Maintenance Information

IF 1848 • 03/19                                                          Copyright

®

 2019, Eaton’s Crouse-Hinds Division 

                                                    Page 1

WARNING

To avoid the risk of fire, explosion or electric shock,

 this product should be 

installed, inspected and maintained by a qualified electrician only, in accordance 

with all applicable electrical codes.

WARNING

To avoid electric shock:

• 

Be certain electrical power is OFF before and during installation and 

maintenance.

• 

Floodlight must be supplied by a wiring system suitable per local code with 

an equipment grounding conductor.

To avoid burning hands:

• 

Make sure LEDs and drivers are cool to touch when performing 

maintenance.  

WARNING

To avoid explosion:

• 

Make sure the supply voltage is the same as the rated floodlight voltage.

• 

Do not install where the marked operating temperatures exceed the 

ignition temperature of the hazardous atmosphere.

• 

Do not operate in ambient temperatures above those indicated on the 

floodlight nameplate.

• 

Use only replacement parts from Eaton’s Crouse-Hinds Division.

• 

Use proper supply wiring as specified on the floodlight nameplate.

• 

All surfaces must be clean.

• 

LED compartment non-serviceable.  Do not open.

• 

Before opening wiring compartment, electrical power to the floodlight 

must be turned off and area must be free from hazardous atmosphere.  

Keep tightly closed when in operation.

• 

To minimize the risk from electrostatic discharge, when cleaning, wipe the 

lens with a clean, damp cloth.

INSTALLATION

Mounting
 

Yoke Mount - Wall Mount Using Floodlight Yoke Only

1. 

Using floodlight yoke as a template, mark and drill desired location on mounting 

surface.

2. 

Secure floodlight yoke to surface using ½” bolts or lag screws (not provided).

WIRING

 

Wiring the Floodlight

1. 

Open back cover/heat sink by loosening nine (9) #10-24 x 0.75” stainless steel 

cover screws using a 5/16” nut socket or flat head screwdriver (see Figure 1).  

The heat sink cover should be removed by pulling back on one corner of the top 

most edge to prevent damage to gasket.

NOTE: 

To avoid pinching hazard between heat sink cover and driver housing, ensure 

that floodlight is oriented in vertical position before, and during, wiring procedure.

2. 

All components in the fixture are pre-wired so only line in, neutral and ground 

need to be connected in the fixture using the supplied Wago connectors, using 

methods that comply with all applicable codes.  See Figure 2 for wiring diagram.

• 

Wire range from AWG 18-14 (0.75 - 2.5mm²) for neutral, and line (strip 

length 0.43” [10.9mm]), and AWG 16-14 (1.5 - 2.5mm²) for ground 

connections (strip length 0.43” [10.9mm]).

• 

Entries to driver housing shall be sealed, using HTL or STL, with 

devices rated a minimum of IP66.

• 

Standard openings are M20, M25 or 3/4” NPT.

• 

Optional openings are M20 (20mm) and/or M25 (25mm).

• 

Secure all electrical connections and wiring entry glands.

• 

Ensure that the following lengths for field wiring, internal to the driver 

housing compartment, are followed:

      – 4.5” ± 0.25” (114 ± 6mm) for ground wire

       – 2.5” ± 0.25” (64 ± 6mm) for neutral wire

       – 2” ± 0.25” (51 ± 6mm) for line in wire

APPLICATION

LED floodlight construction is designed for use indoors and outdoors in marine and wet 

locations, where moisture, dirt, corrosion, vibration and rough usage may be present.

NFMV:

IECEx:

• 

IEC, ATEX:

• 

IECEx UL 15.0029X

• 

DEMKO 15 ATEX 1377X

• 

DEMKO 15 ATEX 1383

• 

Ex ec IIC T4 Gc Tamb -40°C to +55°C

• 

Ex tb IIIC T81C Db Tamb -40°C to +40°C

• 

     II 3 G Ex ec IIC T4 Gc Tamb -40°C to +55°C

• 

     II 2 D Ex tb IIIC T81C Db IP66 Tamb -40°C to +40°C

Refer to the floodlight nameplate for specific classification information, maximum 

ambient temperature suitability and corresponding operating temperature (T-number).

IEC STANDARDS:

• 

IEC 60079-0:2011+ Corr.1(2012-01) + Corr. 2 (2013-12) + I-SH 01 (2013-11) + I-SH 

02 (2014-10) / EN 60079-0:2012 + A11:2013

• 

IEC 60079-7:2017/ EN 60079-7:2015

• 

IEC 60079-31:2013/ EN 60079-31:2014

• 

IEC 60598-1:2008/EN60598-1:2008

• 

IEC 60598-2:2008/EN60598-2:2008

• 

IP66

LED floodlights are supplied for use with a choice of voltages:

• 100-277 VAC, 50/60 Hz and 127-300 VDC

• 347-440 VAC, 50/60 Hz

COVER SCREWS

LINE TERMINAL 

NEUTRAL TERMINAL 

GROUND TERMINAL 

Figure 1

Cover/heat sink

DO NOT PLACE 
ADDITIONAL WEIGHT 
ON THE BACK COVER/
HEAT SINK

Summary of Contents for NFMVA20L

Page 1: ...back on one corner of the top most edge to prevent damage to gasket NOTE To avoid pinching hazard between heat sink cover and driver housing ensure that floodlight is oriented in vertical position be...

Page 2: ...lug fastener down on ground wire Torque to 25 in lbs 2 82 N m as shown in Figure 4 MAINTENANCE Perform visual electrical and mechanical inspections on a regular basis The environment and frequency of...

Page 3: ...inish of the floodlight Torque to 19 in lbs 2 2 N m 5 Install floodlight per above instructions Wire guard catalog number P62 NOTE Guard can be installed before or after floodlight has been in operati...

Page 4: ...ARQUE Pour viter le risque de pincement entre le panneau du dissipateur thermique et le bo tier du pilote veiller orienter le r flecteur en position verticale avant pendant et apr s la proc dure de c...

Page 5: ...re 3 Serrer au couple la fixation de la patte de mise la terre sur le fil de mise la terre Serrer un couple de 2 8 N m 25 lb po comme le montre la figure 4 ENTRETIEN Effectuer r guli rement des inspec...

Page 6: ...rotection en prenant soin de ne pas faire d gratignures sur le r flecteur Serrer les vis un couple de 2 2 N m 19 lb po 5 Installer le r flecteur en suivant les directives ci dessus Num ro du catalogue...

Page 7: ...s las superficies deben estar limpias Compartimento LED al que no se le puede prestar servicio No abrir Antes de abrir el compartimento del cableado se debe desconectar la alimentaci n del reflector y...

Page 8: ...n la leng eta a tierra 3 Ajuste el sujetador de leng eta a tierra en el cable de conexi n a tierra Torque de 25 pulgadas libras 2 82 N m como se muestra en la Figura 4 MANTENIMIENTO Realice las inspec...

Page 9: ...l protector asegur ndose de no rayar el acabado del reflector Gire a 19 pulgadas libras 2 2 N m 5 Instale el reflector seg n las instrucciones mencionadas anteriormente N mero de cat logo de la protec...

Page 10: ...6 Steckschl ssel oder einem Flachkopfschraubendreher siehe Abbildung 1 Die Abdeckung des K hlk rpers durch Zur ckziehen an einer der oberen Ecken entfernen um Sch den an der Dichtung zu vermeiden HINW...

Page 11: ...uben Sie den Verschluss der Erdungslasche bis zum Erdungskabel fest Drehmoment 25 in lbs 2 82 N m wie in Abbildung 4 dargestellt WARTUNGSMASSNAHMEN F hren Sie regelm ig elektrische und mechanische Ins...

Page 12: ...tzen Sie die mit dem Schutzgitter mitgelieferten Schrauben ein und achten Sie darauf die Oberfl che des Flutlichtscheinwerfers nicht zu verkratzen Drehmoment 19 in lbs 2 2 N m 5 Montieren Sie den Flut...

Reviews: