background image

Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this 

product must be performed by a qualified electrician. This product must be installed in accordance 

with the applicable installation code by a person familiar with the construction and operation of  

the product and hazards involved. For continued protection against shock hazard replace all covers 

and guards after field wiring is completed.

Before installing or performing any service, the power MUST be turned OFF at the branch circuit breaker. 

According to NEC 240-83(d), if the branch is used as the main switch for a fluorescent lighting circuit,  

the circuit breaker should be marked with “SWD”. All installations should be in compliance with the 

National Electric Code and all state and local codes.

Risk of Fire and Electric Shock- Make certain power is OFF before starting installation or attempting 

any maintenance. Disconnect power at fuse or circuit breaker. iLumin Plus models may contain 

circuits from more than one power source. 

Risk of Burn- Disconnect power and allow fixture to cool before handling or servicing.

Risk of Personal Injury- Due to sharp edges, handle with care. Always use at least two people when 

lifting and mounting heavy or large units

Failure to comply with these instructions may result in serious injury (including death) and property 

damage.

WARNING

DISCLAIMER OF LIABILITY: Eaton assumes no liability for damages or losses of any kind that may arise from  

the improper, careless, or negligent installation, handling or use of this product. 

 

IMPORTANT:

 Read carefully before installing fixture. Retain for future reference.  

NOTICE:

 Fixture may become damaged and/or unstable if not installed properly. 

Note:

 Specifications and dimensions subject to change without notice.

ATTENTION Receiving Department:

 Note actual fixture description of any shortage or noticeable damage on 

delivery receipt. File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be 

filed within 15 days of delivery. All damaged material, complete with original packing must be retained.

iLumin Plus 

NOTICE:

 If a room is wired for two circuits using two separate hot leads, it is very important to connect only one 

circuit per relay. Both circuits must be fed from the same phase.

NOTICE:

 Ensure that all modules are firmly seated on the DIN rails before beginning field wiring. 

NOTICE:

 The high voltage supply should be fed to the cabinet via an external isolation breaker with sufficient 

capacity for the planned installation.

NOTICE:

 Ensure that the supply is fully isolated at an external breaker before opening doors. Test that power 

has been removed before starting to handle conductors.

NOTICE:

 Ensure that high voltage and low voltage wiring remains separate. 

NOTICE:

 All new wiring must be fully verified before applying power.

NOTICE:

 Designed for indoor installation and use only. Dry location rated.

INS #

iLumin Plus

Installation Quick Guide

ILS-0010 
ILS-1100 
ILS-0020 
ILS-2000

ILM-2201 
ILM-2200 
ILM-2111 
ILM-2110
ILM-0040

ILM-0041
ILM-3000
ILM-3001
ILM-4000
ILM-4001

ILL-3300
ILL-3301
ILL-4400
ILL-4401

Applies to Model #s:

Summary of Contents for ILS-1100

Page 1: ... arise from the improper careless or negligent installation handling or use of this product IMPORTANT Read carefully before installing fixture Retain for future reference NOTICE Fixture may become damaged and or unstable if not installed properly Note Specifications and dimensions subject to change without notice ATTENTION Receiving Department Note actual fixture description of any shortage or not...

Page 2: ...tage Input Installation steps 1 Mount enclosure 2 Connect panel power 3 Connect relay wiring 4 Connect 0 10V dimmer wiring 5 Connect 2 wire data bus wiring 6 Connect iLumin Plus network wiring 7 Clear all power circuit wiring for errors 8 Energize panel power circuit 9 Energize relay and lighting power circuits 10 Coordinate system startup For detailed installation instructions scan the code below...

Page 3: ...only Use 75C wire insulation minimum Load 120 277VAC 20A per relay Mag Res General Purpose 120V 20A Tungsten 120V 16A LED Ballast 277V 16A LED Ballast Do not exceed 192A per module Relay screw torque 1 1Nm Note Branch Circuit over current protection by others Each relay has a 5K SCCR unless protected by another device Class 1 Field Relay Terminals Loads 20A max 10AWG min wire 16A max 12AWG min wir...

Page 4: ...ue nature que ce soit pouvant découler d une installation d une manipulation ou d une utilisation inappropriée imprudente ou négligente de ce produit IMPORTANT Lire attentivement avant d installer le luminaire À conserver pour consultation ultérieure AVIS Ce luminaire peut s endommager ou devenir instable s il n est pas installé correctement Remarque Les caractéristiques techniques et les dimensio...

Page 5: ...câblage de relais 4 Raccordement du câblage du gradateur de 0 à 10 V 5 Raccordement des deux câbles de conducteur du bus de données 6 Raccordement du câblage du réseau iLumin Plus 7 Vérification de tous les câbles du circuit d alimentation pour déceler toutes erreurs 8 Mise sous tension du circuit d alimentation du panneau 9 Mise sous tension des circuits d alimentation des câbles de relais et d é...

Page 6: ...fils sur une longueur allant de 1 3 cm 1 2 po à 1 6 cm 5 8 po Calibre de fil 10 à 12 AWG massif torsadé en cuivre seulement Remarque Apporter le circuit dédié afin d alimenter le panneau d éclairage iLumin Plus Le principal circuit d alimentation ne doit pas également alimenter l éclairage iLumin Plus est déjà câblé pour alimenter tous les modules une fois que le principal circuit d alimentation e...

Page 7: ...imiento de estas instrucciones puede provocar lesiones graves incluida la muerte y daños a la propiedad RENUNCIA DE RESPONSABILIDAD Eaton no asume ninguna responsabilidad por daños o pérdidas de ningún tipo que puedan surgir por la instalación manipulación o uso inadecuado descuidado o negligente de este producto IMPORTANTE Lea atentamente antes de instalar la luminaria Conserve estas instruccione...

Page 8: ...ión del panel 3 Conecte el cableado del relé 4 Conecte el cableado del atenuador de 0 10V 5 Conecte el cableado del bus de datos de 2 cables 6 Conecte el cableado de la red iLumin Plus 7 Borre todo el cableado del circuito de alimentación para detectar errores 8 Energice el circuito de alimentación del panel 9 Energice los circuitos de alimentación del relé y la iluminación 10 Inicio del sistema d...

Page 9: ...a tierra En línea Neutro Información de cableado Pelar el cable 1 2 a 5 8 Tamaño del cable 10 12AWG Solo cobre sólido trenzado Nota Traiga un circuito dedicado para alimentar el panel de iluminación iLumin Plus El circuito de alimentación principal no debería también encender la iluminación iLumin Plus está precableado para alimentar todos los módulos una vez que la alimentación principal está con...

Page 10: ...05 501 3172 2018 Eaton All Rights Reserved Tous droits réservés Todos los derechos reservados Publication No IB503022EN August 2018 Eaton is a registered trademark All trademarks are property of their respective owners Eaton est une marque de commerce déposée Toutes les autres marques de commerce sont la propriété de leur propriétaire respectif Eaton es una marca comercial registrada Todas las mar...

Reviews: