background image

 

 

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2441-P      Issue G        19-03-10                       

Sheet 1 of 6

 

  

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExCS110-05D 

Flameproof Combined Sounder / Beacon 

 
 
 
 
 
 
 

1)  Introduction 

 

The  BExCS110-05D  is  a  flameproof  combined  sounder  / 
beacon  which  is  certified  to  meet  the  requirements  of  the 
ATEX directive 94/9/EC and the IECEx scheme. The sounder 

section produces loud audio warning signals and the beacon 
section  produces  a  synchronised  visual  warning  signal.  The 

unit  can  be  used  in  hazardous  areas  where  potentially 
flammable atmospheres may be present.  Thirty-two different 

first  stage  audio  alarm  sounds  can  be  selected  by  internal 
switches,  and  each  one  can  be  externally  changed  to  a 

second or third stage alarm sound  (

see tone table on Page 

5

).  The  sounder  produces  output  levels  in  the  110dB(A) 

range and the beacon has a flash energy of 5 joules. The unit 

can  be  used  in  Zone  1  and  Zone  2  areas  with  gases  in 
groups  IIA  and  IIB  and  with  Temperature  Classifications  of 

T1, T2, T3 and T4.  
 

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information:- 

 
Unit Type No.     

       BExCS110-05D

 

 

Input Voltage:    DC Units    12V  or 24V  or  48V 

            AC Units         230V or 115V 

 
Code:           

Ex d IIB T4 for T

a

 –50

°

C to +70

°

 
Certificate No.

 

KEMA 01ATEX2223X 

 

 

IECEx KEM 10.0025X 

 

 

 

 

 

 

“Warnings”

 

 

DO NOT OPEN WHEN AN EXPLOSIVE  

                         

     GAS ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 

                    USE HEAT RESISTING CABLES AND        

                   CABLEGLANDS (Rated 110ºC) AT  

                       AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  

Serial No.       

 

 i.e.  10 / 1CS21000001 

 

3) 

Type Approval Standards 

 

The units have an EC Type examination certificate issued by 
KEMA and have been approved to the following standards:- 

 
 

 
 
 

 
 

 
 

 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

 

 

4) 

Installation Requirements

 

 
The  unit  must  be  installed  in  accordance  with  the  latest 

issues of the relevant parts of the EN60079 specifications or 
the equivalent IEC specifications – Selection, Installation and 

maintenance  of  electrical  apparatus  for  use  in  potentially 
explosive  atmospheres  (other  than  mining  applications  or 

explosive processing and manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 

The  installation  of  the  unit  must  also be  in  accordance  with 
any  local  codes  that  may  apply  and  should  only  be  carried 

out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

 

5) 

Zones, Gas Group, Category and Temperature 

Classification 

 

The BExCS110-05D unit has been certified Ex d IIB T4  for 
Ta  –50ºC  to  +70ºC.  This  means  that  the  units  can  be 

installed in locations with the following conditions:- 
  

Area Classification: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if  it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

  

 
Equipment Category:

 

2G 

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

 
 

Ambient Temperature Range: 

 

   

         -50

°

C to +70

°

0518 

CE Marking: 
Notified Body No. 

 

II 2G 

Epsilon x: 

Equipment Group  
And Category: 

Reviews: