Installation instructions

DH75/DH110 RANGE

Installation model DH75/110

1.  Remove machine from packaging and set on a level surface. 

Check that machine is level both vertically and horizontally.

2.  Remove covers as shown in FIG.1 relative to machine type 

installed.

3.  The Electrical supply to unit must be sized according to the 

data on the serial number label, paying close attention to 

I.E.E regulations latest edition regarding the special conditions 

governing electrical supply to machines in potentially damp 

areas (DH75/110 are IP45).

4.  The electrical supply should be connected to the terminals 

on the Printed Circuit Board in the electrical box found in 

the top corner of the machine, see Fig1 & Fig4. Wires to be 

connected as follows: brown/red to live, blue/black - to neutral, 

and green/yellow to earth.The fan mode switch can be set 

to cycle fan when Hygrostat senses demand but should be 

set to continuous to promote good air circulation and reduce 

condensation. 

Note that on models fitted with LPHW and or remote hygrostat 

the fans will start automatically whenever there is an air heating 

or dehumidification demand. During defrost the fans will stop. (Fan 

cycle not recommended for TTW machines with humidistat only). 

Set Fan Speed switch to “High” for maximum duty, “Low” for minimum sound.
5.  Locate drain, 15mm compression fitting, on side of unit and run 

it away to waste as preferred. A single hole is provided in the 

side of the unit. The drain is factory fitted to this hole. (In TTW 

machines there is an alternate position - see drawings).

Models with LPHW fitted

6.  Connect water circuit piping to the 22mm stubs provided on 

the side of the machine as per diagram.

7.  It is recommended that isolation valves are fitted to enable 

isolation of the machine in the event of service. 

The Circulating Pump must be sized to take into account 

the design flow rate of the machine plus the water system 

resistance. (Flow Rate 9.6 l/min Pressure Drop 2.8 m/hd).

Please leave these instructions for the user.

Fig 1

Standard & 

TTW machine

Standard 

machine

Mains in 

terminals on 

printed circuit 

board

Safety

Remove grille

from outer cover 

before

removing cover

from machine

Grille

Fixing screws (3)

Outer cover

Rremove panel

(4 screws)

Mains in

Condensate 

drain

LPHW in

LPHW out

Port B

LPHW out

Port AB

LPHW in

Port A to LPHW fin 

block

Fig 2 

LPHW SCHEMATIC 

Boiler

Radiator

(If fitted)  

Flow

balance

valve

Flow meter

3 way motorised vslve 

LPHW connections

located in cabinet

(Diverting)

Pump 

Fig 3

DH75/110

Radaitor

(If fitted)  

HEALTH & SAFETY WARNING

As the Heat Pump contains electrical and rotational equipment, it is recommended that ONLY competent persons carry out any work on this type of 

machine (see guarantee). Isolate electrically before entering machine or removing panels.

This appliance is not intended for use by persons (including children) with reduced physical,sensory or mental capabilities, or lack of experience and 

knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure that they do not play with the appliance

ISOLATE ELECTRICALLY BEFORE ENTERING MACHINE OR REMOVING PANELS.

Summary of Contents for Calorex DH110 Series

Page 1: ...there is an alternate position see drawings Models with LPHW fitted 6 Connect water circuit piping to the 22mm stubs provided on the side of the machine as per diagram 7 It is recommended that isolati...

Page 2: ...1 Is supply switched on 2 Is supply fuse healthy 3 Turn Hygrostat knob fully anti clockwise 4 Check air inlet and outlet for obstructions and that filter is not blocked 5 Check that HP and LP switch...

Page 3: ...260 350 780 1167 888 980 1474 62 AIR SAMPLE TUBES DO NOT OBSTRUCT AIR AIR 30 DRAIN TTW ONLY STANDARD MACHINE WITH COVER FILTER THROUGH THE WALL MODEL SERVICE REQUIREMENTS VIEW FROM POOL HALL DIMENSION...

Page 4: ...flow nominal High speed m h 925 1007 1007 925 1007 1007 Low speed m h 750 812 812 750 812 812 Water data LPHW flow rate L min 9 6 9 6 9 6 9 6 9 6 9 6 LPHW pressure drop m hd 2 80 2 80 2 80 2 80 2 80 2...

Page 5: ...u ventilateur peut tre r gl pour cycler le ventilateur lorsque l hygrostat en d tecte le besoin mais il devra tre r gl en mode continu afin de maintenir une bonne circulation de l air de LPHW ou ECBP...

Page 6: ...pas obstru es et si le filtre n est pas bloqu 5 V rifiez si les boutons HP et BP sont bien initialis s 6 Appelez le service entretien si apr s avoir effectu toutes ces v rifications et attendu une he...

Page 7: ...SEILL ES POUR L ACC S D ENTRETIEN MACHINE STANDARD AVEC CACHE FILTRE MACHINE STANDARD AVEC CACHE 800 800 1500 1500 800 RECOMMAND POUR EMP CHER LA REMISE EN CIRCULATION LA MACHINE AINSI QUE LE CONDUIT...

Page 8: ...rande vitesse m h 925 1007 1007 925 1007 1007 Basse vitesse m h 750 812 812 750 812 812 Caract de l eau D bit LPHW L min 9 6 9 6 9 6 9 6 9 6 9 6 Chute de pression LPHW m hd 2 80 2 80 2 80 2 80 2 80 2...

Page 9: ...Um eine gute Luftzirkulation zu erreichen und um die Kondensation zu reduzieren sollte der Betriebsschalter jedoch auf Dauerbetrieb gestellt werden Bitte ber cksichtigen Sie dass die Ventilatoren bei...

Page 10: ...P und LP Schalter in der Grundstellung stehen Gerat nach einer Stunde noch nicht angelaufen ist wenden Sie sich an den Kundendienst WASSERAUSTRITT VOM SOCKEL DES GER TES 10 berpr fen Sie ob die Verbin...

Page 11: ...WERDEN UND ALLE HOHLR UME M SSEN BERBR CKT WERDEN UM UMW LZUNGEN ZU VERMEIDENN ANSICHT VON POOL HALLE STANDARD GER T MIT ABDECKUNG SERVICEANFORDERUNGEN DIE MIT EINEM GEKENNZEICHNETEN ABMESSUNGEN WERD...

Page 12: ...AMP 7 8 10 6 5 0 7 8 10 6 5 0 Kompressor LRA Blockierter rotor AMP 55 66 30 55 66 30 Luftfluss Luftstrom Nen nwert Hohe Geschwindigkeit m h 925 1007 1007 925 1007 1007 Niedrige Geschwindigkeit m h 750...

Page 13: ...o sensor de humedad higrostato Ajuste la velocidad del ventilador en el interruptor a Alto HIGH para m ximo servicio y bajo LOW para m xima reducci n del ruido 6 Localizaci n del drenaje 15mm de tuber...

Page 14: ...dos y limpios b Limpie con un trapo h medo o l quido de limpieza apropiado para superficies pintadas Note La tarjeta de garant a que viene con la maquina debe ser devuelta a fabrica para mantener los...

Page 15: ...980 1474 62 TUBOS DE MUESTRA DE AIRE NO OBSTRUIR AIRE AIRE 30 DRENAJE SOLO EN TTW MAQUINA ESTANDAR CON CUBIERTA FILTRO MODELO A TRAVES DE PARED TTW REQUERIMIENTO DE SERVICIO VISTA DESDE EL RECINTO DE...

Page 16: ...m blauw zwart op neutraal en aarde op de aanwezige steunbout 5 De ventilatorschakelaar kan altijd op cyclische ventilatie worden gezet wanneer de hygrostaat aangeeft dat er vraag naar is maar moet op...

Page 17: ...eer of de HD en LD schakelaars gereset zijn Als de machine na 30 minuten nog steeds niet start regel dan een onderhoudsbeurt ER LEKT WATER UIT HET ONDERSTEL Controleer de aansluiting van de machine op...

Page 18: ...RKOMEN ONDERHOUDSVEREISTEN MINIMALE AFMETINGEN VOOR SERVICE WERKZAAMHEDEN STANDAARDMODEL MET DEKPLAAT TTW MODEL MWT MUURDOORVOERING FILTER FILTERVERWIJDERING FILTER VERWIJDERING LUCHT 1520 796 1532 38...

Page 19: ...5 1007 1007 1007 1007 Lage snelheid m u 750 750 812 812 812 812 Watertechnische gegevens LPHW Doorstroming L min 9 6 9 6 9 6 9 6 9 6 9 6 LPHW Drukval m wk 2 80 2 80 2 80 2 80 2 80 2 80 LPHW Spoelvolum...

Reviews: