RT650 

User

’s Manual 

K01-0000485-00 

 
 

 

Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at www.cyberpower.com/registration. 

Registration certifies your product's warranty, confirms your ownership in the event of a product loss or theft and entitles you to free technical 

support. 
 

 

 

(SAVE THESE INSTRUCTIONS) 

This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area  free  of  conductive 

contaminants.    (Please see specifications for acceptable temperature and humidity range). 

CAUTION!   

To reduce the risk of electric shock, do not remove the cover. There are no user serviceable parts inside. 

CAUTION!   

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 

CAUTION!   

The

 

UPS must be connected to an AC power outlet with fuse or circuit breaker protection.    Do not plug into an outlet that is not 

grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 

CAUTION!   

To avoid electric shock, turn off the unit and unplug it from the AC power source before installing a computer component. 

CAUTION!

    Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, 

ANSI/NFPA 75. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with

 

20  amperes  maximum  branch  circuit  over  current  protection in 

accordance with the National Electric Code, ANSI/NFPA 70. 

CAUTION!   

To avoid electrical shock, turn off the unit and unplug it form the AC power source before servicing the battery.

 

CAUTION!   

Do not dispose of batteries in a fire. The batteries may explode. 

CAUTION!   

Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

 

DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT  EQUIPMENT!   

CyberPower  Systems  does  not  sell  products  for  life  support  or  medical 

applications. 

DO  NOT

  use  in  any  circumstance  that  would  affect  operation  and  safety  of  life  support  equipment,  any  medical  applications  or 

patient care. 

DO NOT USE WITH OR NEAR AQUARIUMS!   

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

   

Condensation 

from the aquarium can cause the unit to short out. 

DO NOT USE THE UPS ON ANY TRANSPORTATION!   

To reduce the risk of fire or electric shock, do not use the unit on any transportation 

such as airplanes or ships.

 

The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out. 

 

 

 

 

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following: 

(a) UPS unit (b) 

User’s manual (c) USB device cable 

*PowerPanel®  Personal Edition software is available on our website. Please visit 

www.cyberpower.com

 and go to the Software Section 

for free download. 

 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

 

1.

 

Ensure that the equipment plugged into the UPS 

does not exceed the UPS unit’s rated capacity (650VA/400W). If the rated capacities of the 

unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip. 

2.

  There are many factors that can affect the amount of power that your electronic equipment will require.    For optimal system performance 

keep the load below 80% of the unit’s rated capacity. 

 

HARDWARE INSTALLATION GUIDE 

1.  Your new UPS may be used immediately upon receipt. However, after receiving a new UPS, to   

ensure the battery

’s maximum charge capacity, it is recommended that you charge the battery   

for at least 8 hours. Your UPS is equipped with an auto-charge feature. When the UPS is   

plugged into an AC outlet, the battery will automatically charge when it

’s turned on or turned off. 

2.  With the UPS unit turned off and unplugged, connect your computer, monitor, and any other 

 

peripherals requiring battery backup from the SURGE/BATTERY outlets. Plug the other 

peripheral equipment (e.g. printer, scanner, speakers, etc.) into the full-time surge protection outlets. 

DO NOT plug a laser printer, paper 

shredder, copier, space heater, vacuum cleaner, sump pump, or other large electrical device into the 

“Battery and Surge Protected 

Outlets

”. The power demands of these devices will overload and possibly damage the unit. 

3.  To protect a fax, phone, or modem line, connect a telephone cable from the wall jack outlet to the IN jack of the UPS.   

Connect a telephone cable from the UPS OUT jack to protect a modem port on the computer, a telephone, or fax machine. 

4.  Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet).    Make sure the wall branch outlet is   

protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air   

conditioner, refrigerator, copier, etc.).    The warranty prohibits the use of extension cords, outlet strips, and surge   

strips in conjunction with the UPS unit. 

5.  Press the power switch to turn the unit on.    The Power On indicator light will illuminate green 

and the unit will “beep” twice. 

6.  If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at 

least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 

7.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 

8.  To store the UPS for an extended period of time, cover it and store with the battery fully charged. While in storage, recharge the battery every 

three months to ensure optimal battery life. 

9.  Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility. 

10. The UPS can be laid down on its left side during operation. 

DO NOT

 lay the UPS down on the other side which 

may block the ventilation hole and hinder the heat dissipation.

 

 

 

 

 

DESCRIPTION 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. 

LED Indicators 

The LED indicators will illuminate to show the status of power: on line, on battery, overload, replace battery. 

2. 

Power Switch 

To turn the UPS 

ON

, press the power button for approximately 2 seconds - you will hear a constant tone and release after a short beep. 

To turn the UPS 

OFF

, press the power button for approximately 2 seconds - you will hear a constant tone and release after two short beeps. 

Mute mode: The audible alarm can be turned

 Off 

or

 On 

by quickly pressing the POWER button twice. The default setting is for the Alarm On. 

To turn the Alarm Off, quickly press the power button twice. You will hear two short beeps when the Alarm is turned Off. To turn the Alarm 

back On, quickly press the power button twice. You will hear a single short beep when the Alarm is turned On. *When the Alarm is turned Off, 

there will be no audible notification when the UPS goes to Battery mode or reaches a low battery state.

 

3. 

Communication Protection Ports 

Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).

 

4. 

USB Port to PC 

The USB port allows connection and communication between the USB port on the computer and the UPS unit. The UPS communicates its 

status to the PowerPanel

®

 Personal Edition software. 

5. 

Communication Port to PC 

This port allows connection and communication between the UPS and computer.

 

The UPS communicates its status to the

 PowerPanel

®

 

Personal Edition

 software.

 

For information regarding ordering a serial cable for the unit, please contact technical support at CyberPower 

System. 

NOTE:

 Only one of communication port and USB port can be used as communication and control of the UPS unit at one time.

 

6. 

Wiring fault Indicator (red) 

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If 

this is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The UPS will 

not provide surge protection without being plugged into a grounded and properly wired wall outlet. 

7. 

Battery and Surge Protected Outlets 

The unit has battery powered/surge suppression outlets to ensure temporary uninterrupted operation of your equipment during a power 

failure. 

(DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum cleaner, sump pump, or other large electrical 

device into the 

“Battery and Surge Protected Outlets.” The power demands of these devices will overload and possibly damage 

the unit.) 

8. 

Full-Time Surge Protection Outlets 

The unit has surge suppression outlets to provide surge and line noise protection. 

9. 

Circuit Breaker 

Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection.

 

10.  Outlets Designed for AC Adapters 

The UPS unit has 2 widely-spaced outlets so AC power adapters can be plugged into the UPS without overlapping or blocking adjacent   

outlets. 

 

 

REPLACING THE BATTERY

 

Installation or replacement of batteries located in an 

OPERATOR ACCESS AREA

1. 

When replacing batteries, replace with the same number of the following battery: CyberPower / RB1270C for both RT650. 

2. 

CAUTION!

 Risk of energy hazard, 12V, maximum 9 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such as 

chains, wrist watches, and rings.

 

High energy through conductive materials could cause severe burns. 

3. 

CAUTION! 

  Do not dispose of batteries in a fire. The batteries may explode. 

4. 

CAUTION! 

  Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. 

5. 

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES 

ACCORDING TO LOCAL REGULATIONS.

 

 

 

TO REPLACE THE BATTERY 

1. 

Turn off and unplug all connected equipment. 

2. 

Unplug it from the AC power source. 

3. 

Turn the UPS on its side. 

4. 

Remove the retaining screw. 

5. 

Slide the battery compartment cover completely off of the unit. 

6. 

Remove the battery from the compartment. 

7. 

Disconnect the battery wires from the battery. 

8. 

Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative (-) terminal of the battery. 

9. 

Put the battery back into the compartment. 

10.  Slide back the battery compartment cover and tighten the retaining screw. 

11.  Charge the unit for 8 hours to fully charge the battery. 

REMINDER:   

Batteries are considered 

HAZARDOUS WASTE

 and must be disposed of properly. Most retailers that sell lead-acid batteries 

collects used batteries for recycling, as required by local regulations.

 

 

 

DEFINITIONS FOR ILLUMINATED LED INDICATORS

 

 

On Line 

On Battery 

Overload 

Replace Battery 

 

Alarm 

CONDITION 

On 

Off 

Off 

Off 

Off 

Normal 

Off 

On 

Off 

Off 

Beep twice   

every 30 

seconds 

Utility Failure- 

The UPS is providing power to 

battery protected outlets from its battery. 

Off 

Flash 

Off 

Off 

Rapid Beeping 

every 1/2 

second 

Utility Failure -

 The UPS is providing battery 

power. Rapid beeping indicates the unit will run 

out of power shortly. 

Off 

Off 

One Flash 

every 5 

seconds 

Off 

Constant tone 

Overload Fault -

 Occurs when connected 

equipment exceeds the listed capacity of the 

UPS. Turn the UPS off, unplug at least one piece 

of equipment from battery outlets, wait 10 

seconds, reset the circuit breaker and turn the 

unit on. 

Off 

Off 

On/Flash 

Off 

Constant tone 

Short Fault

 (two flashes every 5 seconds)

 - 

Unplug at least one piece of equipment from 

battery outlets and turn the UPS on again. 

UPS Fault

 (constantly illuminate) 

Contact 

CyberPower Systems for support.

 

On/Off 

Off/On 

Flash 

Off 

Beep every one 

second 

Charger Fault 

(three flashes every 5 seconds)

 - 

Contact CyberPower Systems for support.

 

On 

Off 

Off 

Flash 

Beep every two 

seconds in 30 

seconds 

Battery is worn out or disconnected 

– Make 

sure the battery is connected or replace a new 

battery.

 

 

 

 

 

In line mode, the AC input voltage may not be stable all the time, to prevent the connected equipment from damage caused by the 

unexpected voltage fluctuations, please adjust the sensitivity of the unit by the steps as follows: 

1. Please make sure that the UPS is in 

LINE MODE.

 

2. To Enter the Sensitivity Setup mode, press the Power Button for 10 seconds until all indicators flash 2 seconds rapidly. 

3. The unit will show the current sensitivity setting, as shown in the following table. 

4. To set up a level of sensitivity, hold down the power button until the green indicator (the first one) illuminates. 

5. To select Low Sensitivity setting: shortly press power button until one red indicator (the last one) illuminate. 

6. To select Medium Sensitivity setting, press the power button until both red indicators (the third and fourth from the top) illuminate. 

7. To select High Sensitivity setting, press the power button until yellow and both red indicators (bottom three) illuminate. 

8. Once in setup mode, if there is no action within 5 seconds, the unit will exit setup mode, no setting is done. 

 

BASIC OPERATION 

INSTALLING YOUR UPS SYSTEM 

IMPORTANT SAFETY INSTRUCTIONS 

PRODUCT REGISTRATION 

 

 

FUNCTION SETUP GUIDE 

– SENSITIVITY SETUP 

Reviews: