Salwico ST400 H2S

CGD50/500

Calibration Instruction

Summary of Contents for Salwico ST400 H2S

Page 1: ...Salwico ST400 H2S CGD50 500 Calibration Instruction...

Page 2: ...to revision without notice due to continued progress in methodology design and manufacturing Consilium Building Safety AB assumes no legal responsibility for any error or damage resulting from the usa...

Page 3: ...ntrations H2S is a sticky gas and smells very distinctly from rotten eggs Consilium Replacement article number for ST400 H2S detectors is no 004462 S A new sensor is supplied without the metal housing...

Page 4: ...2 Prerequisites 1 Use the arrow keys on the control panel to manoeuvre through the different menus Press the right arrow key to access the menu tree 2 Scroll to 4 Gas Detectors and press Continue 3 S...

Page 5: ...ibration 1 Connect the Multi meter set to mA as shown in the picture 2 Adjust with the ZERO potentiometer to 4 0 mA signal output 1 4 Calibrating the sensor Span calibration Verification of detector t...

Page 6: ...When the reading is stabilized adjust the readout to 14 6 mA or 16 8 mA with the SPAN potentiometer NOTE Response can be estimated to several minutes in some cases If this reading cannot be reached th...

Page 7: ...Calibration Instruction 1 Calibration Instruction for Salwico ST400 H2S 5103028_Salwico ST400 H2S_Calibration Instruction_I0_EN_2019_C 5...