background image

1948768 

V1.8  

19 May 2022 

Instruction Sheet Template - V1.3 – Updated 20/01/2022 

Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

 

Zoneworks, HIVE (HV/HVG) and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV, -HVG, -DATA 

are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 

be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 

single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 

a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, HVG, 

DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 

green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV, HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 

a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 

version)  

 

DALI EM Option

 

Luminaires with part numbers having 

-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

 Party Lighting Control Systems.  Before installing the -DALI luminaire, please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The -DALI 

fitting  will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress  LED flashes at 1s On (Yellow) & 1s Off 
“IDENTIFY COMMAND” 

Lamp and Status LED Flash for 30 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da. . 

 

 

 

 

 

LP™ Sustained Emergency LED Battens 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the 

requirements of AS2293.3: 2005 and AS/NZS 

CISPR15: 2017 

NOTE: Standard product codes with this symbol       are 

enabled with Clevertest Plus capability.  Please refer to 

the operation guide supplied with the product for details. 

 

 

Models:      

CBS4LEDS-xx-DIF-zz-yy-vv-xx

 

Testing: 

Manual Test  

xx = Blank 

Options:

 

Low Output 

xx = LO 

 

Zoneworks 

xx = ZW 

 

Hi-LO Sensor Control 

zz=MS-HL 

 

Z/W DATA   

xx = DATA 

 

DALI Driver 

zz=DD 

 

Zoneworks HIVE

 

xx = HV/HVG

   

Black Colour 

xx = BLK 

 

DALI Registered.      

xx = DALI 

 

4 Hour Battery 

vv = 4HR 

 

Clevertest 

xx = CT   

 

 

 

(NOTE: -CT Products supplied with the Clevertest Plus Symbol         are activated with Clevertest PLUS capability. 

Please refer to the operation guide supplied with the product for details). 

 

Spare Parts: 

1550050 

Replacement Battery 

1100635 

Replacement Emergency LED Board 

1100641 

Replacement Emergency LED Board 

(-4HR) 

8002695

 

Replacement 240V LED Strip 

AUM02370170001  Replacement Emergency Driver 

AUM02270170002  Replacement Emergency Driver  

(-DALI) 

AUM02870100001  Replacement Emergency Driver  

(-HV) 

AUM02970060001  Replacement Emergency Driver  

(-HVG) 

AUM02370080001  Replacement Emergency Driver  

(-4HR) 

1330059

 

Replacement 240V Driver 

1330023

 

Replacement 240V Driver 

 

(-LO) 

1330056

 

Replacement 240V Driver 

 

(-DD) 

1330070

 

Replacement 240V Driver 

 

(-MS-HL) 

1190118

 

Replacement Microwave Sensor 

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

 

 

 

 

 

 

 

Reviews: