background image

RESIDENTIAL DC

VEHICULAR SLIDE GATE OPERATOR

INSTALLATION MANUAL

LiftMaster
300 Windsor Drive
Oak Brook, IL 60523

Model 

RSL12UL

•  

THIS PRODUCT IS TO BE INSTALLED AND 

SERVICED BY A TRAINED GATE SYSTEMS 

TECHNICIAN ONLY. 

•  

This model is for use on vehicular passage 

gates ONLY and not intended for use on 

pedestrian passage gates. 

•  

This model is intended for use in Class I and II 

vehicular slide gate applications.

•  

Visit LiftMaster.com to locate a professional 

installing dealer in your area.

•  

This gate operator is compatible with MyQ

®

 

and S 2.0

®

 accessories.

Access installation and technical support
guides or register this product

Send it in 

by texting the 

photo to 71403.

Take a photo

 of the 

camera icon including 
the points ( ).

1.

2.

RSL12ULTECH

Summary of Contents for RSL12UL

Page 1: ...and not intended for use on pedestrian passage gates This model is intended for use in Class I and II vehicular slide gate applications Visit LiftMaster com to locate a professional installing dealer...

Page 2: ...HOOTING 31 Diagnostic Codes 31 Diagnostic Codes Table 32 Control Board LEDs 34 Troubleshooting Chart 35 APPENDIX 37 Dual gate settings 37 Step 6 Solar Panel s 38 Limit setup with a remote control 42 W...

Page 3: ...ment protection devices in each entrapment zone l This vehicular slide gate operator will operate only after installation of a minimum of two independent monitored entrapment protection devices in eac...

Page 4: ...d and work freely in both directions prior to the installation of the gate operator 8 Permanently mounted access controls intended for users to activate must be located at least 6 feet 1 8 m away from...

Page 5: ...existing gate shall be upgraded to conform to the provisions of this specification 2 4 When the gate of an automated gate system requires replacement the new gate shall conform to the provisions of t...

Page 6: ...6 Carton Inventory NOT SHOWN Documentation Packet Chain 41 30 feet Eye Bolt Kit INTRODUCTION...

Page 7: ...24 m Maximum Gate Travel Speed 12 inches second Maximum Daily Cycle Rate 120 cycles day Maximum Duty Cycle Continuous Operating Temperature Without Heater 20 C to 60 C 4 F to 140 F With Optional Heate...

Page 8: ...your gate application Install a warning sign two provided on the inside and outside of the property where easily visible Gate Gate must be constructed and installed according to ASTM F2200 standards...

Page 9: ...derground utility locating companies BEFORE digging more than 18 inches 46 cm deep l ALWAYS wear protective gloves and eye protection when changing the battery or working around the battery compartmen...

Page 10: ...e front roller of the gate Lay out the concrete pad 2 Install the electrical conduit 3 Pour a concrete pad reinforced concrete is recommended Rear Installation 1 The gate operator should be installed...

Page 11: ...crete pad with appropriate fasteners The gate operator should be installed near the front roller of the gate or near the back of the gate in the OPEN position The space between the gate and the output...

Page 12: ...ain length Rear Installation DO NOT run the operator until instructed NOTE This installation will require two extra idler pulleys Make sure all exposed pinch points are guarded Refer to Gate Construct...

Page 13: ...stallation is unique It is the responsibility of the installer to ensure that ALL entrapment zones are protected with an external monitored entrapment protection device protecting both the open and cl...

Page 14: ...ensor entrapment protection for the close direction When an obstruction is sensed during gate closing the gate will reverse to the full open position disengaging the Timer to Close This input will be...

Page 15: ...NOTE The operator should be on a separate fused line of adequate capacity l ALL electrical connections MUST be made by a qualified individual l DO NOT install ANY wiring or attempt to run the operato...

Page 16: ...rod can be grounded to the chassis 7 Connect the white wire to NEUTRAL using a wire nut 8 Connect the black wire to HOT using a wire nut 9 Replace the junction box cover Ensure the wires are not pinc...

Page 17: ...pplication requires the 33AH wire harness Model K94 37236 1 Unplug the transformer 2 Unplug the J15 plug labeled BATT on the control board by squeezing the plug and pulling it from the control board T...

Page 18: ...ARN button again on the primary operator The yellow NETWORK LED will light 4 Press and release the OPEN test button to assign this operator as network primary 5 Press and release the LEARN button on t...

Page 19: ...he chassis ground of one operator 6 Connect ALL power to the operator and plug the J15 plug into the control board DUAL GATE WIRE TYPE SHIELDED TWISTED PAIR CABLE 22AWG up to 200 feet 61 m 18AWG 200 1...

Page 20: ...Cover 1 Slide the cover over the operator 2 Align the hole in the cover with the threaded hole in the operator s chassis and secure the cover with the provided 5 16 18 screw The basic installation is...

Page 21: ...d below or a remote control refer to Limit Setup with a Remote Control in the Appendix Setting the limits with a remote control requires a 3 button remote control programmed to OPEN CLOSE and STOP NOT...

Page 22: ...n be adjusted independently from the other by following steps 1 3 of the Initial Limit and Force Adjustment section Obstruction Test The operator is equipped with an inherent built in to the operator...

Page 23: ...TER LED will go out if programming is successful To program additional Security 2 0 remote controls or remote control buttons repeat the programming steps above Entering programming mode using externa...

Page 24: ...ns simultaneously 5 seconds until both the SET OPEN and SET CLOSE LEDs blink rapidly and the operator beeps 2 Release the buttons and the SET OPEN and SET CLOSE LEDs will blink slowly indicating the l...

Page 25: ...TC dial can be set to automatically close the gate after a specified time period The TTC is factory set to OFF If the TTC is set to the OFF position then the gate will remain open until the operator r...

Page 26: ...secutively the alarm will sound up to 5 minutes and the operator will need to be reset A The gate is hitting a wall or vehicle B The gate does not meet specifications C Debris is on the gate s track s...

Page 27: ...holds open an open gate if maintained pauses Timer to Close at OPEN limit SHADOW 2 Terminals This input is used for external shadow loop detector when loop is positioned under the swing of the gate l...

Page 28: ...s and resets alarm condition within line of sight l STOP and COM Stops a moving gate Hard stop maintained switch overrides Open and Close commands and resets alarm condition If maintained pauses Timer...

Page 29: ...properly adjusted and there are no obstructions to gate travel l To reduce the risk of FIRE or INJURY to persons use ONLY LiftMaster part 29 NP712 for replacement batteries l SAVE THESE INSTRUCTIONS...

Page 30: ...rt 29 NP712 for replacement batteries The batteries contain lead and need to be disposed of properly The operator comes with one 7AH battery One 33AH Battery A12330SGLPK with 33AH Battery Harness K94...

Page 31: ...show the code sequence number followed by the code number To Scroll Through the Saved Codes The operator will only keep track of up to 20 codes then will start saving over the oldest codes as new code...

Page 32: ...r less than 10V on a 12V system Make sure there is NOT a single 12V battery on a 24V system YES 43 Exit Loop Error Failure or missing loop SHORT or OPEN LiftMaster Plug in Loop Detector only Check loo...

Page 33: ...rom other operator Check inputs and communication method between operators either wired bus or radio Ensure operator is powered May have to erase the wireless communication and reprogram the two opera...

Page 34: ...ery low MEDIUM BLINK 1 blink per second Battery critically low ACC PWR OVLD OFF Accessory power is okay ON Accessory overload protector opened INPUT LEDS OPEN CLOSE STOP INPUT OFF Input inactive ON In...

Page 35: ...input LEDs b Stop button is active c Reset button is stuck d If on battery power only low or dead batteries e Entrapment Protection Device active f Vehicle loop detector or vehicle probe active a Che...

Page 36: ...ct Press the reset button to shut off alarm and reset the operator Alarm beeps three times with a command a Low battery a Check if AC power is available If no AC power then running on batteries and ba...

Page 37: ...rator insufficient standby time a Insufficient panel wattage b Excessive accessory power draw c Battery capacity too low a Add more solar panels b Reduce the accessory power draw by using LiftMaster l...

Page 38: ...e average solar radiation and the temperature effects on batteries in the given zones as shown on the map below Local geography and weather conditions may require additional solar panels Solar powered...

Page 39: ...lar applications SOLAR GATE CYCLES PER DAY BATTERY CURRENT DRAW mA ZONE 1 ZONE 2 ZONE 3 7AH batteries Two 7AH batteries 33AH batteries 7AH batteries Two 7AH batteries 33AH batteries 7AH batteries Two...

Page 40: ...IRE GAUGE AWG 20 WATTS OF PANELS 40 WATTS OF PANELS 60 WATTS OF PANELS 16 235 71 6 m 115 35 1 m 80 24 4 m 14 375 114 3 m 190 57 9 m 125 38 1 m 12 600 182 9 m 300 91 4 m 200 61 m 10 940 286 5 m 475 144...

Page 41: ...Batteries Solar panel applications require the Solar Harness Kit model K94 37236 see Accessories Wire the Solar Panels Proceed to the Dual Gate section if applicable or proceed to the Adjustment secti...

Page 42: ...e set properly the operator will automatically exit limit setting mode Refer to the Adjustment section and follow the instructions for Fine Tune the Force and Obstruction Test Perform the Obstruction...

Page 43: ...gainst fire and electrocution l DISCONNECT power AC or solar and battery BEFORE installing or servicing operator For continued protection against fire l Replace ONLY with fuse of same type and rating...

Page 44: ...s K94 37236 Battery Harness for 33AH batteries K1A6408 APE Assembly with plastic tray RPM board with mounting hardware K94 37259 Wiring Harness with product ID 1941240D 41 Chain 10 feet 1950307 41 Mas...

Page 45: ...04AL S505AL S506AL Wraparound round monitored edge 4 ft 5 ft 6 ft Models WR4 WR5 WR6 Wraparound square monitored edge 4 ft 5 ft 6 ft Models WS4 WS5 WS6 Remote Controls LiftMaster offers a variety of L...

Page 46: ...r gate operation The heater can be powered by 110 to 250 Vac Model HTR Wire harness Between main control board and expansion board Model K94 34778 LiftMaster internet gateway Internet enabled accessor...

Page 47: ...ION TO THE THREE YEAR LIMITED WARRANTY PERIOD SET FORTH ABOVE AND NO IMPLIED WARRANTIES WILL EXIST OR APPLY AFTER SUCH PERIOD Some states do not allow limitations on how long an implied warranty lasts...

Page 48: ...300 Windsor Drive Oak Brook IL 60523 LiftMaster com 2018 The Chamberlain Group Inc All Rights Reserved 01 39379B...