background image

 

WSD12-EVTT 

User Manual

 

 

 

CAPETTI ELETTRONICA s.r.l. - Strada Stratta, 57 
10090 CASTIGLIONE TORINESE - TORINO - ITALY 
VAT 04837130014 - Phone 011.981.98.11 - Fax 011.981.98.210 
e-mail

 

[email protected]

 - web 

www.capetti.it

 

 

WA0304E_WSD12-EVTT_User Manual_R05 

V4.8

 

 

1.

 

Description. 

The 

WSD12-EVTT

 is a 

datalogger

 

with 2 clean contact or “open collector” inputs capable to count pulses coming from a thermal 

energy meter (

energy and volume

).  

Channels 3 and 4 are equipped with contact NTC10K

Ω

 BETA 3435 temperature sensors to acquire the heat-transfer fluid temperature 

(

flow and return

). 

All channels are provided with storage functionality of samples acquired. 

 

2.

 

Configuration. 

It is necessary to verify the setup regarding the weight expressed in Wh and litres matching the impulse supplied from the energy 
meter to which the 

datalogger

 will be connected. Refer to the technical sheet of energy meter. 

To select weights, ac

t on the “

dip switches

” located in the inner electronic board. To verify the correct range setup please refer to 

the table below. 

NOTE

: in order that the modification take effect, the association between 

datalogger

 and the receiving 

basestation

 is necessary.   

If the sensor were already associate, so reset and associate operations must be done again. (

refer to “

WineCapManager User Manual

).

 

 

Pulse weight setup: 

 
 
 
 

 
 
 
 

 
 

 

 

 

Picture 1 - Product Image

 

ON

 

1

 

2

 

ON

 

1

 

2

 

ON

 

1

 

2

 

SW1: OFF

 

SW2: ON

 

CH1: 100 KWh/pulse 

CH2: 1.000 l/pulse 

 

SW1: ON

 

SW2: OFF

 

CH1: 10 KWh/pulse 

CH2: 100 l/pulse 

 

SW1: OFF

 

SW2: OFF

 

CH1: 1 KWh/pulse 

CH2: 10 l/pulse 

ON

 

1

 

2

 

SW1: ON

 

SW2: ON

 

CH1: 1.000 KWh/pulse 

CH2: 1.000 l/pulse 

 

Picture 2 - Pulse weight setup

 

Summary of Contents for WSD12-EVTT

Page 1: ...regarding the weight expressed in Wh and litres matching the impulse supplied from the energy meter to which the datalogger will be connected Refer to the technical sheet of energy meter To select weights act on the dip switches located in the inner electronic board To verify the correct range setup please refer to the table below NOTE in order that the modification take effect the association bet...

Page 2: ...is operation mode stand alone with data downloads through USB the connection with the PC and the WineCapManager running on it is necessary in order to modify the device s operation mode The sampling interval must be set with the device in STAND ALONE refer to 7 Stand alone USB datalogger installation mode and automatically the device s clock is aligned with the PC s clock in order to assure the te...

Page 3: ...ion procedure to the basestation refer to WineCap System User Manual R30 4 flashes 4 flashes STANDBY Temporary device deactivation the device is stopped The sampling process and the radio are is turned off losing the connection to the network To reactivate a TEST command is necessary The STANDBY command must be given twice to confirm it at the first sequence the led flashes alternating RED and GRE...

Page 4: ...fferent command is associated to confirm the command the WineCapKey must be removed from the sensible area immediately after the number of flashes corresponding at the desired command The TEST corresponds to the second pulse and activate the Field Measurer function The device will give back the radio signal quality through led flashes WIRELESS MODE STATUS Table Flash count Wireless mode Status Rad...

Page 5: ...ashes 2 seconds long STANDBY Sequence of red flashes short 2 seconds long short FACTORY RESET INVALID datalogger clock PC connection required 8 Shutting off Reactivating the device If the device is shut off and left unused for a long time you can issue the STANDBY command refer to Picture 5 Commands table It corresponds to the command number 4 and must be issued twice to confirm the operation Posi...

Page 6: ...M 868MHz Radio coverage Up to 6Km in line of sight can be extended using WR12 battery powered repeaters Sealing IP65 Dimensions 90 x 120 x 50 mm Weight 350g Case material ABS Mounting Fix on 4 points Connections Wireless USB Cable external diameter 4 7mm maximum Copper wire section 0 05 2 5mm 14 AWG Thermal energy Weight counting Selectable on board CH1 KWh CH1 KWh 1 1 10 10 100 100 1 000 1 000 NT...

Page 7: ...Strada Stratta 57 10090 CASTIGLIONE TORINESE TORINO ITALY VAT 04837130014 Phone 011 981 98 11 Fax 011 981 98 210 e mail info capetti it web www capetti it WA0304E_WSD12 EVTT_User Manual_R05 V4 8 11 Mechanical dimensions Picture 9 Mechanical dimensions ...

Page 8: ...011 65 CE that restricts the use of substances in the manufacturing of electronic devices The WEEE logo on the label indicates that this product is compliant with the WEEE EC Directive This symbol valid only in the European Union countries indicates that the product it is applied to MUST NOT be discarded with ordinary household or industrial waste but must be sent to an authorized reception point ...

Reviews: