INSTRUCTIONS FOR THERMOWELD GROUNDING CONNECTIONS - CABLE TO BUS BAR
CB-26
Place cable and bus bar into mold.
CB-32
Place cable into mold and then
butt bus bar against cable.
CB-28
Place bus bar in the mold as
shown. Position cable into mold
until the end is even with the
center of the tap hole.
CB-15
Place bus bar in the mold with end of the bus bar at the
center of the tap hole. Place cable into mold until end
is butted against the bar. After weld
is complete, open mold. One side will
swing open away from
bus bar. Now slide
mold down
bus bar until
mold is clear
of weld and
then lift mold
up off of bus
bar.
CB-33
Place lug in mold and butt cable
up against lug under center of
tap hole.
CB-23 & CB-24
Place bus bar in the mold as
shown then butt end of cable
against bus bar.
CB-24
CB-23