background image

Cancels: II 580F-180-2

II 580F-180-3

3/15/06

installation, start-up and
service instructions

SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS

580F

Dura

Pac Series

Sizes 180-300

15 to 25 Tons

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . .  1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-25

I.  Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . .  1

II.  Step 2 — Rig and Place Unit

. . . . . . . . . . . . . . . . . . .  4

III.  Step 3 — Field Fabricate Ductwork

 . . . . . . . . . . . .  11

IV.  Step 4 — Make Unit Duct Connections

 . . . . . . . . .  11

V.  Step 5 — Install Flue Hood and Wind Baffle

. . . . .  11

VI.  Step 6 — Trap Condensate Drain

. . . . . . . . . . . . . .  11

VII.  Step 7 — Orifice Change

. . . . . . . . . . . . . . . . . . . . .  12

VIII.  Step 8 — Install Gas Piping

 . . . . . . . . . . . . . . . . . .  13

IX.  Step 9 — Make Electrical Connections

 . . . . . . . . .  13

X.  Step 10 — Make Outdoor-Air Inlet Adjustments

. .  15

XI.  Step 11 — Install Outdoor-Air Hood

. . . . . . . . . . . .  15

XII.  Step 12 — Install All Accessories

 . . . . . . . . . . . . .  16

XIII.  Step 13 — Adjust Factory-Installed Options

. . . . .  18

XIV.  Step 14 — Install Control Accessory for Optional

 Perfect Humidity™ Dehumidification Package

 . .  24

START-UP

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-34

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-42

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . .43-47

INDEX

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  48

START-UP CHECKLIST

 . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extin-
guishers available for all brazing operations.

IMPORTANT: 

Units have high ambient operating limits. If

limits are exceeded, the units will automatically lock the com-
pressor out of operation. Manual reset will be required to
restart the compressor.

INSTALLATION

I. STEP 1 — PROVIDE UNIT SUPPORT

A. Roof Curb

Assemble or install accessory roof curb or horizontal adapter
roof curb in accordance with instructions shipped with this
accessory. See Fig. 1A, 1B, and 2. Install insulation, cant
strips, roofing, and counter flashing as shown. Ductwork can
be installed to roof curb or horizontal adapter roof curb before
unit is set in place. Curb or adapter roof curb should be level.
This is necessary to permit unit drain to function properly.
Unit leveling tolerance is ± 

1

/

16

 in. per linear ft in any direc-

tion. Refer to Accessory Roof Curb or Horizontal Adapter Roof
Curb Installation Instructions for additional information as
required. When accessory roof curb or horizontal adapter roof
curb is used, unit may be installed on class A, B, or C roof cov-
ering material.

Instructions continued on page 4.

WARNING: 

 Before performing service or mainte-

nance operations on unit, turn off main power switch to
unit and install lockout tag to disconnect switch. Elec-
trical shock could cause personal injury.

WARNING: 

 

1. Improper installation, adjustment, alteration, ser-

vice, or maintenance can cause property damage,
personal injury, or loss of life. Refer to the User’s
Information Manual provided with this unit for
more details.

2. Do not store or use gasoline or other flammable

vapors  and  liquids  in  the  vicinity  of  this  or  any
other appliance.

What to do if you smell gas:

1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any

phone in your building.

3. IMMEDIATELY call your gas supplier from

a neighbor’s phone. Follow the gas supplier’s
instructions.

4. If you cannot reach your gas supplier, call the fire

department.

WARNING: 

 Disconnect gas piping from unit when

pressure testing at pressure greater than 0.5 psig. Pres-
sures greater than 0.5 psig will cause gas valve damage
resulting in hazardous condition. If gas valve is subjected
to pressure greater than 0.5 psig, it must  be replaced
before use. When pressure testing field-supplied gas pip-
ing at pressures of 0.5 psig or less, a unit connected to
such piping must be isolated by closing the manual gas
valve(s).

Содержание DuraPac 580F Series

Страница 1: ...TALLATION I STEP 1 PROVIDE UNIT SUPPORT A Roof Curb Assemble or install accessory roof curb or horizontal adapter roof curb in accordance with instructions shipped with this accessory See Fig 1A 1B and 2 Install insulation cant strips roofing and counter flashing as shown Ductwork can be installed to roof curb or horizontal adapter roof curb before unit is set in place Curb or adapter roof curb sh...

Страница 2: ...80 240 PKG NO REF CURB HEIGHT DESCRIPTION CRRFCURB010A00 1 2 305 Standard Curb 14 High CRRFCURB011A00 2 0 610 Standard Curb for Units Requiring High Installation CRRFCURB012A00 2 0 610 Side Supply and Return Curb for High Installation ...

Страница 3: ... 3 Fig 1B Roof Curb Details 580F300 A A ...

Страница 4: ...airflow and service access Do not install unit in an indoor location Do not locate air inlets near exhaust vents or other sources of contaminated air For proper unit operation adequate combustion and ventila tion air must be provided in accordance with Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 American National Standards Institute Although unit is wea...

Страница 5: ...ards for spreader bars on all units 5 Weights do not include optional EconoMi erIV Add 90 lb 41 kg for EconoMi erIV weight 6 Weights given are for aluminum evaporator and condenser coil plate fins CAUTION All panels must be in place when rigging Fig 3 Rigging Details UNIT 580F MAXIMUM SHIPPING WEIGHT DIMENSIONS A B lb kg ft in mm ft in mm 180 1875 850 6 111 2 2121 4 0 1219 210 1925 873 6 111 2 212...

Страница 6: ...oil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fan operation Bottom 14 356 to combustible surfaces when not using curb Control box side 3 0 914 to ungrounded surfaces non combustible Control box side 3 6 1067 to block or concrete walls or other grounded surfaces Local code...

Страница 7: ...l airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fan operation Bottom 14 356 to combustible surfaces when not using curb Control box side 3 0 914 to ungrounded surfaces non combustible Control box side 3 6 1067 to block or concrete walls or other grounded surfaces Local codes ...

Страница 8: ...ox access Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fan operation Bottom 14 356 to combustible surfaces when not using curb Control box side 3 0 914 to ungrounded surfaces non combustible Control box side 3 6 1067 to block or concrete walls or other grounded surfaces Local codes or jurisdiction may prevail 7 With the...

Страница 9: ...Cfm 10 500 10 500 14 200 21 000 Quantity Diameter in 3 22 3 22 2 30 6 22 Motor Hp Rpm 1 2 1050 1 2 1050 1 1075 1 2 1050 Watts Input Total 1100 1100 3400 2200 EVAPORATOR COIL Cross Hatched 3 8 in Copper Tubes Aluminum Lanced or Copper Plate Fins Face Split Rows Fins in 4 15 4 15 4 15 4 15 Total Face Area sq ft 17 5 17 5 17 5 17 5 EVAPORATOR FAN Centrifugal Type Quantity Size in 2 12 x 12 2 12 x 12 ...

Страница 10: ...0 1285 30 0 136 29 0 1285 30 0 136 29 0 1285 30 0 136 29 0 1285 30 0 136 29 Thermostat Heat Anticipator Setting amps 208 230 v Stage 1 0 98 0 98 0 98 0 98 Stage 2 0 44 0 44 0 44 0 44 460 v Stage 1 0 80 0 80 0 80 0 80 Stage 2 0 44 0 44 0 44 0 44 Gas Input Stage 1 206 000 270 000 206 000 270 000 206 000 270 000 206 000 270 000 Stage 2 275 000 360 000 275 000 360 000 275 000 360 000 275 000 360 000 E...

Страница 11: ... box To install secure flue hood to access panel See Fig 10 The wind baffle is then installed over the flue hood NOTE When properly installed flue hood will line up with combustion fan housing See Fig 11 VI STEP 6 TRAP CONDENSATE DRAIN See Fig 12 for drain location One 3 4 in half coupling is pro vided inside unit evaporator section for condensate drain connection An 81 2 in x 3 4 in diameter and ...

Страница 12: ...sage for elevations up to 7000 ft For elevations above 7000 ft refer to Table 4 to identify the correct orifice size for the elevation See Table 3 for the number of orifices required for each unit size Purchase these orifices from your local Bryant dealer Follow instructions in accessory Installation Instructions to install the correct orifices Table 4 LP Gas Conversion As the height above sea lev...

Страница 13: ...ed space to sense average temperature Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low voltage connections as shown on unit label wiring diagram and in Fig 16 NOTE For wire runs up to 50 ft use no 18 AWG American Wire Gage insulated wire 35 C minimum For 50 to 75 ft use no 16 AWG insulated wire 35 C minimum For over 75 ft use n...

Страница 14: ... optional convenience outlet a 115 v GFI ground fault interrupt convenience outlet receptacle is pro vided for field wiring Field wiring should be run through the 7 8 in knockout provided in the basepan near the return air opening LEGEND NOTE The maximum wire size for TB1 is 2 0 Fig 15 Field Power Wiring Connections EQUIP Equipment GND Ground NEC National Electrical Code TB Terminal Board RH RC Y1...

Страница 15: ...and EconoMi erIV If EconoMi erIV is factory installed all electrical connections have been made and adjusted at the factory Assemble and install hood in the field UNIT 580F NOMINAL VOLTAGE 3 Ph 60 Hz VOLTAGE RANGE COMPRESSOR OFM IFM POWER EXHAUST COMBUSTION FAN MOTOR POWER SUPPLY No 1 No 1A No 2 Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA ea Hp FLA FLA LRA FLA MCA MOCP 180 208 230 187 253 32 1 195 ...

Страница 16: ...ory installation instructions included with each accessory A Motormaster I Control 20 F Installation 580F180 and 210 Only Install Field Fabricated Wind Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures See Fig 22 for baffle details Use 20 gage galvanized sheet metal or similar corrosion resistant metal for baffles Use f...

Страница 17: ...ent temperatures at which the unit will operate are To operate down to the ambient temperatures listed Motormaster V controls Fig 24 must be added Field fabricated and installed wind baffles are also required for all units see Fig 22 The Motormaster V control permits opera tion of the unit to an ambient temperature of 20 F The con trol regulates the speed of 3 phase fan motors that are compatible ...

Страница 18: ...elocated See Fig 25 The operating range of tem perature measurement is 40 to 100 F Supply Air Temperature SAT Sensor The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan See Fig 26 This sensor is factory installed The operating range of temperature measurement is 0 to 158 F See Table 10 for sensor tempera ture resistance values The temperature sensor looks l...

Страница 19: ... air dampers will be con trolled to provide free cooling using outdoor air When in this mode the LED next to the free cooling set point potentiome ter will be on The changeover temperature set point is con trolled by the free cooling set point potentiometer located on the control See Fig 28 The scale on the potentiometer is A B C and D See Fig 29 for the corresponding temperature changeover values...

Страница 20: ...per must be in place across terminals SR and SR on the EconoMi erIV controller See Fig 25 and 32 Differential Enthalpy Control For differential enthalpy control the EconoMi erIV controller uses two enthalpy sensors HH57AC078 and CRENTDIF004A00 one in the outside air and one in the return airstream on the EconoMi erIV frame The EconoMi erIV controller compares the outdoor air enthalpy to the return...

Страница 21: ...er position above which the exhaust fan will be turned on When there is a call for exhaust the EconoMi erIV controller provides a 45 15 sec ond delay before exhaust fan activation to allow the dampers to open This delay allows the damper to reach the appropri ate position to avoid unnecessary fan overload Minimum Position Control There is a minimum damper position potentiometer on the EconoMi erIV...

Страница 22: ... terminal TB2 10 When unoccupied mode is desired install a field supplied timeclock function in place of the jumper between terminals TB2 9 and TB2 10 See Fig 27 When the timeclock contacts are closed the EconoMi erIV control will be in occupied mode When the timeclock contacts are open removing the 24 v signal from terminal N the EconoMi erIV will be in unoccupied mode Demand Controlled Ventilati...

Страница 23: ...wice The STDSET Menu will appear 3 Use the Up Down button to select the preset number See Table 12 4 Press Enter to lock in the selection 5 Press Mode to exit and resume normal operation The custom settings of the CO2 sensor can be changed any time after the sensor is energized Follow the steps below to change the non standard settings 1 Press Clear and Mode buttons Hold at least 5 sec onds until ...

Страница 24: ...ell venti lated area to sense average humidity 2 Route thermostat cable or equivalent single leads of colored wire from humidistat terminals through con duit in unit to the low voltage connection on the 2 pole terminal strip TB3 as shown in Fig 34 and Fig 35 See Fig 36 for operation diagram Fig 35 Typical Perfect Humidity Dehumidification Package Control Box Fig 34 Typical Wiring Perfect Humidity ...

Страница 25: ... 25 Fig 36 Perfect Humidity Dehumidification Package Operation Diagram Single Circuit Shown ...

Страница 26: ...rt up Otherwise damage to compressor may result VIII EVAPORATOR FAN Fan belt and variable pulleys are factory installed See Tables 13 20 for fan performance data Be sure that fans rotate in the proper direction See Table 21 for air quantity limits See Table 22 for static pressure information for acces sories and options See Table 23 for fan rpm at various motor pulley settings See Tables 24 and 25...

Страница 27: ...00 950 3057 3 59 1013 3364 3 95 1072 3675 4 31 1129 3991 4 68 1183 4311 5 06 7200 986 3401 3 99 1047 3717 4 36 1104 4037 4 74 1159 4361 5 11 1211 4689 5 50 7500 1022 3770 4 42 1081 4095 4 80 1136 4423 5 19 1189 4755 5 58 1241 5091 5 97 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1044 2345 2 75 1...

Страница 28: ... 4 52 1190 4163 4 88 6900 1000 3298 3 87 1059 3603 4 23 1115 3912 4 59 1168 4225 4 96 1220 4543 5 33 7200 1038 3672 4 31 1095 3986 4 67 1149 4303 5 05 1201 4625 5 42 1251 4950 5 81 7500 1077 4072 4 78 1131 4394 5 15 1184 4720 5 54 1234 5050 5 92 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 4500 1060 2...

Страница 29: ... 1236 5 13 4310 1288 5 50 4622 1313 5 68 4780 1337 5 87 4939 6 500 1219 5 29 4450 1270 5 66 4759 1320 6 03 5073 1344 6 22 5232 1368 6 41 5391 7 000 1258 5 88 4942 1307 6 25 5253 1355 6 62 5569 1378 6 81 5729 1402 7 00 5890 7 500 1299 6 52 5480 1346 6 89 5794 1392 7 27 6113 1415 7 46 6273 1437 7 65 6435 8 000 1341 7 21 6065 1387 7 59 6383 1392 7 97 6704 1453 8 16 6866 1475 8 36 7028 8 500 1385 7 97...

Страница 30: ...24 5915 7 02 1272 6154 7 30 1319 6395 7 59 1364 6639 7 88 9 500 1235 6315 7 49 1282 6552 7 77 1327 6791 8 06 1372 7033 8 34 1415 7276 8 63 10 000 1295 6988 8 29 1340 7225 8 57 1383 7465 8 86 1426 7706 9 14 1468 7949 9 43 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp 6 000 1141 3829 4 54 1196 4082 4 84 ...

Страница 31: ... 6 65 1277 5847 6 94 1323 6088 7 22 1368 6331 7 51 9 000 1244 6011 7 13 1290 6247 7 41 1335 6485 7 69 1380 6726 7 98 1423 6968 8 27 9 500 1308 6687 7 93 1352 6924 8 21 1395 7162 8 50 1437 7402 8 78 1479 7644 9 07 10 000 1372 7401 8 78 1414 7638 9 06 1455 7876 9 34 1496 8117 9 63 1535 8358 9 92 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Watts Bhp Rpm Watts Bhp Rpm ...

Страница 32: ...766 1314 7 55 6 243 8 500 1117 5 74 4 750 1169 6 28 5 190 1219 6 83 5645 1268 7 40 6 114 1315 7 98 6 597 1361 8 58 7 094 9 000 1177 6 75 5 583 1226 7 31 6 047 1274 7 89 6524 1320 8 48 7 015 1365 9 09 7 520 1410 9 72 8 037 9 500 1237 7 98 6 511 1284 8 46 6 999 1329 9 07 7499 1374 9 69 8 012 1417 10 33 8 538 1459 10 98 9 076 10 000 1297 9 12 7 450 1342 9 74 8 051 1385 10 37 8574 1428 11 02 9 110 146...

Страница 33: ... Energy Policy Act of 1992 EPACT effective October 24 1997 UNIT 580F MINIMUM COOLING CFM MINIMUM HEATING CFM MAXIMUM CFM Low Heat High Heat 180 4500 3800 3800 7 500 210 5400 4750 5450 9 000 240 6000 4750 5450 10 000 300 7000 4750 5450 11 250 COMPONENT CFM 4500 5000 5400 6000 7200 7500 9000 10 000 11 250 EconoMi erIV 0 040 0 050 0 060 0 070 0 090 0 100 0 110 0 120 0 140 Perfect Humidity Dehumidific...

Страница 34: ...minimum position of the damper will be increased proportionally As the CO2 level decreases because of the increase in fresh air the outdoor air damper will be proportionally closed Damper position will follow the higher demand condition from DCV mode or free cooling mode Damper movement from full closed to full open or vice versa will take between 11 2 and 21 2 minutes If free cooling can be used ...

Страница 35: ...Condenser and Evaporator Fan Motor Bearings The condenser and evaporator fan motors have permanently sealed bearings so no field lubrication is necessary III EVAPORATOR FAN PERFORMANCE ADJUSTMENT Fig 38 and 39 Fan motor pulleys are factory set for speed shown in Table 1 To change fan speeds 1 Shut off unit power supply 2 Loosen nuts on the 2 carriage bolts in the motor mounting base Install jackin...

Страница 36: ...sing VII POWER FAILURE Dampers have a spring return In event of power failure dampers will return to fully closed position until power is restored Do not manually operate economizer motor VIII REFRIGERANT CHARGE Amount of refrigerant charge is listed on unit nameplate and in Table 1 Refer to GTAC II Module 5 Charging Recovery Recycling and Reclamation section for charging methods and procedures Un...

Страница 37: ... the main valve opens to its preset position The regular factory setting is stamped on the valve body 3 3 in wg To adjust regulator 1 Set thermostat at setting for no call for heat 2 Turn main gas valve to OFF position 3 Remove 1 8 in pipe plug from manifold or gas valve pressure tap connection Install a suitable pressure measuring device 4 Set main gas valve to ON position 5 Set thermostat at set...

Страница 38: ...reenergized by resetting the compressor lockout XIII RELIEF DEVICES All units have relief devices to protect against damage from excessive pressures i e fire These devices protect the high and low side XIV CONTROL CIRCUIT 24 V This control circuit is protected against overcurrent by a 3 2 amp circuit breaker Breaker can be reset If it trips determine cause of trouble before resetting See Fig 45 an...

Страница 39: ... 39 SEE DETAIL C SEE DETAIL C SEE DETAIL C 580F180275 Low Heat 580F180360 High Heat AND 580F210275 300275 Low Heat 580F210360 300360 High Heat Fig 44 Spark Gap Adjustment ...

Страница 40: ... 40 Fig 45 Typical Wiring Schematic 580F240 208 230 V Shown ...

Страница 41: ... 41 Fig 46 Typical Component Arrangement 580F240 Shown ...

Страница 42: ...ir Temperature Sensor OCCUP Occupancy Sensor OFC Outdoor Fan Contactor OFM Outdoor Fan Motor LEGEND NOTES 1 Compressor and or fan motor s thermally protected three phase motors protected against primary single phasing conditions 2 If any of the original wire furnished must be replaced it must be replaced with Type 90 C or its equivalent 3 Jumpers are omitted when unit is equipped with economizer 4...

Страница 43: ...ubleshooting D DCV Demand Controlled Ventilation and Power Exhaust To check DCV and Power Exhaust 1 Make sure EconoMi erIV preparation procedure has been performed 2 Ensure terminals AQ and AQ1 are open The LED for both DCV and Exhaust should be off The actuator should be fully closed 3 Connect a 9 v battery to AQ positive node and AQ1 negative node The LED for both DCV and Exhaust should turn on ...

Страница 44: ...s Check flame ignition and sensor electrode positioning Adjust as needed No gas at main burners Check gas line for air purge as necessary After purging gas line of air allow gas to dissipate for at least 5 minutes before attempting to relight unit Check gas valve Water in gas line Drain water and install drip leg to trap water No power to furnace Check power supply fuses wiring and circuit breaker...

Страница 45: ...t system Locate restriction and remove Compressor Operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Excessive...

Страница 46: ... 46 Fig 47 IGC Control Heating and Cooling LEGEND IGC Integrated Gas Unit Controller NOTE Thermostat Fan Switch in the AUTO position ...

Страница 47: ...n DCV or fully open supply air signal INPUTS OUTPUTS Demand Control Ventilation DCV Enthalpy Y1 Y2 Compressor N Terminal Outdoor Return Stage 1 Stage 2 Occupied Unoccupied Damper Below set DCV LED Off High Free Cooling LED Off Low On On On On Minimum position Closed On Off On Off Off Off Off Off Low Free Cooling LED On High On On On Off Modulating between min position and full open Modulating betw...

Страница 48: ...6 Gas pressure 1 10 Heat anticipator settings 10 13 High pressure switch 10 38 Hinged access doors 38 Horizontal adapter roof curb 4 Humidistat 24 Indoor air quality sensor 21 Integrated gas controller Error codes 46 Liquid propane 10 12 Low pressure switch 10 38 Main burners 34 37 Manual outdoor air damper 15 Motormaster I control 16 17 Motormaster V control 17 18 Mounting Compressor 26 Unit 4 Na...

Страница 49: ...d skills programs are available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training which includes hands on experience with the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALO...

Страница 50: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 04 53580003 01 ...

Страница 51: ......

Страница 52: ... VERIFY SETSCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS II START UP ELECTRICAL SUPPLY FAN AMPS EXHAUST FAN AMPS TEMPERATURES OUTDOOR AIR TEMPERATURE F DB Dry Bulb RETURN AIR TEMPERATURE F DB F WB Wet Bulb COOLING SUPPLY AIR F GAS HEA...

Отзывы: