  500mm  

  368mm  

(14.5")

(20")

 A 

2 layers of minimum 16mm (5/8") 

fireproof insulation must be installed 

on all surfaces of ceiling box

Supporting structure 

for fireproof insulation

Fireproof 

insulation

 

Ceiling surface

1. Prepare ceiling cut out & ceiling box. 

Ceiling box minimum internal dimensions must 

be as showin table.

Heater must be installed with heater surface at 

least 2400mm above the floor level.

2. From below, bring ceiling frame up and into 

ceiling cut out.

3. Fasten ceiling frame to ceiling box

 

through 

mounting  holes with fasteners (not supplied).

4. Prepare heater for installation

Attach mounting brackets to both ends 

of heater with supplied fasteners

CEILING RECESS KIT (SOLD SEPARATELY)

MODEL

DIMENSION "A"

2000W & 4000W

1170mm (46")

3000W & 6000W

1463mm (57.5")

www.bromicheating.com