background image

 

5

 

2

 

5

2

S2000-IP

 

S2000-KDL

"-MAL"

"+MAL"

Figure 1.

 Wiring Diagram 

Addressable 

Device

 

Addressable 

Device

 

S2000-IP

ANALOGUE ADDRESSABLE 

RATE-OF-RISE AND FIXED TEMPERATURE DETECTOR 

S2000-IP rev.02 (version 2.02) 

 

INSTRUCTION MANUAL 

1 TECHNICAL DATA 

1.1 General

 

S2000-IP rev.02 is a combination Rate-of-Rise and Fixed Temperature Heat Detector. It is designed to provide fire protection and to be used with 

S2000-KDL Multiplex Addressable Loop (MAL) controller in Orion integrated security systems. In standard usage mode both sudden temperature 
increases that match the predetermined alarm criteria and fixed ambient temperature point exceeding cause the detector to issue fire alarms. In 
analogue mode S2000-IP returns the S2000-KDL measured temperature values, the S2000-2 making its own decisions to issue fire alarms or fire 
prealarms in accordance with user programmable temperature thresholds. 

Moreover, S2000-IP responds with the measured ambient temperature values in degrees Centigrade upon the relevant request of the network 

controller (either S2000/S2000-M console or ARM Orion). 

Both detector power and communication between the detector and the S2000-KDL controller are accomplished over the two wire Multiplex 

Addressable Loop controlled by S2000-KDL. The detector supports MAL_v2.xx protocol and provides measuring of the addressable loop voltage at 
its location. 

The detector is designed for round the clock operation. 

1.2 Specification

 

1.3 Standard Delivery

 

1) Fixed Temperature 

- from +54 to +65

°

С

 

Single-piece

 delivery: 

2) Current Consumption 

- 0.5 mA max 

- S2000-IP rev.02 Detector 

- 1 pc. 

3) Input Voltage 

 

- from 8 to 10V 

- Address Label  

- 1 pc. 

4) Technical Readiness Time 

- 60s max 

- Instruction Manual 

 

- 1 pc. 

5) Measurement Accuracy 

- ± 1

°

С

 

 

6) Operating Temperatures 

- from 

30 to +55

°

С

 

 

7) Relative Humidity 

- up to 93% at +40

°

С

 

Group

 delivery: 

8) Ingress Protection Rating 

- IP 41 

- S2000-IP rev.02 Detector 

- 10 pcs. 

9) Weight 

- 0.2 kg max 

- Address Label 

- 1 pc. 

10) Storage Temperature 

- from 

50 to +50

°

- Instruction Manual 

а

 

 

- 1 pc. 

11) Overall Dimensions: Diameter 

- 100 mm max 

 

Height 

- 52 mm max 

 

2 OPERATION INSTRUCTIONS

 

2.1  S2000-IP Wiring Diagram.

 

Figure 1 shows the standard diagram to wire S2000-IP detectors into 

a two wire Multiplex Addressable Loop controlled by S2000-KDL. 

If an S2000-IP is used to detect fire the S2000-KDL is programmed 

to monitor for the S2000-IP with zone type 3, Heat (in the standard 
mode) or 9, Heat Analog Addressable With Programmable Threshold (in 
the analogue mode). 

If, otherwise, an S2000-IP is used in thermostatic systems the S2000-

KDL is programmed to monitor for the S2000-IP with zone type 10, 
Thermal. To get information about zone types and S2000-KDL 
programming, please refer to the S2000-KDL User’s Manual as well as used network controller description. 

2.2 Mounting

 

Heat detectors are installed on ceilings at distances at least 15cm from relevant walls. 

There are three ways to attach S2000-IP detectors (see Figure 2). To attach a detector to solid surface (Variant 

А

) the detector base plate provided 

is used. Optionally, Suspended Ceiling Mounting Kit MK-1 (Variant B) or 

МК

-2 (Variant C) can be purchased to install a S2000-IP detector into a 

suspended ceiling. 

 

 
 
 
 
 
 
 
 

 

1

S2000-IP Detector 

2

LED 

3

Alignment Guides 

4

The Mark and the Bar, 

OPEN HERE 

5

Base Plate 

6

*:  S2000-IP Suspended Ceiling Mounting Kit MK-1 

7

*:  S2000-IP Suspended Ceiling Mounting Kit MK-2 

 

* : ordered separately 

Figure 2

Figure 3 

ISO 9001 

Reviews: