OPERATION MANUAL

AXIAL FANS

Axis / Tubo

EN

AXIS-QRA

AXIS-QA G

AXIS-Q

TUBO-F

AXIS-QA

TUBO-M/MZ

AXIS-QR

AXIS-F

Summary of Contents for Axis series

Page 1: ...OPERATION MANUAL AXIAL FANS Axis Tubo EN AXIS QRA AXIS QA G AXIS Q TUBO F AXIS QA TUBO M MZ AXIS QR AXIS F ...

Page 2: ... 3 Transport and storage requirements 3 Manufacturer s warranty 4 Fan design 4 Delivery set 4 Modifications and options 5 Technical data 10 Mounting and operation guidelines 11 Mounting sequence 11 Installation and connection to power mains 13 Maintenance 14 Warranty card CONTENT ...

Page 3: ...not contain any dust or other solid impurities sticky substances or fibrous materials The fan is not designed for use in an inflammable and explosive medium The transported medium must not have an aggressive effect on steel at the temperature stated on pages 5 8 of the section Technical data Do not close or block the fan intake or exhaust vent not to disturb the normal air passage Do not sit on th...

Page 4: ...AXIS QRA FAN DESIGN AXIS F FAN DESIGN TUBO M TUBO MZ MODIFICATIONS AND OPTIONS MODIFICATIONS AND OPTIONS flange impeller cover casing casing terminal block impeller mounting bracket TUBO M Fan made of polymer coated steel TUBO MZ Fan made of galvanized steel AXIS Q Fan with a square mounting plate AXIS QR Fan with a round mounting plate Fig 1 Fig 2 Fig 3 fan 1 item operation manual flange impeller...

Page 5: ...60 50 60 50 60 50 60 Power W 75 92 140 147 180 240 250 325 Current A 0 35 0 4 0 65 0 66 0 82 1 08 1 2 1 46 Max air flow m3 h 1340 1475 2500 2650 3580 3890 4680 4790 RPM min 1 1350 1405 1380 1700 1380 1655 1350 1600 Noiselevel 3m dBA 58 59 62 63 63 64 64 65 Max transported air temperature C 30 60 30 50 30 60 30 50 30 60 30 50 30 60 30 50 Ingress Protection Rating IP24 Axis F IPX4 IP24 Axis F IPX4 I...

Page 6: ...370 320 155 4 2 Axis Q 250 4E Axis Q 250 4D 260 7 370 320 155 4 1 Axis Q 300 2E 326 9 430 380 195 5 3 Axis Q 2 300 D 326 9 430 380 155 5 3 Axis Q 300 4E 326 9 430 380 195 5 1 Axis Q 300 4D 326 9 430 380 155 5 1 Axis Q 350 4E Axis Q 350 4D 388 9 485 435 200 7 1 Axis Q 400 4E Axis Q 400 4D 417 9 540 490 240 8 8 Axis Q 450 4E Axis Q 450 4D 465 11 576 535 250 10 6 Axis Q 500 4E Axis Q 500 4D 520 11 65...

Page 7: ...65 605 636 11 5 660 230 17 3 13 9 Axis F 630 4E Axis F 630 4D 645 674 715 11 5 740 250 20 13 16 4 Type Dimensions mm Weight kg Ø D Ø D1 Ø D2 Ø d L Axis QR 200 2E 210 250 280 7 145 2 5 Axis QR 250 2E Axis QR 250 2D 260 295 320 7 155 3 4 Axis QR 250 4E Axis QR 250 4D 260 295 320 7 155 3 4 Axis QR 300 2E 326 380 397 9 195 4 4 Axis QR 300 2D 326 380 397 9 155 4 4 Axis QR 300 4E 326 380 397 9 195 4 7 A...

Page 8: ...ght kg Ø D Ø d B B1 L Axis QA 150 162 7 250 210 120 2 5 Axis QA 200 208 7 312 260 120 3 0 Axis QA 250 262 7 370 320 140 3 5 Axis QA 315 312 9 430 380 170 6 1 Overall dimensions Tubo F 200 2E Tubo F 250 2E Tubo F 250 4E Tubo F 300 2E Tubo F 300 4E Tubo F 350 4E Voltage 50 Hz V 230 230 230 230 230 230 Power W 55 80 50 145 75 140 Current A 0 26 0 4 0 22 0 66 0 35 0 65 Max air flow m3 h 860 1050 800 2...

Page 9: ... Tubo MZ 250 262 283 270 55 30 3 7 Tubo M 315 Tubo MZ 315 315 337 278 55 40 4 9 The Tubo M fans are equipped with MD polymer coated steel and MDZ Zn galvanised steel reducers for connection to 150 mm 200 mm and 250 mm air ducts The reducers are not included in the delivery set and must be ordered separately Tubo F Axis QA G Type Dimensions mm Weight kg Ø D Ø d B B1 L Axis QA 150 G 162 7 325 275 12...

Page 10: ...ent and quick access for servicing and repair operations The fan must be grounded While mounting protect the fan against water ingress in the following way 1 Install an outer hood above in case of vertical mounting position fig 13 MOUNTING SEQUENCE Fig 13 Fig 14 Fig 22 Fig 15 Fig 23 Fig 16 Fig 18 Fig 20 Fig Fig 17 Fig 21 Fig 19 AXIS Q AXIS QR AXIS QA AXIS QRA Fig 24 Fig 25 Fig 26 Fig 27 ...

Page 11: ...h an automatic switch at the external input Connect the fan to power mains through the automatic switch The contact gap on all poles at least 3 mm The automatic switch trip current must be in compliance with the fan current consumption refer Table on pag es 5 6 Install the automatic switch to ensure prompt access Cut power supply to the fan off by turning the automatic electric switch QF to OFF po...

Page 12: ...o INSTALLATION AND CONNECTION TO POWER MAINS AXIS QA AXIS QRA TUBO M TUBO MZ TUBO M TUBO MZ Fig 50 Fig 51 Fig 52 Fig 53 Fig 42 Fig 43 Fig 44 Fig 45 AXIS Q AXIS QR AXIS F Fig Fig 47 Fig 46 Fig 54 Fig 56 Fig Fig 48 Abb Fig 49 Fig 55 AXIS QA G ...

Page 13: ...e impeller motor impeller blades Mounting sequence of the fan is shown on fig 59 70 Clean the impeller blades with a soft cloth or a brush wetted in a mild soap solution Avoid liquid splashing on the motor Clean the impeller blades thoroughly at least once in 6 months Operation recommendations 1 Clean the fan regularly from dust dirt and foreign objects 2 Check all fastening connections periodical...

Page 14: ... EEC on the approximation of the laws of the Member States relating to electromag netic compatibility which relate to electrical appliances used in set voltage classes This certificate is issued following test carried out on samples of the product referred to above Quality Inspector s Stamp Manufacture Date ____________________ Company Expert s Full Name Date Signature Axial fans Axis___________ T...

Page 15: ...www blaubergventilatoren de 15 Axis Tubo ...

Page 16: ...BL_AXIS_4 8 _EN www blaubergventilatoren de ...