Summary of Contents for AFII 100

Page 1: ...ructions provided in this manual regarding your responsi bilities in caring for your heating equipment Contact a professional qualified service agency for installation start up or service work To the...

Page 2: ...Page2 RWB 6104 BAFII R01 All manuals and user guides at all guides com...

Page 3: ...uel Line Valves and Filters 6 Prepare the Burner 7 General 7 Low Fire Rate Baffle if specified 7 Mount Burner on Appliance 7 Connect Fuel Lines 7 Wiring Connection Diagram 8 Start the Burner and Set C...

Page 4: ...e agency for the installation adjustment and service of your oil heating system This work requires technical training trade ex perience licensing or certification in some states and the proper use of...

Page 5: ...or writing You will find the serial number on the silver label located on the left rear of the burner Refer to Figure 1 inspect Prepare installation Site Clearances to Burner and Appliance Provide spa...

Page 6: ...g of all appliances within the enclosure The openings should have free access to the build ing interior which should have adequate infiltration from the outside Exhaust fans and other air using device...

Page 7: ...ilter located near the fuel tank and a secondary filter rated for at least 10 microns located near the burner Also install a generous capacity filter rated for 50 microns or less inside the building b...

Page 8: ...r when the combustion chamber is very hot Do not attempt to re establish flame with the burner running if the flame becomes extinguished during start up venting or adjustment Vaz0or Filled Aoj01iance...

Page 9: ...the control locks out three times in a row the control enters restricted lockout 5 IGNITION CARRYOVER Once flame is estab lished the ignition remains on for 10 seconds to ensure flame stability befor...

Page 10: ...k the smoke and CO2 levels and readjust the burner if necessary Once combustion is set tighten all fasteners on air dial rear access door and escutcheon plate Start and stop the burner several times t...

Page 11: ...low rates at various pressures see ac companying chart 1 Turn off power to burner before proceeding 2 Disconnect copper oil connector tube from noz zle line 3 Loosen the screw that fastens the rear ac...

Page 12: ...or is scratched the nozzle will not function properly To install a new nozzle place a 3 4 open end wrench on the nozzle adapter Insert the nozzle into the adapter and secure finger tight Finish tighte...

Page 13: ...r Dial Setting Firing Rate AFII 85 AFII 100 AFII 150 140 psig 0 40 0 65 3 0 60 0 75 4 3 0 70 0 85 5 4 0 75 1 00 5 2 0 95 1 20 3 1 15 1 35 4 1 25 1 50 5 Head AFII 85 AFII 100 AFII 150 FB0 0 40 0 65 0 5...

Page 14: ...Replacement Parts Diagram For best performance specify genuine _ __ replacement parts SK8265B Page 14 RWB 6104 BAFII R01 All manuals and user guides at all guides com...

Page 15: ...d Head insulator Kit FB0 3 4 6 only 2184404U 31658 Speci_ 51671U 51672U 51685 Item Kit No 12 51805U 13 51485 14 51584U 51476U 15 21444U 16 213 17 Speci_ 18 51481 19 20 21 22 23 Description Igniter Ele...

Page 16: ...ctive in material or workmanship and within the warranty period may be returned for credit as follows Beckett Burners Beckett branded major components and non Beckett branded major components that cam...