background image

AB-6584 

  Azbil Corporation’s Infilex series controllers: Infilex is named for “Infinity” and “Flexible.”

 

 

Specifications/Instructions

 

Infilex

 AC 

AHU Controller 

Model WY5317C 

 

General 

Infilex AC (Infilex: named for “Infinity” and “Flexible”) Model 
WY5317C is a DDC (direct digital control) controller for AHU 
(air handling unit).  It can be placed in a small place such as 
an AHU control panel. 

Infilex AC is equipped with inputs and outputs suitable for 
AHU control, and its software can be freely edited in 
response to the applications. 

In terms of operation, Infilex AC can be operated with a user 
terminal (Neopanel

 / Neoplate) or Operator Panel to 

correspond with various situations.  Besides, it performs 
advanced control and management by communicating with 
BMS (building management system) savic-net

 FX via 

LonTalk

®

 protocol.  Infilex AC integrated into BMS enables 

autonomous control since Infilex AC itself has the time 
scheduling function. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Features 

 Compact 

design: 

Small size body can be fit into a control panel of a 
compact AHU unit. 

 

Various input/output (I/O) configurations: 
Model number changes depending on the number of its 
I/O points, which allows external cooling control, 
humidification, and other AHU controls. 

 

User interface module (Operator Panel): 
Operator Panel (panel mount type/integral type) 
connected to Infilex AC allows you, without changing the 
settings from the BMS center unit, to change the Infilex 
AC settings. 

 

Remote control with a user terminal: 
Neopanel

 or Neoplate is connectable, so that a user at 

a remote location can perform ON/OFF operation and 
change temperature setting. 

 

Autonomous distributed control: 
Even if a trouble occurs in the BMS center unit, the 
backup operation is performed individually to distribute 
potential risks caused by malfunction of the system. 

 

 I/O 

module: 

To Model WY5317C0400, one I/O module can be added 
so that the number of I/O points is increased. 

 Cooperation 

with 

BMS: 

To perform advanced control and management, Infilex 
AC can directly communicate with the BMS center unit 
(savic-net

 FX client PC). 

 Installation: 

Quick-fit screwless (clamp) terminal blocks are used for 
the I/O terminal block, ensuring the labor saving of the 
wiring work. 
Additionally, a desired mounting method can be selected 
from two kinds of mounting methods, DIN rail mounting 
and screw mounting. 

 

CE Marking certified product: 
Infilex AC conforms to all the applicable standards of CE 
Marking (Class A). 

 

 

 

 

Summary of Contents for Infilex WY5317C

Page 1: ...number of its I O points which allows external cooling control humidification and other AHU controls User interface module Operator Panel Operator Panel panel mount type integral type connected to Infilex AC allows you without changing the settings from the BMS center unit to change the Infilex AC settings Remote control with a user terminal Neopanel or Neoplate is connectable so that a user at a ...

Page 2: ...atmospheric condition etc specified in this manual to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Install a circuit breaker or circuit protector in the power supply circuit that supplies the power to the product Use crimp terminal lugs with insulation for electric wires connected to the screw terminals Connect cables to the pow...

Page 3: ...ote units sub controllers can be connected Max wiring length of LS bus is 900 m Infilex GC Model WY5311 Infilex AC Model WY5317C Infilex ZM Model WY5322 Infilex VC Model WY5306 Infilex FC Model WY5305 Infilex VC Model WY5306 LS bus LonTalk protocol Neoplate Analog user terminal Neopanel Digital user terminal SMS Client PC Infilex AC Model WY5317C Infilex GC Model WY5311 Infilex GD Model WY5310 PMX...

Page 4: ...4 Temperature input 2 pts voltage input 2 pts digital input 8 pts voltage output 6 pts relay output 6 pts 1 user interface module and or 1 I O module can be combined e g for proportional humidifying control outdoor air cooling control the same as Model WY 5317C03 outdoor air cooling control 00 Fixed Notes For I O modules and user interface modules UT module and Operator Panel to be combined with I...

Page 5: ...ee contact Input signal RTD Pt 100 Ω 0 C Temperature input Measuring range 20 C to 80 C Input voltage range 1 V to 5 V Input Voltage input Input impedance 500 kΩ Output method Relay output N O contact N O contacts share the same common line Max 24 V AC 0 5 A inductive load cos φ 0 4 or more Contact rating Max 24 V DC 0 5 A Relay output normally open N O contact Min applicable load 5 V 10 mA Output...

Page 6: ... stripped length 8 mm pin terminal cannot be used Organize the cables with cable binding bands so as not to hide LED battery holder or tag JIS Japanese Industrial Standards KPEV is a wiring standard provided by Furukawa Electric Co Ltd JCS Japanese Electric Wire and Cable Makers Association System common Ground line is used as a common line for signal transmission Actuator damper thus has to have ...

Page 7: ...V Temperature input 20 to 80 C Relay output for momentary only 24 V AC DC 1 2 3 4 5 6 7 8 9 10 11 12 DO1 DO2 DO3 DO4 DO5 DO6 13 14 15 16 17 18 19 20 21 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 IN OUT CONF COM AI1 AI2 AI3 AI4 AO1 AO2 AO3 AO4 AO5 AO6 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 COM COM COM COM Relay output for momentary maintained 24 V AC DC Voltage input 1 to 5 V Digital input curr...

Page 8: ...AB 6584 8 Dimensions Figure 4 Dimensions mm 60 140 90 ...

Page 9: ...Data Setter adaptor Part No DY5301S0000 For details of Data Setter adaptor Part No DY5301S0000 refer to its Specifications manual see Note Figure 6 Connection example of Data Setter with Data setter adaptor to LC bus port CONF port of Infilex AC LED for operating status S1 switch Do not press S1 switch Battery holder Indication tag DIN rail mounting hook Infilex AC Model WY5317 Infilex GC Model WY...

Page 10: ...ithium battery with the power ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Figure 7 Battery replacement 1 Pull out the battery holder using a slotted screwdriver 2 Disconnect the battery connector and detach the lithium battery from the battery holder 3 Place a new lithium battery in the bat...

Page 11: ...after the power is turned on During this time the LED on the front lights up temporarily but this does not indicate an error Be sure to use a small power circuit to turn on off the fan Be sure to use a shielded wire for the signals output to the inverter Leave at least 35 mm clearance between the top bottom surfaces of the product and other devices Peel off the protective sheet on the top surface ...

Page 12: ...AB 6584 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 3 0 Sep 2015 AB 6584 H W03 J AI 6584 Rev 3 1 Printed in Japan 12 ...