Installation Operation & Maintenance Instructions for the 

PuroPak-CP 

 

 
Step 1: Clean The Closed Loop Hydronic System With Clean 5 

 
Add 1 bottle (500 mL or 16.9 oz.) of AXI-THERM CLEAN 5 for every 100 litres (25 gallons) of 
water (Dosage: 0.5 %). Lower concentrations do not yield satisfactory results. Higher concentrations 
have no adverse effects.  
 
Use an AXI-THERM INJET, or a mechanical fill pump to add the product to the system. Clean 5 
may be circulated in one of two ways: 1) Power Flushing with external high velocity pump (see 

Figure 1 ‘A’) or by circulating throughout the entire system using the existing system circulators (see 

Fi

gure 1 ‘B’). 

 

 
When Power Flushing, the heating appliance must be off during the entirety of the cleaning process, 
2-

4 hours, (Figure 1 ‘A’). When 

Clean 5 is left to circulate through the entire system it is 

recommended to shut the heating appliance off only while the solution is being added to the system. 
Once cleaner has been administered the system operation may be restored and should be circulated 

for at least 2 days and may remain in the system for up to 30 days (Figure 1’B’). 

  

 
Once the cleaning operation is completed, the system should be well drained and rinsed. Rinsing 
should continue until the water runs clear. If the water does not run clean, repeat the cleaning session.  
 
 

 

 

 

 

 

 

Figure 

1 ‘A’

Power flush Clean 5 through existing 

system via mechanical pump. Depending on the 
severity of encrustrations, power flushing may 
require 2-4 hours of run time 

Figure 

1 ‘B’

Circulate Clean 5 through system via 

existing system circulators. Circulate for 2-30 days 
before draining and rinsing. 