background image

 

 

Specifications

MULTI FUNCTION TIMER

AT11DN/AT11EN SERIES

Sockets (PG-11, PS-11(N)) are sold separately.

AT 11 DN -

No mark

100-240VAC 50/60Hz, 

24-240VDC

1

12VDC

2

24VAC 50/60Hz, 24VDC

DN

Time limit 2c

EN

Instantaneous 1c 

+ Time limit 1c

11

11-pin plug type

AT

Analog Timer

Power

supply

Time operation

Number of plug pins

Item

Model

AT11DN-

AT11EN-

Function

Multi Function Timer

Control time setting range

1

0.05 sec. to 100 hour

Power supply

•100-240VAC

 50/60Hz, 24-240VDC

 universal  •24VAC

 50/60Hz, 24VDC

 universal  

• 12VDC

Allowable voltage range

90 to 110% of the rated voltage

Power consumption

•Max. 3.5VA (100-240VAC

) ,

Max. 1.5W (24-240VDC

)

•Max. 4VA (24VAC

), 

 

 

Max. 1.5W (24VDC

•Max. 1W (12VDC

)

•Max. 4.3VA (100-240VAC

) , 

Max. 2W (24-240VDC

)

•Max. 4.5VA (24VAC

), 

 

 

Max. 2W (24VDC

•Max. 1.5W (12VDC

)

Return time

Max. 100ms

Time operation

Signal ON Start

Min. input signal width

START, RESET, INHIBIT: Min. 50ms

Input

START, RESET, INHIBIT: [No-voltage input] - Short-circuit impedance: Max. 1

,

Residual voltage: Max. 0.5VDC, Open-circuit impedance: Max. 100

Control

output

Contact type

Time limit DPDT (2c)

Instantaneous SPDT (1c)+Time limit SPDT (1c)

Contact capacity 250VAC

 5A resistive load

Relay

life cycle

Mechanical

Min. 10,000,000 operations

Electrical

Min. 100,000 operations (250VAC 5A resistive load) 

Repeat error

Max. ±0.2% ±10ms

Setting error

Max. ±5% ±50ms

Voltage error

Max. ±0.5%

Temperature error

Max. ±2%

Insulation resistance

100

 (at 500VDC megger) 

Dielectric strength

2,000VAC 50/60Hz for 1 minute

Environ-

ment

Ambient temp.

-10 to 55

, Storage: -25 to 65

 

Ambient humid. 35 to 85%RH, Storage: 35 to 85%RH 

Approval

  

Accessory

Bracket

Weight

2

Approx. 132.2g (approx. 85g)

Approx. 134.7g (approx. 87.5g)

I N S T R U C T I O N   M A N U A L

 

Safety Considerations

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

Please observe all safety considerations for safe and proper product operation to avoid hazards.

Safety considerations are categorized as follows.

Warning

 Failure to follow these instructions may result in serious injury or death.

Caution 

Failure to follow these instructions may result in personal injury or product damage.

The symbols used on the product and instruction manual represent the following

 symbol represents caution due to special circumstances in which hazards may occur. 

Warning

 

Caution

 

Ordering Information

 

Time Specifications

 

AT11DN SERIES

 

AT11EN SERIES

 

Unit Description

 

Connections

1: AC/DC voltage: 100-240VAC 50/60Hz, 24-240VDC

                               : 24VAC 50/60Hz, 24VDC      

       DC voltage: 12VDC

RESET

START

INHIBIT

6

5

4

3

2

1 11

10

9

8

7

CONTACT OUT: 

250VAC 5A

RESISTIVE LOAD

1

(Time limit

 1c)

(Time limit 1c)

RESET

START

INHIBIT

6

5

4

3

2

1 11

10

9

8

7

CONTACT OUT: 

250VAC 5A

RESISTIVE LOAD

1

(Time limit 1c)

(Instantaneous

 1c)

The above specifications are subject to change and some models may be discontinued 

without notice.

Be sure to follow cautions written in the instruction manual and the technical descriptions 

   (catalog, homepage).

Time range Time unit Time setting range
0.5

sec 

0.05 to 0.5 sec.

1.0

0.1 to 1 sec.

5

0.5 to 5 sec.

10

1 to 10 sec.

0.5

min

0.05 to 0.5 min.

1.0

0.1 to 1 min.

5

0.5 to 5 min.

10

1 to 10 min.

0.5

hour

0.05 to 0.5 hour

1.0

0.1 to 1 hour

5

0.5 to 5 hour

10

1 to 10 hour

0.5

10h

0.5 to 5 hour

1.0

1 to 10 hour

5

5 to 50 hour

10

10 to 100 hour

Mode

Time chart

A

t

t1

t2

Power 2-10

START 2-6

INHIBIT 2-5

RESET 2-7

Time limit contact N.C.

Time limit contact N.O.

Time limit output indicator

Operation/Power indicator

Signal ON

Delay

F

t

t

t-a

t

t1

t2

Power 2-10

START 2-6

INHIBIT 2-5

RESET 2-7

Time limit contact N.C.

Time limit contact N.O.

Time limit output indicator

Operation/Power indicator

Flicker

(OFF Start)

F1

t

t

t-a

t

t1

t2

Power 2-10

START 2-6

INHIBIT 2-5

RESET 2-7

Time limit contact N.C.

Time limit contact N.O.

Time limit output indicator

Operation/Power indicator

Flicker 1

(ON Start) 

C

t

t-a

t1

t2

t-a

Power 2-10

START 2-6

INHIBIT 2-5

RESET 2-7

Time limit contact N.C.

Time limit contact N.O.

Time limit output indicator

Operation/Power indicator

Signal OFF

Delay

D

t

t

t-a t1

t2

t-a

t

t-a t-a

START 2-6

INHIBIT 2-5

RESET 2-7

Time limit contact N.C.

Time limit contact N.O.

Time limit output indicator

Operation/Power indicator

Power 2-10

Signal 

ON/OFF

Delay

I

t

t

t

t-a

t-a t1

t2

Operation/Power indicator

Time limit output indicator

Time limit contact N.O.

Time limit contact N.C.

INHIBIT 2-5

START 2-6

Power 2-10

RESET 2-7

Interval

If power is cut or the RESET terminal is short-circuited, the timer will be reset.

If the INHIBIT terminal is short-circuited during a time limit operation, the time will stop.

In case of F, F1 output operation mode, setting time should be over 100ms. 

    If not, it may cause abnormal output operation due to under 100ms of setting time.

[t: Setting time, t=t1+t2, t>t-a]

 

Output Operation Mode

64.5

50

15

44.8

 

Dimensions

 

Panel cut-out

 

Bracket

31

55

56

20

15

21

5

45

16

48.6

44.9

36

 (unit: mm)

 

Cautions during Use

 

Major Products

 Photoelectric Sensors

 Temperature Controllers

 Fiber Optic Sensors

 Temperature/Humidity Transducers

 Door Sensors

 SSRs/Power Controllers

 Door Side Sensors

 Counters 

 Area Sensors

 Timers

 Proximity Sensors

 Panel Meters

 Pressure Sensors

 Tachometers/Pulse (Rate) Meters

 Rotary Encoders

 Display Units

 Connector/Sockets

 Sensor Controllers

 Switching Mode Power Supplies

 Control Switches/Lamps/Buzzers

 I/O Terminal Blocks & Cables

 Stepper Motors/Drivers/Motion Controllers

 Graphic/Logic Panels

 Field Network Devices

 Laser Marking System (Fiber, Co

, Nd: YAG) 

 Laser Welding/Cutting System

M

ain 

circ

uit

(Figure 1)

< Sensor >

Power

Rectification

circuit

Isolation

transformer

<External sensor

   power supply>

START

RESET

INHIBIT

1: Refer to time specifications for control time setting range by model.

2: The weight includes packaging. The weight in parenthesis is for unit only.

Environment resistance is rated at no freezing or condensation.

48

55

Operation/Power indicator 

(Flashes for timer operation,

Turns ON for timer stop)

Output operation mode indicator

(sec, min, hour, 10h mode)

Output operation 

mode indicator

(A, F, F1, 

C, D, 

mode)

Output operation 

mode setting SW

Time limit output 

indicator

Time range indication

Time range setting switch

Min. 65

Min. 65

45

45

+0.6

0

+0.6

0

1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury 

  or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, 

  railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)

 

Failure to follow this instruction may result in fire, personal injury, or economic loss.

2. Install on a device panel to use.

 

Failure to follow this instruction may result in electric shock or fire.

3. Do not connect, repair, or inspect the unit while connected to a power source.

 

Failure to follow this instruction may result in electric shock or fire.

4. Check 'Connections' before wiring.

 

Failure to follow this instruction may result in fire.

5. Do not disassemble or modify the unit.

 

Failure to follow this instruction may result in electric shock or fire.

1. Use the unit within the rated specifications.

  Failure to follow this instruction may result in fire or product damage.

2. Use dry cloth to clean the unit, and do not use water or organic solvent.

  Failure to follow this instruction may result in electric shock or fire.

3. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, 

  radiant heat, vibration, impact, or salinity may be present.

  Failure to follow this instruction may result in fire or explosion.

4. Keep metal chip, dust, and wire residue from flowing into the unit.

  Failure to follow this instruction may result in fire or product damage.

http://www.autonics.com

 

HEADQUARTERS:

18, Bansong-ro 513beon-gil, Haeundae-gu,  

Busan, South Korea, 48002

TEL: 82-51-519-3232

 

E-mail:

 [email protected]

DRW171149AA

DRW171149AA

1. Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.

2. 12VDC, 24VDC, 24VAC power supply should be insulated and limited voltage/current or Class 2, SELV power 

  supply device.

3. When supplying or turning off the power, use a switch or etc. to avoid chattering.

4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.

5. In order to block peripheral current, use isolation transformer which of secondary part is not grounded as (Figure 1) 

  to supply power to the external input device.

6. In order to avoid leakage current flowing, connect resistance and condenser as (Figure 3).

  If connect as (Figure 2), it may cause malfunction due to leakage current.

7. Do not connect two or more timers with only one input contact or transistor simultaneously.

8. Keep away from high voltage lines or power lines to prevent inductive noise.

  In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at 

  input signal line.

  Do not use near the equipment which generates strong magnetic force or high frequency noise.

9. Change setting time, time range, operation mode or etc. after turning off the power of the timer.

10. This unit may be used in the following environments.

   ①

Indoors (in the environment condition rated in 'Specifications')

   ②

Altitude max. 2,000m

   ③

Pollution degree 2

   ④

Installation category II

Power

Power

Timer

Timer

 (Figure 2)

 (Figure 3)

R
C

T

R

C

T

Leakage

current

Reviews: