POOL HEAT PUMP 

MANUAL 

(R32, ON/OFF Type) 

Automated Environmental Systems Ltd., Unit 1, 1 Wimbledon Avenue, Brandon, Suffolk IP27 0NZ

01842 819130 | [email protected] 

Summary of Contents for Remora f10

Page 1: ...1 POOL HEAT PUMP MANUAL R32 ON OFF Type Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 2: ...er 12 6 2 Usage of wire controller 13 6 3 Unit status query 19 6 4 Parameters query settings 20 7 ERROR CODES 21 8 MAINTENANCE AND INSPECTION 22 9 WIRING DIAGRAM 28 10 CABLE SPECIFICATION 31 11 WIFI APP APPLICATION 32 READ THIS MANUAL CAREFULLY BEFORE OPERATING THE UNIT DO NOT THROW IT AWAY RETAIN FOR FUTURE REFERENCE BEFORE OPERATING THE UNIT ENSURE THE INSTALLATION HAS BEEN CARRIED OUT IN ACCORD...

Page 3: ...s manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics a Durable The heat exchanger is made of PV...

Page 4: ...g regulations Do not operate your air conditioner in a wet room such as a bathroom or laundry room Before obtaining access to terminals all supply circuits must be disconnected An all pole disconnection device which has at least 3mm clearances in all pole have a leakage current that may exceed 10mA residual current device RCD having a rated residual operating current not exceeding 30mA disconnecti...

Page 5: ...ste bin that is underneath the appliance indicates that this product at the end of its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for ...

Page 6: ...ms are found inside the box Carton Box Item Image Quantity Swimming pool heat pump 1 Operation and Installation Manual 1 Winter Cover 1 Accessories 1 Set Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 7: ... f15 Remora f20 Remora f23 A 552 657 707 B 826 933 1125 C 100 157 181 D 610 606 750 E 346 356 429 F 370 380 453 G 96 96 87 H 260 370 370 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 8: ...lve assembly 4 Evaporator 14 Right panel 5 Left panel 15 Handle 6 Fan bracket 16 Titanium heat exchanger 7 Fan motor 17 Pressure gauge 8 Fan blade 9 Grill 10 Front panel Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 9: ... reference only Please check the water inlet outlet label on the heat pump while plumbing installation The schematic diagram is for reference only Please check the water inlet outlet label on the heat pump while plumbing installation The controller is mounted on the wall 5 2 Swimming Pool Heat Pumps Location The unit will perform well in any outdoor location provided that the following three facto...

Page 10: ...en the pool water and the ground surrounding the pipe which translates to about 3 to 5 increase in run time 5 4 Swimming Pool Heat Pumps Plumbing The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no special plumbing arrangements except bypass please set the flow rate according to the nameplate The water pressure drop is less than 10kPa at max Flow rate Since there ...

Page 11: ... to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is completed you should follow these steps 1 Turn on your filter pump Check for water leaks and verify flow to and from the pool 2 Turn on the electrical power supply to the unit then press the key ON OFF of wire controller It should start in several seconds ...

Page 12: ...MAGE THE DIGITAL CONTROLLER NEVER INSPECT OR SERVICE THE DIGITAL CONTROLLER YOURSELF REFER TO A QUALIFIED SERVICE ENGINEER Features and functions Basic controller functions The basic controller functions are Turning the heat pump ON OFF 24 hour time clock Timer ON and timer OFF Parameter adjustment Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 ...

Page 13: ... upward option or increase the parameter value DOWN Press this button to select the downward option or decrease the parameter value TIMER ON Press this button to set timer on TIMER OFF Press this button to set timer off CLOCK Press this button to set clock or system time Notes If there is no operation for 10s it will automatically save the settings and go back to the previous interface Automated E...

Page 14: ...u can press to shut down the unit For example 6 2 2 Mode switch When the unit is ON you can choose heating or cooling mode by pressing for 5s It is not available when the unit is OFF For example Heating indicator light on Cooling indicator light on press press for 5s Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsyst...

Page 15: ...n press and to set the target temperature of inlet water Press to save the settings and it will go back to the previous interface If you want to check the settings you set press or it will be displayed For example Flash press press Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 16: ...then press to increase value or press to decrease value After you finishing the settings you can press to save the settings and set next number or press to save and go back to the previous interface For example Flash press press press press Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 17: ...ss to save the setting and set minutes or back to the timer interface The settings will be also saved by pressing and it will back to the previous interface the timer on indicator light on If you press the settings will not be saved The setting of timer off is as the same as setting timer on use instead of press or Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 ...

Page 18: ...an press once to enter into the timer interface then press and the timer will be cancelled you will see the timer on off indicator light off press press press press press press or Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 19: ... 18 For example Timer on indicator light off press press Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 20: ...below Code Parameter Name Range o 2 Inlet water temp 31 99 o 3 Outlet water temp 31 99 o 4 Ambient temp 31 99 A 1 Compressor exhaust gas temp 0 150 A 2 Coil temp 31 99 A 3 Compressor suction gas temp 31 99 A 4 Compressor current A 5 Opening of the EEV Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 21: ... Range Default L0 Temperature Differential 1 18 2 L1 Heat Mode Temp Set 20 40 28 L2 Cool Mode Temp Set 8 30 12 L3 Auto Mode Temp Set 8 40 28 L26 Defrosting Cycle Set 20min 90min 45min L27 Defrosting Entry Coil Temp Set 15 1 7 L28 Max Defrosting Time Set 5min 20min 8min L29 Defrosting Exit Temp Set 1 40 13 L30 Ambient Coil Temp Differential to Enter Defrosting 0 30 10 L32 Water Pump Mode 0 OFF when...

Page 22: ... Communication failure E22 Ambient temp failure E25 N A P01 Water flow protection P02 High pressure protection P06 Low pressure protection P10 N A P11 High compressor exhaust gas temp protection P15 Big inlet outlet water temp difference protection P16 Low outlet water temp protection under cooling mode P17 Anti freeze protection when unit in standby mode P18 N A P19 N A P23 Low outlet water temp ...

Page 23: ...gnition is minimised For repair to the refrigerating system the following precautions shall be complied with prior to conducting work on the system prolonged period of no usage Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed General work area All maintenance staff and others...

Page 24: ...e manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant containing parts are installed The ventilation machinery and outlets are operating adequately and are not obstructed If an indirect refrigerating circuit is being used the secondary ...

Page 25: ...materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment Intrinsically safe components do not have to be isolated prior to Repair to intrinsically safe...

Page 26: ...of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the system or isolated by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing process Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other pur...

Page 27: ...ts In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant relea...

Page 28: ...ation valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as ...

Page 29: ...r to the wiring diagram on the electric box Models Remora f6 Remora f8 Remora f10 Remora f12 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 30: ... 29 Models Remora f15 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 31: ... 30 Models Remora f20 Remora f23 0NZ 0NZ Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 32: ...Please refer to table below Heat Pump Model Cable Size Remora f6 3x1 5mm2 Remora f8 Remora f10 3x2 0mm2 Remora f12 Remora f15 3x2 5mm2 Remora f20 3x4 0mm2 Remora f23 3x6 0mm2 The above are an indication only Please refer to qualified electricians if in doubt Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Page 33: ...bile phone 11 2 Startup software After the installation completed click Smart Life icon on the desktop to use this APP 2 Recognize this trademark 1 Search smart life 3 Install Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 34: ... 33 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 35: ... 34 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 36: ... 35 Input family name location rooms then press Done Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 37: ... 36 11 3 Add device Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...

Page 38: ... entering the 1 Press for 5s 2 Flash Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk right hand icon light flashes quickly If this light is flashing skip this step ...

Page 39: ... 11 4 Control Set temperature Slide on the screen to adjust Device information Running mode Timer settings Switch ON OFF Mode setting Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk ...