Acano solution 

Acano Server Installation Guide 

 

 

Acano 

February 2014 

76-1002-04-D 

 

 

 

 

 

 

 

 

Summary of Contents for Solution

Page 1: ...Acano solution Acano Server Installation Guide Acano February 2014 76 1002 04 D...

Page 2: ...ation 11 4 1 Creating an Administrator Account 11 4 2 Setting up the Network Interfaces for IPv4 12 4 3 Creating the Web Admin Interface Certificate 13 4 4 Configuring the Web Interface for HTTPS Acce...

Page 3: ...e not designed to be load bearing The power units do not have an on off switch the server will power on as soon as power is connected Therefore do not do so until instructed DC power option only See A...

Page 4: ...Up to five Ethernet patch cables The cabling required depends on your network speed and the length of the cable run 10GBASE T Cat 6 patch or Cat 6A 1000BASE T Cat 5e Cat 6 or Cat 6A 100BASE T Cat 5e...

Page 5: ...low Not all the connections are required during installation Figure 1 Acano Server front panel Figure 2 Acano Server back panel with power units installed OK and Warning status lights Power units stat...

Page 6: ...LEDs There are four LEDs on the front of the Acano Server OK Warning Power Supply A and Power Supply B They have the following behavior OK Blue normal operation Warning If on red check the cause urge...

Page 7: ...The Acano Server Acano solution Installation Guide 76 1002 04 D Page 7 Amber Link at 1G Off Link at 10 100M Right Green Link up Blinking Activity on link Off Link down...

Page 8: ...e server 12 x M5 cage nuts and 12 x M5 screws for fixing the rails and ears into the rack 4 Lift the rack rails out of the packaging noting the orientation in each case that is which end goes at the f...

Page 9: ...until they latch see Figure 2 Notes Do not connect power to the server at this time DC power option only See Appendix A for DC wiring instructions Do not switch on the power at this time 14 Connect a...

Page 10: ...lation Acano solution Installation Guide 76 1002 04 D Page 10 speed and cable length The interface LEDs show which speed is in use See the section LED descriptions 16 If required connect the other int...

Page 11: ...e Acano Server Console port to a terminal emulator using the serial cable supplied in the box Use baud rate 115200 8 data bits no parity and 1 stop bit Note Be sure that the login prompt is displayed...

Page 12: ...nds to configure that interface To set the Admin interface to 1GE full duplex type iface admin 1000 full and to switch auto negotiation on or off type iface admin autoneg on off We recommend that the...

Page 13: ...te to install onto the Acano Server For users happy to trust that Acano meets requirements for generation of private key material private keys and associated Certificate Signing Requests can be genera...

Page 14: ...st is pending taken under submission then follow the steps in Appendix D before going on to step 3 below CAUTION If you are using a CA with the Web Enrolment feature installed you may copy the CSR tex...

Page 15: ...webadmin certs webserver key webserver crt webadmin listen mmp 443 webadmin enable Note Be sure to use the same names as the certificates you uploaded in section 4 3 34 Test that you can access the W...

Page 16: ...0950 1 IEC 60950 1 or equivalent see http www ul com Wiring Use 10 AWG wire for the RTN 48V and ground earth connections The RTN is the positive power connection and the 48V is the negative power conn...

Page 17: ...rposes only and its contents are subject to change without notice This document may not be reproduced or transmitted in any form or by any means for any purpose other than the recipient s personal use...