Trouble shooting guide

If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the 
following table as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes 
from the right column.

If the unit still does not work after checking these possible causes, contact ABB service in Australia on 1300 666 595, 
Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help. Our trained service personnel will usually be able to 
take your call immediately and assist you in resolving your difficulty. ABB is committed to providing valuable through-life 
support for its products. 

Exit LED Quickfit

®

Standard, Nexus LX, Nexus RF

Installation manual

Doc no. 29-01100

Congratulations

Congratulations on choosing to use this ABB product covered by our unique through-life support system. This document 
is designed to assist you during the installation of this product; for the safety of yourself and others 

ABB recommends 

that you read this document thoroughly before commencing installation

. The fittings are designed for easy 

installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through 
regular and appropriate servicing, will perform reliably for many years to come.

Safety warning

In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000,  
AS/NZS2293). Refer to the applicable standards for data and mains cabling installation procedures and requirements.

Important note: This product is designed for indoor use only.

Nexus LX (data cable system)

The Nexus

®

 range of emergency light fitting are designed to be connected together into a special communication network 

over a Level 4 (or higher) high speed, single twisted pair data cable. The Nexus user and technical guide describes all 
you need to know to successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your 
nearest ABB product supplier. The network cabling of the building must be installed as per the procedure detailed in the 
Nexus user and technical guide. No mains or mains carrying cables are to be connected to the data terminals or cables.

Nexus RF (wireless system)

The Nexus RF range of light fittings are designed to communicate via a proprietary RF network, however the electrical 
installation of the fittings is identical to that of a standard non-monitored fitting.

This document covers

What’s inside the box

Safety warning

Main chassis and diffuser assembly

Installation instructions

Ceiling bracket assembly

Removal instructions

Pictograph insert pack

Testing precautions

Hole plug set (6 pieces)

Trouble shooting guide

Installation manual

Warranty information

No.

Fault

Possible causes

1

LED light source and indicating LED not lit

AC supply not connected; or

AC supply turned off; or

Unit not inserted into the base properly; or

Test switch damaged

2

LED light source is lit but indicating LED not lit

Test switch damaged; or

Battery not connected

3

LED light source does not switch to emergency mode when the 

test button is pressed

Test switch damaged

4

LED light source works momentarily on emergency when the test 

button is pressed

Battery not yet charged (allow up to 24 hours)