background image


ABB Australia Pty Limited

For enquiries
ABB contact centre: 1800 60 20 20
E-mail: [email protected] 

www.stanilite.com.au

© Copyright 2022 ABB. All rights reserved. 

Doc no. 29-EEIS003_B

 

I N S TA LL ATI O N  M A N UA L 

Stanilite®

Ecoexitblade Exit Sign

9

A

K

K

10

8

4

6

6

A

6

17

0 - B - A

u

g

u

st 2

0

22

Troubleshooting guide

If you have installed and connected the fitting as per the instructions and it does not function 
correctly, use the following table as a guide to fixing the problem. Look up the type of fault in 
the left column and check the possible causes from the right column. 

If the fitting still does not work after checking these possible causes, please contact your place 
of purchase.

No. Fault

Possible causes

1

LED light source and red LED not lit

AC supply not connected; 

or

 

AC supply turned off; 

or

Test switch damaged

2

LED light source is lit but red LED not lit

AC supply not connected; 

or

AC supply turned off; 

or

Test switch damaged; 

or

Battery not connected or faulty

3

LED light source does not switch to emergency mode 
when the test button is pressed

Test switch damaged; 

or

Battery not connected or faulty

4

LED light source works momentarily on emergency 
when the test button is pressed

Battery not yet charged (allow up to 24 hours)

Thank you for choosing ABB product

Please read this document thoroughly before 
commencing installation and retain for future 
reference. The installation instructions were 
correct at the time of print. To reflect changes in 
technology and Australian standards; ABB reserves 
the right to amend the instructions without notice. 
Updated document can be found on the Stanilite 
website. 

Safety warning

In Australia and New Zealand, only licensed 
electricians are permitted by law to work with 240 
volt electrical installations. Do not attempt to 
install or connect this product unless you are a 
licensed electrician. Turn off and isolate the 
electrical supply before connecting this fitting to 
the building wires. Do not touch the terminals of 
the terminal block when the light fitting is  
energized. The only user serviceable part is the 
battery pack. The LED light source is not user 
serviceable. Do not attempt to service other parts 
of the fitting as this will void the warranty. As the 
installer, it is your responsibility to ensure 
compliance with all relevant building and safety 

codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to 

the applicable standards for mains cabling 
installation procedures and requirements. 

This document covers

What’s inside the box

Safety warning

Ecoexitblade Base assembly

Testing precautions

Ecoexitblade Blade assembly

Troubleshooting guide

Pictograph insert pack

Instructions on

Installation manual

Installation

Warranty information

Battery replacement

Product removal

In accordance with AS 60598.2.2:2016 the 
luminaire classification is CA90. Insulation can 
abut but cannot cover the luminaire. 
Where possible we recommend to leave a gap
surrounding the luminaire.

Not suitable for use with loose-fill insulation.
No fire rated box is required for the product.

Class II luminaire, protection against electric 
shock is provided by double insulation or 
reinforced insulation.

This luminaire is suitable for indoor use only.

Product Specification

•  Norminal design Voltage: 240 V~50 Hz.
•  Line current: 43 mA
•  In-rush current: 38.5 A/50 

μs

• 

Circuit power: 2.9 W standby, 4.4 W max.

• 

Battery: LiFePO4 3.2 V 1500 mAh  

• 

Viewing Distance (m): 24  

• 

Classification (C0/C90): D10 / C10  

• 

Test Mode: Manual  

• 

Protection Class: II

• 

IP Rating: IP20  

• 

Operating Temp. (

): 10 to 40

90