Monitor de Corriente y Protección Diferencial  RGU-10 B

RGU-10 B  Residual Current device and Monitor

CONSIDERACIONES INICIALES

INSTALACIÓN Y PUESTA EN MARCHA

¡ IMPORTANTE !

!

DESCRIPCIÓN GENERAL

Si se utiliza el equipo de forma no especificada por el fabricante, la protección 
puede resultar comprometida.

Electronic  type  B  earth  leakage  current  protection  and  monitoring  relay. Associated  to 
external  core    balance    transformer  the 

.  It  has  2 

programmables outputs relays. Main trip and prealarm signal. It has one free voltage input 
for  external TRIP/RESET.  Mounting  in  DIN  rail  466277  (En50022)  or  PANEL  72x72  by 
means  of  accesories  M5ZFF1.  Displays  setting  values  and  instantaneus  earth  leakage 
current value.

WG-xx-TB  and  WGC-xx-TB  families

GENERAL DESCRIPTION

PRELIMINARY CONSIDERATIONS

INSTALLATION AND START-UP

¡ IMPORTANT !

!

The  unit´s  protections  systems  might  not  be  effective  if  the  unit  is  used  for 
purpose other  than those specifications by the manufacturer.                

El equipo no debe ser utilizado hasta que haya finalizado por 
completo su instalación. El equipo debe conectarse a un circuito 
de alimentación protegido con fusibles acorde con el rango de 
alimentación  y  consumo  del  mismo.  A  su  vez  el  circuito  de 
alimentación  tiene  que  estar  provisto  de  un  interruptor 
magnetotermico o dispositivo equivalente para desconectar el 
equipo de la red de alimentación.   Durante el conexionado se 

2

aconseja una sección cable permitida entre 1- 1.5 mm . Un par 
de  apriete  recomendado  de  0,5-0,6  N.m  y  una  longitud  a 
desaislar cable de 7 mm.

terminals and opening covers or removing elements, can 
give  access  to  dangerous  parts  to  touch. The  equipment 
must not be used until it has completely finished installation. 
The  unit  must  be  connected  to  a  power  supply  circuit 
protected  by  fuses  in  line  with  the  range  and  power 
consumption. In turn, the supply circuit must be provided 
with a circuit breaker or equivalent device to disconnect the 
equipment  from  the  mains.  During  the  wiring  cable  is 
advisable  a  section  permitted  between  1  -  1.5  mm2.  A 
recommended torque of 0.5-0.6 N.M. Cable Stripping Tools 
length 7 mm.

Dispositivo de protección/ monitorización diferencial tipo B. Se asocia a los toroidal 
externo  de las familias WG-xx-TB y WGC-xx-TB. Dispone de relés programables, 2 
salidas. Disparo relé principal  y de señalización por prealarma. Posee entrada libre 
de tensión para disparo y rearme exterior. Montaje en Carril DIN 46277 (EN 50022) o 
en panel 72x72 mediante accesorio (M5ZZF1). Permite  visualizar  por  display  los 
valores  de  ajuste y  de la  corriente de  fuga  instantánea.

P11951

RGU-10 B           

0,1-0,3-0,5-1-3 

P 1 X X X X 0 0 X

Código

Code

Código interno
 

Internal code

Tensión/alimentac

Power supply

230 Vc.a./

a.c.

 

0

0,1-0,2-0,3-0,4-0,5-0,75-1-5-10 

Retardo disparo (s)
   

Tripping delay

Sensibilidad (A)
   Sensivity

Tipo

Type

Código
  

code

COMPROBACIONES A LA RECEPCIÓN

Asegurarse del cumplimiento de:
               - El equipo corresponde a las especificaciones de su pedido.
               - El equipo no ha sufrido desperfectos durante el transporte.

PRECAUCIONES DE SEGURIDAD

Para la utilización segura del equipo, es fundamental que las personas que lo instalen o 
manipulen, sigan las medidas de seguridad habituales, así como las advertencias en dicha 
guía rápida.

El RGU-10 B es un equipo diseñado específicamente para ser instalado dentro de un 
cuadro eléctrico o envolvente, con fijación en carril DIN o en panel  mediante accesorio.  
Dispone de LED luminoso (ON) indicando que hay presencia de tensión. Aunque este 
LED no esté encendido, no exime al usuario de comprobar que el equipo está 
desconectado de toda de toda fuente de alimentación.

CHECKS ON RECEPTION

On receving the instrument, check the following points:
               - The unit’s specifications are the same as those on your order.
               - Check that the device has not suffered any damage during transport.

SAFETY  PRECAUTIONS

The staff using or handling the unit  must follow the common safety measures and warnings 
included in the instruction manual. 

The RGU-10 B unit has been specifically designed for its installation in a electric board, 
enclosure to a DIN rail or mounted in panel by means of accesories.  It has a flashing green 
LED (ON) when it is operation and, therefore, it shows that there is  voltage and current in 
the electronic circuit. The user must make sure that the equipment is not conected to the 
power supply at all the times, even when the LED is not flashing.

The user must take into account and observe the informations and warnings included in this 
instruction manual to guarantee the correct operation of the equipment and comply whit the 
safety  specifications.  The  equipment  must  not  turned  on  until  is  fully  installed  in  the 
electrical panel.

Disconnect the equipment from the power supply when the unit´s safety protection systems 
are not working or there are signs of a problem (in case of visible damage). In this case, 
contact a qualified technical service or with our own technical service (TAS).

INSTALLING THE EQUIPMENT

DIN rail installation. Through the CBT must pass all live conductors supplyng electrical 
energy to  loads or part of the installation which requires it to earth leakage  protection with 
this device. In single-phase installation (phase and neutral, L and N), three phase - 3 wires 
(three phases, L1, L2  and L3) or three phases - 4 wires (L1, L2, L3 and N).  All  connections 
Should be inside t he  electrical  board. Please  note  that  with  the  connected   equipment,

Peso 

/ Wheight 

: 168 gr

52,5

85

45

43,5

67,9

Fijación carril/ 
Fixed by rail DIN 46277

 (EN 50022)

cotas en mm

dimensions in mm.

Optoacoplada, 0.7W /230 Vac 

± 

20%

Corriente Nominal:  10 Ac.a.
Tensión Nominal:  250 Vc.a.   
Carga Nominal:   2500 V·A en AC1

DESCRIPCIÓN DE BORNES

CARACTERÍSTICAS

Corriente Nominal:  10 Ac.a.
Tensión Nominal:  250 Vc.a.   
Carga Nominal:   2500 V·A en AC1

1 - 2   Entrada disparo externo

        3  Sin uso
        4  Contacto salida relé prealarma común
        5  Contacto salida relé prealarma NC
        6  Contacto salida relé prealarma NA
        7  Sin uso

        8  Entrada toroidal 1S1
        9  Entrada toroidal 1S2

      10  Alimentación Aux. 

(fase o neutro)

      11  Alimentación Aux. 

(neutro o fase)

      12  Sin uso

     13  Contacto salida relé disparo NA

     14  Contacto salida relé disparo NC

     15  Contacto salida relé disparo  COMUN

BORNES DE CONEXIONADO

La presente guía rápida contiene informaciones y advertencias que el usuario tiene que 
respetar  para  garantizar  el  funcionamiento  seguro  del  equipo.  En  su  funcionamiento 
habitual  no debe ser utilizado hasta su instalación definitiva en el cuadro eléctrico. 

Cuando sea probable que el equipo haya perdido la protección de seguridad (presencia de 
daños visibles) debe desconectarse la alimentación del equipo. En este caso póngase en 
contacto con el servicio técnico cualificado, o bien, con nuestro S.A.T. (Servicio Asistencia 
Técnica).

INSTALACIÓN DEL EQUIPO

La instalación en carril DIN. Por el toroidal asociado tienen que pasar todos los conductores 
activos  que alimentan a las cargas o parte de la instalación en la que se requiera realizar la 
protección diferencial con este equipo. En instalación monofásica (fase y neutro, L y N), 
trifásica (las tres fases, L1,L2 yL3) o trifásica mas neutro (L1, L2, L3 y N). En el interior del 
cuadro eléctrico. A tener en cuenta, que con el equipo conectado, los bornes y la apertura 
de cubiertas o eliminación de elementos, puede dar acceso a partes peligrosas al tacto. 

M98230212-20-15A

TERMINAL CONNECTIONS 

             TERMINAL DESCRIPCIÓN

FEATURES

1 - 2 External Input Trip / Reclose
     3 Not used
     4 Pre-alarm output relay common
     5 Pre-alarm output relay, NC
     6 Pre-alarm output relay common
     7 Not used
     8 Input C.B.T.  1S1
     9 Input C.B.T.  1S2
   10 Supply 230 Va.c. (Phase or Neutral)
   11 Supply 230 Va.c. (Neutral or Phase)
   12 Not used
   13 Tripping output relay NO
   14 Tripping output relay NC
   15 Tripping output relay COMMON

Rated current:   10 A

c.a.

Rated voltage: 250 V

c.a.

   

Rated Load:  2.500 V·A en AC1

Rated current:   10 A

c.a.

Rated voltage: 250 V

c.a.

   

Rated Load:  2.500 V·A en AC1

Optocoupled, 0.7W /230 Vac 

±

 

20%

8

9

1

2

4

5

6

10 11

13 14 15

Reset

Test

Tipo

Type

Tipo

Type