background image

Relion

®

 SAM600

Switchgear control unit SAM600-IO
Version 2.2

Operation manual

Summary of Contents for Relion SAM600-IO

Page 1: ...Relion SAM600 Switchgear control unit SAM600 IO Version 2 2 Operation manual...

Page 2: ......

Page 3: ...Document ID 1MRK 500 131 UEN Issued June 2021 Revision C Product version 2 2 2017 2021 Hitachi Power Grids All rights reserved...

Page 4: ...roduct includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit https www openssl org This product includes cryptographic software written developed by Eric Young eay cryptsof...

Page 5: ...ould create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so...

Page 6: ...ning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by Hitachi Power Grids in accordance with the produc...

Page 7: ...view 13 4 1 User interface 13 4 1 1 Introduction 13 4 2 PCM600 tool 13 4 2 1 Connectivity packages 13 4 3 SAM600 IO LHMI service kit 14 4 3 1 Display 14 4 3 2 Keypad 16 4 4 Local HMI functionality 18...

Page 8: ...supervision 38 6 2 5 Non operative functions 38 6 3 IED parameterization 38 6 3 1 IED settings for IED functionality 39 6 3 2 IED settings for different operating conditions 39 Section 7 Operating pr...

Page 9: ...D status via the LHMI hint menu 52 8 2 Indication messages 53 8 2 1 Internal faults 53 8 2 2 Warnings 54 8 2 3 Additional indications 55 8 3 Correction procedures 55 8 3 1 Creating user accounts and s...

Page 10: ...4...

Page 11: ...fault The manual provides information related to the need of LHMI service kit to monitor diagnostics and make configuration changes 1 2 Intended audience GUID C9B8127F 5748 4BEA 9E4F CC762FE28A3A v11...

Page 12: ...er in which the IED should be installed The commissioning manual contains instructions on how to commission the IED The manual can also be used by system engineers and maintenance personnel for assist...

Page 13: ...technical reference during the engineering phase installation and commissioning phase and during normal service 1 3 2 Document revision history GUID 7099E1DB 1CD6 4037 A418 92AB57FA9462 v5 Document re...

Page 14: ...equipment may result in degraded process performance leading to personal injury or death It is important that the user fully complies with all warning and cautionary notices 1 4 2 Document convention...

Page 15: ...ed Working in a high voltage environment requires serious approach to avoid human injuries and damage to equipment M2362 2 v1 Do not touch circuitry during operation Potentially lethal voltages and cu...

Page 16: ...are made in the IED measures should be taken to avoid inadvertent tripping GUID F2A7BD77 80FB 48F0 AAE5 BE73DE520CC2 v1 The IED contains components which are sensitive to electrostatic discharge ESD...

Page 17: ...ur products and processes 3 2 Disposing of the IED AMU0600460 v6 Definitions and regulations of hazardous materials are country specific and change when the knowledge of materials increases The materi...

Page 18: ...12...

Page 19: ...entation 4 2 1 Connectivity packages GUID D480127C 3F19 44A3 9A6F A8549C02CDCD v2 A connectivity package is a software component that consists of executable code and data which enables system tools to...

Page 20: ...d in 670 650 series which includes the following elements Display LCD Keypad LED indicators Communication port for PCM600 Serial cable for connection between the SAM600 IO LHMI service kit and the ser...

Page 21: ...tatus area shows the current IED time the user that is currently logged in and the object identification string which is settable via the LHMI or with PCM600 If text pictures or other items do not fit...

Page 22: ...are used to navigate in different views or menus The push buttons are also used to acknowledge alarms reset indications provide help and switch between local and remote control mode The keypad also c...

Page 23: ...t in use for SAM600 IO with LHMI service kit 8 Escape 9 Left 10 Down 11 Up 12 Right 13 Key 14 Enter 15 Remote Local Not in use for SAM600 IO with LHMI service kit 16 Uplink LED 17 Not in use 18 Multip...

Page 24: ...el Scrolling active digits of a parameter when entering a new setting value Left Right Moving left and right in menus Selecting pages in the SLD Changing the active digit of a parameter when entering...

Page 25: ...Trip LED red LED state Description Off Normal operation On A protection function has tripped An indication message is displayed if the auto indication feature is enabled in the local HMI The trip indi...

Page 26: ...r cover plate X402 for the service port on SAM600 IO 3 Connect the service port cable between SAM600 IO and the LHMI service kit 4 Power on SAM600 IO 4 6 Removing the LHMI service kit from SAM600 IO G...

Page 27: ...ts VIEWER Viewer Can read parameters and browse the menus from LHMI OPERATOR Operator Can read parameters and browse the menus as well as perform control actions ENGINEER Engineer Can create and load...

Page 28: ...ive For passwords see the section Password policies GUID 75BBAD63 2CA0 4169 97C8 2EC31C945FF4 v1 See the Cyber security guideline for information on cyber security 4 8 Communication GUID 12C44065 8E0C...

Page 29: ...SE TX with connector RJ45 IEC 61850 FTP PTP HSR PRP SNTPv4 RFC2030 SFP Galvanic RJ45 The IED supports SNTPv4 RFC2030 PTP or Binary time synchronization methods with a time stamping resolution of 1 ms...

Page 30: ...24...

Page 31: ...IED before changes for example setting parameter or local remote control state changes are saved IEC13000282 1 en vsd GUID 6B1C3B17 FFD1 4D3C A50B 29524361C368 V1 EN US Figure 7 Saving changes animati...

Page 32: ...V3 EN US Figure 9 Selecting the user name 4 Select OK on the on screen keyboard and press to stop editing the user name 5 Press to select the Password field and press to activate it An on screen keyb...

Page 33: ...D and the following message is displayed IEC13000283 1 en vsdx IEC13000283 V1 EN US Figure 12 Error message indicating blocked ID The logon dialog appears if the attempted operation requires another l...

Page 34: ...e display backlight has turned off The factory default for display timeout is 10 minutes The minimum is 1 minute The display returns to the default view and all unconfirmed operations for example para...

Page 35: ...Level Set the parameter ContrastLevel via Main menu Configuration HMI Screen SCREEN 1 to permanently change the display contrast 5 1 7 Navigating in the menu AMU0600412 v7 Navigate the menus and chang...

Page 36: ...pwards press To scroll the view downwards press To jump from the last row to the first row press again Press to jump from the first row to the last row 5 1 7 3 Changing the default view GUID 068D31CD...

Page 37: ...or to select No and to exit IEC13000054 2 en vsd IEC13000054 V2 EN US Figure 19 Selecting a setting group 6 To browse the settings scroll the list with and and to select a setting press To move back t...

Page 38: ...ned steps digits smaller than the step value cannot be edited 3 Press or to move the cursor to another digit 4 To select the minimum or maximum value select the arrow symbol in front of the value To s...

Page 39: ...etrieved using the HMI 1 Activate the setting mode and select a setting When editing string values the cursor moves to the first character 2 Press to open the editor An on screen keyboard is shown on...

Page 40: ...9E 478E 97AC 4E33897E5085 v6 Editable values are stored in the non volatile flash memory Most of the parameter changes take effect immediately after storing but some parameter changes require applicat...

Page 41: ...he Clear view IEC17000246 1 en vsd IEC17000246 V1 EN US Figure 24 Clear view The content of the Clear menu depends on the configuration configured with PCM600 2 Select the item to be cleared with or 3...

Page 42: ...00065 2 en vsd IEC13000065 V2 EN US Figure 25 Help menu Section 5 1MRK 500 131 UEN Rev C Using the HMI 36 Switchgear control unit SAM600 IO Operation manual 2017 2021 Hitachi Power Grids All rights re...

Page 43: ...Only authorized and skilled personnel should analyze possible errors and decide on further actions Otherwise stored disturbance data can be lost 6 2 1 Disturbance recording triggering GUID 5569488B F9...

Page 44: ...ther actions The IED records IED status data and events Document all the recorded data from the IED before resetting the tripping and IED lockout functions 6 2 5 Non operative functions GUID 752CDABC...

Page 45: ...e editing of setting group values the new values are activated The user can either commit the edited values or discard them 6 3 2 IED settings for different operating conditions GUID 7328A918 CE00 4F9...

Page 46: ...40...

Page 47: ...status Ethernet port Route configuration status 7 1 1 1 Monitoring an internal IED fault GUID 67B6F8FD 3E2B 4EA6 8822 539F7FA3678B v4 If there is an internal fault in the IED the reason for the fault...

Page 48: ...7 1 2 1 Creating disturbance recordings GUID B0CE46C1 1219 4BA2 9627 E53FC0413409 v5 Normally disturbance recordings are triggered by the IED applications but the recording can also be triggered manu...

Page 49: ...to monitor disturbance recorder data 1 Select Main menu Disturbance records All disturbance records are listed 2 Scroll the view with or IEC13000262 1 en vsd GUID ACB5A57F 394B 475B 96C0 7C515A530D1F...

Page 50: ...GUID 257DAC08 C4E7 4BB2 9654 630C3AAF29FC v4 The event view contains a list of events produced by the application configuration The events are grouped by day and each event takes one line Select the o...

Page 51: ...IED values For more information see PCM600 documentation 7 2 Resetting the IED 7 2 1 Clearing and acknowledging via the local HMI GUID 9880CE57 79DE 4949 B9FA 1E91ED2F5F4B v5 Use the Clear button to r...

Page 52: ...Do not switch off the auxiliary power supply to the IED before changes For example when setting parameter changes are saved 7 3 1 1 Activating a setting group AMU0600439 v8 IED settings are planned i...

Page 53: ...up for editing 2 Press on the Setting group line in the dialog box to activate selection mode 3 Select the wanted setting group with or and press IEC13000241 1 en vsd GUID 5196A07A 9DAF 4696 8773 F52A...

Page 54: ...elongs to a setting group 8 To browse the settings scroll the list with and 9 To edit the selected setting press In case of a parameter that is not part of a setting group the parameter is activated f...

Page 55: ...38 Changing the setting value 10 Press or to change the value 11 Confirm the change with 1MRK 500 131 UEN Rev C Section 7 Operating procedures Switchgear control unit SAM600 IO 49 Operation manual 20...

Page 56: ...50...

Page 57: ...Identifying runtime errors GUID 105A9FFE 75F3 4E65 BFF7 F31268CD7DCE v8 1 Check the error origin from IED s internal event list Main menu Diagnostics IED status General 2 Reboot the IED and recheck t...

Page 58: ...tical Ethernet via ST connectors Check that the LinkStatus value is 1 that is the communication is working When the value is 0 there is no communication link 8 1 4 2 Checking the time synchronization...

Page 59: ...ends LDCM AnalogLatency LDCM analog latency is different in local and remote Check the LDCM parameters AnalogLatency and remAinLatency at both ends HW Configuration missing HW configuration necessary...

Page 60: ...instance number is shown as part of the fault indication such as 3 in this example Internal Fail BOM4 Error A binary out module error has occurred The instance number is shown as part of the fault in...

Page 61: ...rd setting and password changing is done using PCM600 If Central Account Management is enabled in the IED user account creation and initial password setting is done using the SDM600 server Individual...

Page 62: ...data for example 100 mA at 24 V AC DC Output relays especially power output relays are designed for breaking high currents Due to this layers of high resistance may appear on the surface of the contac...

Page 63: ...dimmed diode The second signal is the status Normal or Forced Forced status is only achieved when the BO is set to Forced or operated on the LHMI Set the parameter TestMode to Off after completing th...

Page 64: ...58...

Page 65: ...odule BOS Binary outputs status BR External bistable relay BS British Standards BSR Binary signal transfer function receiver blocks BST Binary signal transfer function transmit blocks C37 94 IEEE ANSI...

Page 66: ...Carrier send CT Current transformer CU Communication unit CVT or CCVT Capacitive voltage transformer DAR Delayed autoreclosing DARPA Defense Advanced Research Projects Agency The US developer of the T...

Page 67: ...dule GDE Graphical display editor within PCM600 GI General interrogation command GIS Gas insulated switchgear GOOSE Generic object oriented substation event GPS Global positioning system GSAL Generic...

Page 68: ...nformation that is representative of a type In the same way an instance of a function in the IED is representative of a type of function IP 1 Internet protocol The network layer for the TCP IP protoco...

Page 69: ...dard PELV circuit Protected Extra Low Voltage circuit type according to IEC60255 27 PMC PCI Mezzanine card POR Permissive overreach POTT Permissive overreach transfer trip Process bus Bus or LAN used...

Page 70: ...arpoint Neutral point of transformer or generator SVC Static VAr compensation TC Trip coil TCS Trip circuit supervision TCP Transmission control protocol The most common transport layer protocol used...

Page 71: ...me 1 UT1 thus allowing for the eccentricity of the Earth s orbit the rotational axis tilt 23 5 degrees but still showing the Earth s irregular rotation on which UT1 is based The Coordinated Universal...

Page 72: ...66...

Page 73: ...67...

Page 74: ...d Automation Products SE 721 59 V ster s Sweden Phone 46 0 10 738 00 00 https hitachiabb powergrids com protection control 2017 2021 Hitachi Power Grids All rights reserved Scan this QR code to visit...