Caution: 

Before  instaffing  in a nuclear application,  determine 

that  the product is intended tor such use. 

Warning: 

Disconnect power before  installing  or seNicing. 

Description 

ABB  300-Une full-voltage  magnetic motor starters include a magnetic 

contactor and  a three-leg block overload relay, providing motor 

protection against running  and stalled  motor  overloads.  The 

overload  relay  may  be provided with  a yellow trip  indicator  which  is 

located  to the  right of the  reset arm,  and is visible  when  the  overload 

relay is  tripped. 

OVERLOAD  RELAY 

HEATER SLOTS 

Figure 1.  Typical  300-Une magnetic starter. 

Ratings 

CR305 contactors are  suitable for  use  on a  circuit  capable of deliver­

ing  not more than  10,000  RMS  symmetrical  amperes,  600 volts  max­

imum  when  protected by H,  J,  K1,  KS,  RKi,  and RK5 class  fuses  or 

a circuit breaker  having an interrupting rating not  less  than  10,000 

RMS symmetrical  amperes,  600 volts  maximum. 

Installation 

Before  connecting  starter  to power supply: 

1.  Remove a!!  packing. 

2. Clean magnet  mating  surfaces  of any  dirt  or foreign matter. 
3. Select and install  heaters in accordance  with heater  table which 

accompanies  each  starter  unit. 

Caution:  Do not energize starter before heaters are  instalfed. 

4. Operate  movable  magnet by  pressing on the  nameplate  to  assure 

free movement.

5. Mount  starter on  a sturdy vertical support. 

6.  Make  the electrical  connections.

7. The overload relay can be  reset manually by depressing and

releasing the reset arm. 

8. The  ultimate  tripping  current  of  the installed  relay  heater  can  be

adjusted  ± i0%  by  using the adjustment dial,  shown  in  Figure  1.

Coil  Replacement 

1. Remove  power from  the  device.

2. Unscrew  one end  of  the  retainer (B-Figure  1)  and slide  it out of 

the  slot.

3.  Remove movable  magnet assembly.
4. Loosen four coil  retainer  screws  (C-Figure  1}.  Press against coil

and pull up and out on  coil  retainers (A-Figure  1).

5.  Remove coil  from  magnet. 

6.  Replace coll.

7.  Reassemble device by reversing procedure.

Contact  Replacement 

1 .  Perform steps  1  through 5 under 

Coil Replacement. 

2. Remove complete  magnet assembly by pulling entire assembly

from  the contactor  assembly,

3. With the  magnet  assembly resting on its side,  remove  the

movable arm by  sliding it  out the back of the assembly.

4. Depress  movable contact and spring and slide  movable contact

from  movable  arm. 

5.  Remove screws  holding  stationary contact in  place and  remove 

stationary contact.

6. Reassemble by  reversing the above procedure.  When reassem­

bling,  note  that  the cover  will fit only one way.  Magnet and

movable arm will  fit either  way but  will  be quleter  if  reassembled

the  same  way they were  taken  apart.

NOTE:  Do not attempt to remove  or replace arc traps  in  molded 

cover. 

Figure  2. 

Overload  Relay  Check 

Remove power  from the device,  disconnect the control  wiring  from 

the  relay  terminals,  and place  a bell set  or  resistance  measuring  in­

strument  across  the  relay  terminals.  Depress  and  release  the reset 

arm to  insure  the relay  is  reset.  In this  condition  there  should  be 

continuity  between  the  terminals.  Depress  the  white  manual  check 

operator to trip the relay.  !n the tripped condition  the circuit between 

GEH-4839 INSTALLATION INSTRUCTIONS

300-Line CR305/CR306/CR309 Magnetic

 

Contactors,

Starters, & Reversers

For

 NEMA Size 5

Supersedes GEH-4839 and GEH-4869