MANUAL 

CEM11-FBP.xxx

Earth leakage monitor

Summary of Contents for CEM11-FBP Series

Page 1: ... MANUAL CEM11 FBP xxx Earth leakage monitor ...

Page 2: ... important information and conditions Sign to indicate a potentially dangerous situation that can cause human injuries Terms and abbreviations TOL Thermal Overload Relay EOL Electronic Overload Relay UMC Universal Motor Controller High grade motor protection and control device from ABB STOTZ KONTAKT GmbH CEM Common Accessory Earth Leakage Monitor PTC Positive Temperature Coefficient thermistor sen...

Page 3: ...ARTH LEAK AGE MONITOR MANUAL Table of contents Contents 2 Important notice 4 Overview 5 Product description 7 Connection to UMC100 3 PLC 8 Mounting instructions 9 Technical data 10 Dimensional drawings 12 Ordering details ...

Page 4: ...e motor to prevent further damage or to alert the maintenance personnel to perform maintenance Instead of earth fault current monitor the term residual current monitor is often used as well Product features With only four products a wide residual current range can be covered Type Pass through hole size Current range CEM11 FBP 20 20 mm 80 mA 1700 mA CEM11 FBP 35 35 mm 100 mA 3400 mA CEM11 FBP 60 60...

Page 5: ...switch set to Earth fault current threshold mA Comment 0 80 Tolerance 30 1 300 Tolerance 10 2 550 Tolerance 10 3 750 Tolerance 10 4 1000 Tolerance 10 5 1300 Tolerance 10 6 1500 Tolerance 10 7 1700 Tolerance 10 8 for functional test 9 for functional test Product description Setting the earth fault current The current threshold when the CEM11 signals an earth fault can be adjusted with a rotary swit...

Page 6: ... 4 8000 Tolerance 10 5 9600 Tolerance 10 6 12000 Tolerance 10 7 13600 Tolerance 10 8 for functional test 9 for functional test CEM11 FBP 60 Rotary switch set to Earth fault current threshold mA Comment 0 120 Tolerance 30 1 1000 Tolerance 10 2 2000 Tolerance 10 3 2800 Tolerance 10 4 4000 Tolerance 10 5 4800 Tolerance 10 6 6000 Tolerance 10 7 6800 Tolerance 10 8 for functional test 9 for functional ...

Page 7: ...motor startup time It is recommended to select after startup time to avoid a tripping during the motor start phase Additionally a filter time can be configured for this input to ignore short disturbances 01 CEM11 Connection to a UMC Terminals 1 24 V DC supply 2 Signal output Connector Supply e g 230 V AC Through hole diameter 20 35 60 120 mm Adjustment of the current threshold Type 1 80 to 1700 mA...

Page 8: ...ed using the provided accessories See the figures below how to snap on the parts With the CEM11 FBP120 only the assembly with screws is possible CEM11 FBP xxx front view CEM11 FBP xxx CEM11 FBP xxx bottom view metal adapters 2 or 4 pcs view from the rear Mounting instructions 02 CEM11 FBP xxx DIN rail mounted using the black plastic adapter several possibilities available 04 Wall mounted CEM11 FBP...

Page 9: ...ents marked with1 Output signal Earth fault current lower than threshold value Signal output switches to 24 V DC closed contact Max voltage drop 4 1 V DC Max load 30 mA Earth fault current higher than threshold value Signal output opens open contact Max output current 0 5 mA Max output low voltage 1 9 V DC Connecting capacity Solid or stranded 0 75 1 5 mm2 18 16 AWG Stripping length 5 6 mm 0 2 0 2...

Page 10: ...CEM11 FBP X X X EARTH LEAK AGE MONITOR MANUAL Dimensions Type X A B C D E F G H K CEM11 FBP 20 20 76 40 30 56 29 20 35 29 50 48 63 6 50 CEM11 FBP 35 35 99 50 30 79 48 50 12 85 41 50 48 63 6 50 CEM11 FBP 60 60 135 37 116 66 17 60 54 50 69 50 6 50 All dimensions in mm 05 Dimensions CEM11 FBP xxx Dimensional drawings ...

Page 11: ...G H 11 CEM11 FBP X X X EARTH LEAK AGE MONITOR MANUAL Dimensions Type X A B C D E F G H K CEM11 FBP 120 120 210 37 190 103 65 25 97 50 51 50 61 6 50 All dimensions in mm 06 Dimensions CEM11 FBP 120 A R 9 3 5 0 X E F C D ...

Page 12: ...rth Leakage Monitor pass through hole size 20 mm 1SAJ929200R0035 CEM11 FBP 35 Earth Leakage Monitor pass through hole size 35 mm 1SAJ929200R0060 CEM11 FBP 60 Earth Leakage Monitor pass through hole size 60 mm 1SAJ929200R0120 CEM11 FBP 120 Earth Leakage Monitor pass through hole size 120 mm Ordering details ...

Page 13: ...nges or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of infor mation in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third part...