background image

Mylos KNX

Switch Actuator with rocker switches

2CSYK1102C/S

2CSYK1103C/S

2CSYK1106C/S

Product manual

Summary of Contents for 2CSYK1102C/S

Page 1: ...Mylos KNX Switch Actuator with rocker switches 2CSYK1102C S 2CSYK1103C S 2CSYK1106C S Product manual ...

Page 2: ... delay 18 2 5 Scenes 20 2 6 Logic function 21 2 7 Rocker switch 1 2 23 2 7 1 Switching Rocker switch 23 2 7 2 Rocker switch 2 switching objects 24 2 7 3 Dimmer Rocker switch 25 2 8 Shutter rocker switch 26 2 8 1 Rocker switch Standard 26 2 8 2 Rocker switch Movement 27 2 9 Scene rocker switch 28 2 9 1 Scene 29 2 10 8 bit scene rocker switch 30 3 Operation of communication objects 32 3 1 Rocker swi...

Page 3: ...itch with programmable indicator light that can be configured according to the following functions simple switching or switching with two communication objects Dimmer functionality Shutter functionality 1 bit and 8 bit scene functionality manual operation that makes it possible to control the relays directly 1 1 1 Technical data Power supply Operating voltage 21 30 VDC over the bus Absorbed power ...

Page 4: ...g Automation Technical features L N NA 3 2 1 NC Device type Application program Maximum number of communication objects Maximum number of group addresses Maximum number of associations 2CSYK1102x Switching 1c 16A 1 0 1 interr 18 255 255 1 1 2 Connection diagram ...

Page 5: ...rammable indicator light that can be configured separately according to the following functions simple switching or switching with two communication objects Dimmer functionality Shutter functionality 1 bit and 8 bit scene functionality manual operation that makes it possible to control the relays directly 1 2 1 Technical data Power supply Operating voltage 21 30 VDC over the bus Absorbed power EIB...

Page 6: ... Automation Technical features L N NA 3 2 1 NC Device type Application program Maximum number of communication objects Maximum number of group addresses Maximum number of associations 2CSYK1103x Switching 1c 16A 1 0 2 switches 28 255 255 1 2 2 Connection diagram ...

Page 7: ...igured separately according to the following functions simple switching or switching with two communication objects Dimmer functionality Shutter functionality 1 bit and 8 bit scene functionality manual operation that makes it possible to control the relays directly 1 3 1 Technical data Power supply Operating voltage 21 30 VDC over the bus Absorbed power EIB KNX 12 mA Nominal output values Number o...

Page 8: ... Automation Technical features L1 L2 N NA 2 1 NA Device type Application program Maximum number of communication objects Maximum number of group addresses Maximum number of associations 2CSYK1106x Switching 2c 8A 1 0 2 switches 36 255 255 1 3 2 Connection diagram ...

Page 9: ... The device features a Programming button for assignment of the physical device address The red Programming LED lights up after the button has been pushed It switches off as soon as the ETS has assigned the physical address or the Programming button is pressed again Cleaning If devices become dirty they can be cleaned using a dry cloth or a cloth dampened with a soapy solution Corrosive agents or ...

Page 10: ...egrams It is possible to define the maximum number of unchanged telegrams during a time interval This parameter is important upon bus voltage restoration since many devices can send their status at the same time Maximum number of telegrams every 10 seconds if you wish to limit the telegram number it is set on Yes Maximum number of telegrams that can be sent by the device within 10 seconds Sending ...

Page 11: ...ct value The Switching object can be written with 0 or 1 when bus voltage is restored The contact position is determined again and the device parametrisation function is set Courtesy light activation Selecting Yes courtesy lights are activated LED operating mode It is possible to adjust the status of LEDs to that of the relay Show relay status to the LED communication object value Show communicati...

Page 12: ...it object it is possible to enable 0 or lock 1 the delay time upon switching on or off and stairlight functions over the bus As long as the time function is locked the output can be activated or deactivated only without delay by means of the Switching object If a time function is enabled and subsequently disabled using time function lock the output position remains unchanged A switching command th...

Page 13: ...via 1 bit object and OFF via 1 bit object refer to the 1 bit Forced operation safety object and determine the output switching status during forced operation A Forced operation 2 bit object is enabled with the option switching status via 2 bit object The telegram value that is sent via the 2 bit object determines how it follows switch position Value Bit 1 Bit 0 Access Description 0 0 0 Free If the...

Page 14: ...hing position is defined by the Contact switching status in forced operation programming With the selection inactive the forced operation is disabled and the output works as if it were programmed with the Behaviour upon safety end parameter Options for 2 bit 0 inactive 2 OFF 3 ON Selecting 2 OFF causes the forced operation object to be written with the 2 value and the output to be deactivated Sele...

Page 15: ... time has been set If pre warning time and stairlight time are different from 0 the stairlight time is extended with the pre warning time Note Active means that a normally open contact is closed or a normally closed contact is opened Note The stairlight function can be recalled from the Switching object Logic gate x or from a bright scene call Note The stairlight function can be disabled by a tele...

Page 16: ...by the increasing action Options no max up to 1x stairlight time max up to 2x stairlight time max up to 3x stairlight time max up to 4x stairlight time max up to 5x stairlight time With the no setting a switching telegram ON is simply ignored The stairlight time passes without modifications until it is over If a simple boot function is required max until 1x stairlight time must be set In this case...

Page 17: ...elegram object is set at 1 at the beginning of the pre warning time and remains unchanged until the pre warning time has elapsed The object can be used for example to switch an indicator light on Switching the output briefly OFF and ON again Both possibilities can be used individually or can be combined The duration time between OFF and ON is approximately 1 second This time is extended when more ...

Page 18: ...ing parameter Options 0 65 535 minutes Delayed ON Sec 0 59 parameter Here you set the time in seconds by which the switching on command is delayed The time can be entered in minutes and in seconds see the previous parameter Options 0 59 seconds Delayed OFF Min 0 65 535 parameter Here you set the time in minutes by which the switching off is delayed after a switching off command The time can be ent...

Page 19: ...ng Automation Commissioning Delayed OFF Sec 0 59 parameter Here you set the time in seconds by which the switching off is delayed after a switching off command The time can be entered in minutes and in seconds see the previous parameter Options 0 59 seconds ...

Page 20: ...ter The output can be associated with 63 different bright scenes using a group address The output can be associated with 5 bright scenes as a slave output Options no scene Scene 1 Scene 63 Standard value parameter Here you set the status that the output assumes when the scene is recalled Options ON OFF When a scene is stored the user has the possibility to modify the value that has been parametris...

Page 21: ... connected to the object Logic gate 2 See section 4 2 3 for explanations of the logic function Please examine the chart of operation of section 4 2 1 Logic gate x object parameter x 1 2 The object Logic gate 1 or Logic gate 2 is enabled with this parameter Options inactive active Logic gate x object function parameter x 1 2 Here the logic function of the Logic gate x object is defined together wit...

Page 22: ...result can be inverted using the Yes setting The no setting does not invert the result Options no yes Logic gate x x 1 2 object value upon Bus voltage restoration This parameter is visible only if a logic function has been selected This parameter determines the value that is assigned to the Logic gate x object after bus voltage restoration The same object values 0 and 1 are available Options 0 1 ...

Page 23: ...ifferent from no Cyclic sending multiplier if Cyclic Sending is different from no These two parameters allow you to determine the time period for message cyclic repetition over the bus Time interval is calculated as follows Period for message repetition Base Multiplier Courtesy light activation This parameter allows you to switch on the courtesy lights LED operating mode The LEDs can remain always...

Page 24: ...age cyclic repetition over the bus Time interval is calculated as follows Period for message repetition Base Multiplier Lower rocker switch operation It defines the operating mode if the lower rocker switch is pressed Lower push button cyclic sending This parameter allows you to determine in which cases the cyclic sending should begin if different from no Base for cyclic repetition lower push butt...

Page 25: ...ssure on the rocker switch Rocker switch reaction to long pressure Upper Lower Rocker switch It determines device reaction after a long pressure on the upper and lower rocker switch Long pressure duration It allows you to determine the time that is sufficient to consider a pressure as a long pressure Courtesy light activation This parameter allows you to switch on the courtesy lights LED operating...

Page 26: ...er switch Rocker switch reaction to long pressure Upper Lower Rocker switch It determines device reaction after a long pressure on the upper and lower rocker switch Long pressure duration s It allows you to determine the time that is sufficient to consider a pressure as a long pressure Courtesy light activation This parameter allows you to switch on the courtesy lights LED operating mode The LEDs ...

Page 27: ...eaction to pressure Upper Lower Rocker switch It determines device reaction after a pressure on the upper and lower rocker switch Courtesy light activation This parameter allows you to switch on the courtesy lights LED operating mode The LEDs can remain always on or always off they can be controlled by communication objects Show communication object value follow the rocker switch direct value Show...

Page 28: ... ends as soon as the push button is released If With object value 1 storage is activated as soon as the Store scene communication object receives value 1 If In case of long pressure if object value 1 storage is activated as soon as a long pressure is detected and the value of Store scene communication object is 1 Storage ends as soon as the push button is released Long pressure Base Long pressure ...

Page 29: ...9 MYLOS Building Automation Commissioning 2 9 1 Scene Actuator unit A B C D E check via It is possible to choose only one type of 1 bit datum Actuator unit A B C D E value It associates the corresponding actuator unit with a 1 bit value ON OFF ...

Page 30: ...ed with the short pressure of the lower rocker switch or which scene the new value should be associated with after a storage request Store scene This parameter determines the way in which the current scene storage begins and which function the Store scene communication object has If In case of long pressure the scene is stored as soon as a long pressure command is detected and storage ends as soon...

Page 31: ... Long pressure Multiplier 0 255 if In case of long pressure or if in case of long pressure if object value 1 These two parameters allow you to determine the time that is sufficient to consider a pressure as a long pressure Time interval is calculated as follows Period for long pressure Base Multiplier ...

Page 32: ...fter bus voltage restoration the object value can be determined via the Disable time function object value after bus voltage restoration object in the parameter window X Function See paragraph 4 2 2 for an application example Telegram value 1 disables the time function Telegram value 0 enables the time function If the time function is blocked only a switching without delay is possible Contact posi...

Page 33: ...has to be recalled or the current switching status must be assigned to it The communication object is visible only if the output X in the Function parameter window is assigned to at least a 8 bit scene Telegram size 1 byte MXSSSSSS MSB LSB M 0 the scene is recalled 1 the scene is stored if permitted X not used S Scene number 1 64 00000000 00111111 Value of the 1 byte EIB KNX telegram Meaning decim...

Page 34: ... C W 14 Logic gate 1 Output B 1 bit EIS 1 DPT 1 002 C W The object is visible if the logic function has been enabled in the parameter window X Function The output X can be assigned to the first of two logic objects The logic operation should be defined in the parameter window X Logic The communication object is first of all connected to the object Logic gate 1 The result is connected to the object...

Page 35: ...nput drive With Switching the previous value for example 1 is directly switched to value 0 It is important to ensure that the communication object can be written from the outside Therefore cyclic sending is interrupted or is not possible 34 Disabling LED Rocker switch 1 1 bit DPT_Enable C W 34 Disabling LED Rocker switch 2 1 bit DPT_Enable C W The Disabling Led communication object makes it possib...

Page 36: ...witching input drive With Switching the previous value for example 1 is directly switched to value 0 It is important to ensure that the communication object can be written from the outside Therefore cyclic sending is interrupted or is not possible 34 Disabling LED Rocker switch 1 1 bit DPT_Enable C W 35 Disabling LED Rocker switch 2 1 bit DPT_Enable C W The Disabling Led communication object makes...

Page 37: ...rom the parameters or to disable it 0 forcing it into a continuous switching off status 3 1 4 Shutter rocker switch No Function Object name Type of datum Flags 16 Disabling Rocker switch 1 1 bit DPT_Enable C W 23 Disabling Rocker switch 2 1 bit DPT_Enable C W T U The channel circuitry can be blocked or enabled using the communication object A blocked channel behaves as if there was no input signal...

Page 38: ... Rocker switch 1 1 bit DPT_Switch C W T U 24 25 26 27 28 Upper rocker 2 push button Scene A B C D E Rocker switch 2 1 bit DPT_Switch C W T U This communication object sends the following values over the bus to fulfil the scene setting 1 Byte value ON OFF EIS 1 DPT 1 001 switching command 22 Scene memory Rocker switch 1 1 bit DPT_Enable C W T U 29 Scene memory Rocker switch 2 1 bit DPT_Enable C W T...

Page 39: ...This communication object sends the following values over the bus to fulfil the scene setting 1 Byte value ON OFF EIS 1 DPT 1 001 switching command 22 Store scene Rocker switch 1 1 bit DPT_Enable C W T U 29 Store scene Rocker switch 2 1 bit DPT_Enable C W T U This communication object appears only with the option object value 1 This option can be set in the parameter Store scene This communication...

Page 40: ...tch C W Through these communication objects it is possible to control the upper LED status directly over the bus Send a telegram containing the value 1 to switch them on or value 0 to switch them off 31 Lower LED Rocker switch 1 1 bit DPT_Switch C W 33 Lower LED Rocker switch 2 1 bit DPT_Switch C W Through these communication objects it is possible to control the lower LED status directly over the...

Page 41: ...A 59 3B 0 0 1 1 1 0 1 1 60 A 60 3C 0 0 1 1 1 1 0 0 61 A 61 3D 0 0 1 1 1 1 0 1 62 A 62 3E 0 0 1 1 1 1 1 0 63 A 128 80 1 0 0 0 0 0 0 0 1 S 129 81 1 0 0 0 0 0 0 1 2 S 130 82 1 0 0 0 0 0 1 0 3 S 131 83 1 0 0 0 0 0 1 1 4 S 132 84 1 0 0 0 0 1 0 0 5 S 133 85 1 0 0 0 0 1 0 1 6 S 134 86 1 0 0 0 0 1 1 0 7 S 135 87 1 0 0 0 0 1 1 1 8 S 136 88 1 0 0 0 1 0 0 0 9 S 137 89 1 0 0 0 1 0 0 1 10 S 138 8A 1 0 0 0 1 0 ...

Page 42: ...uone MI Italy Tel 39 02 9034 1 Fax 39 02 9034 7609 www abb it mylos www abb com The data and illustrations are not binding We reserve the right to modify the contents of this document on the basis of technical development of the products without prior notice Copyright 2012 ABB All rights reserved from Monday to Saturday from 9 00 to 19 00 ...

Reviews: