ZURN Z1175 Manual Download Page 6

SOLIDS INTERCEPTORS

ZURN PLUMBING PRODUCTS GROUP

SPECIFICATION DRAINAGE OPERATION, 1801 PITTSBURGH AVENUE, ERIE, PA 16502 PHONE 814/455-0921 FAX: 814/454-7929 WEBSITE: www.zurn.com

Page 54

Z1184 SOLIDS INTERCEPTOR – OPERATION and MAINTENANCE INSTRUCTIONS

SIZING

There are no sizing requirements for this interceptor except to specify
the inlet and outlet size. All units are made with a standard 2" [51 mm]
pipe size inlet and outlet, reduced to 1-1/2" [38 mm] with a bushing
when specified and are capable of handling drainage volumes standard
to their respective pipe size.

DESIGN

The Zurn Z1184 Solids Interceptor is designed to recover all types of
solids from precious metal particles to plaster, clay, or similar materials.
This is accomplished through the principal of gravity separation.
Particles of various sizes and weights are trapped in the bucket.

OPERATION

The wastewater flows from the inlet piping into the removable bucket,
passing through the screen, into the main body chamber, then exits
the interceptor to the sanitary drain system.

MAINTENANCE

Cleaning should be done on a regular basis, either before or after the
bucket becomes clogged. First, remove the handle in the center of
the cover and drain out the water in the interceptor; replace handle.
Then unlatch and remove the cover/bucket assembly, twist and lift
the bucket to remove from cover, take out the screen and clean out
all debris. Replace the screen in the bucket. Next place the bucket
back on the cover and twist to reattach. Make certain the cover
gasket is intact and clean. Apply a light coating of oil on the cover
gasket, which helps prevent the cover gasket from adhering to the
cover and aids in maintaining a complete seal. The cover/bucket
assembly should then be placed back in the unit,

making sure the

screen in the bucket is on the outlet side as shown

, and relatch

to secure cover. Efficiency of operation is directly related to the level
of maintenance.

Note:

Damage from high-temperature water will not occur to the acid

resistant composite material of this unit when installed downstream
from a dishwasher. There is a chance, however, that the thin-walled
PVC screen in the bucket may deform. It is recommended that a
stainless steel perforated screen be used in applications that involve
high-temperature water.

Z1183-DF SOLIDS INTERCEPTOR with DISPOSABLE FILTER BAGS – OPERATION and MAINTENANCE INSTRUCTIONS

SIZING

The sizing of this interceptor relates to the size of the Z1170 grease
interceptor it is being used with. All units are made with a standard
no-hub pipe size inlet and outlet, and are capable of handling drainage
volumes standard to their respective pipe size.

DESIGN

The Zurn Z1183-DF Solids Interceptor is designed to recover food
waste from sinks, garbage grinders, and dishwashers. This is
accomplished through filtration. The food wastes are retained in the
disposable filter bags while allowing wastewater to pass through to
the outlet drainage line.

OPERATION

The wastewater flows from the inlet piping into the main body chamber.
It is then redirected through the solids filter bags by the retainer plate.
Solid material is captured in the filter bag allowing the wastewater to
pass through. Any solids that pass through the filter bag will settle into
the removable sediment basket. The filtered wastewater then exits the
interceptor to the sanitary drain system.

MAINTENANCE

Cleaning should be done on a regular basis, before the sediment
basket or filter bags become clogged. Remove the cover, lift out the
filter bags from the retainer plate and properly dispose of them.
Remove the retainer plate and sediment basket and clean out all

debris, hosing off the interior as necessary. Replace the basket and
retainer plate into the interceptor. Insert clean filter bags into the
retainer plate. Make certain cover gasket is intact and clean. Apply a
light coating of oil on the cover gasket, which helps prevent the cover
gasket from adhering to the body and aids in maintaining a complete
seal. The cover should then be placed back on the unit and secured.
Efficiency of operation is directly related to the level of maintenance.

Summary of Contents for Z1175

Page 1: ... 15 0 15 10 20 x 18 x 8 2 18 7 20 10 30 x 20 x 8 1 15 5 20 10 24 x 20 x 12 1 18 7 20 10 22 x 20 x 8 2 23 0 25 15 22 x 20 x 12 2 34 0 35 20 24 x 24 x 12 2 44 9 50 25 Product selection should be made with a specific application and the type of construction in mind The varied types and sizes of Zurn interceptors along with their options offer a selection for all applications APPLICATION INDEX APPLICA...

Page 2: ... 16502 PHONE 814 455 0921 FAX 814 454 7929 WEBSITE www zurn com Page 50 PICTORIAL INDEX SOLIDS INTERCEPTORS Z1182 Side Access Solids Interceptor Z1183 Solids Interceptor Z1181 Solids Interceptor Z1180 Solids Interceptor Z1184 Bottom Access Solids Interceptor Z1183 DF Solids Interceptor with Disposable Filter Bags ...

Page 3: ...eptor options and variations are specified as a PREFIX and or SUFFIX letter or number added to the series designation Below are the available options PREFIXES Z Standard Assembly See Engineering Specification ZA Acid Resistant Coated Fabricated Steel or Dura Coated Cast Iron ZAB All Satin Finish ZS All Type 304 Fabricated Stainless Steel SUFFIXES AR Acid Resistant Coated Fabricated Steel Finish CP...

Page 4: ...iciency of operation is directly related to the level of maintenance Z1181 SOLIDS INTERCEPTOR OPERATION and MAINTENANCE INSTRUCTIONS SIZING There are no sizing requirements for this interceptor except to specify the inlet and outlet size All units are made with a standard 2 51 mm pipe size inlet and outlet reduced to 1 1 2 38 mm with a bushing when specified and are capable of handling drainage vo...

Page 5: ...lean Apply a light coating of oil on the gasket Z1183 SOLIDS INTERCEPTOR OPERATION and MAINTENANCE INSTRUCTIONS SIZING The sizing of this interceptor relates to the size of the Z1170 grease interceptor it is being used with All units are made with a standard no hub pipe size inlet and outlet and are capable of handling drainage volumes standard to their respective pipe size DESIGN The Zurn Z1183 S...

Page 6: ...erature water will not occur to the acid resistant composite material of this unit when installed downstream from a dishwasher There is a chance however that the thin walled PVC screen in the bucket may deform It is recommended that a stainless steel perforated screen be used in applications that involve high temperature water Z1183 DF SOLIDS INTERCEPTOR with DISPOSABLE FILTER BAGS OPERATION and M...

Page 7: ...ic Hydrocarbons E E Chlorinated Hydrocarbons F F Ketones F F Ethers F F Esters F F Gasoline E E Carbon Tetrachloride E E Organics Aniline G P Benzenc E E Formaldehyde 37 E G Phenol 5 G F Mineral Oils E E Vegetable Oils E E Chlorobenzene G P Z1180 and Z1184 CHEMICAL RESISTANCE CHART For Composite Material in Light Acid Concentration Environment Only Key E Excellent Corrosion Resistance G Good F Fai...

Page 8: ...te a a Potassium sulfate a a Silver nitrate a a Salts Continued Silver cyanide a a Sodium bicarbonate a a Sodium borate a a Sodium bromide a a Sodium chloride 2 aerated a a Sodium citrate a a Sodium fluoride b Sodium hydroxide a a Sodium nitrate a a Sodium peroxide 212 F a a Stannic chloride c c Stannous chloride b Sulfur molten 500 F a a Sulfur chloride b Titanium tetrachloride a a Zinc chloride ...

Page 9: ...t is ideally suited to traffic bearing grates and strainers in finished floor areas It affords the combined advantage of greater strength better appearance and longer service life at the same price as chrome plated brass Superior ductility and shock resistance are the result of a copper nickel alloy Copper Alloy 997 having a wearing surface similar in appearance to satin chrome plate however becau...

Reviews: