Model 350AST(R) & 350ASTDA(R)

Double Check Valve Assembly (2-1/2", 3", 4" & 6")

Double Check Detector Assembly (2-1/2", 3", 4" & 6")

Installation

 

 

Testing

 

 

Maintenance Instructions

®

INSTALLATION INSTRUCTIONS

CAUTION:

 Installation of Backflow Preventers must be performed by qualified, licensed 

personnel. The installer should be sure the proper device has been selected for the par

-

ticular installation. Faulty installation could result in an improperly functioning device.

ZURN WILKINS Model 350AST Series Assemblies are for use on potable water lines 

where a health hazard does not exist in the event of a backflow situation.

Damage to the device could result wherever water hammer and/or water thermal expan

-

sion could create excessive line pressure. Where this could occur, shock arrestors, check 

valves and/or pressure relief valves should be installed downstream of the device.

If installation is in a pit or vault, the Backflow Preventer must never be submerged in 

water because this could cause a cross-connection. Make sure that the pit or vault always 

remains dry by providing ample drainage.

1. Before installing a Model 350AST Series Backflow Preventer, flush the line thor

-

oughly to remove all debris, chips and other foreign matter. If required, a strain

-

er  should be placed upstream of the Backflow Preventer. CAUTION: Do not use a

strainer in seldom used emergency waterlines such as fire lines.

2. Provide adequate space around the installed unit so that the test cocks will be

accessible for testing and servicing.

3. Install valve at least 12 inches above surrounding flood level.

4. Always consult local codes for installation methods, approvals and guidance.

5. Resilient seated shutoff valves are required to be installed on both the inlet and

outlet of the device to make field testing possible.

INDOOR INSTALLATION

Indoor installation is preferred in areas that 

are subject to freezing conditions. All the 

basic installation instructions apply to such 

installations.

OUTDOOR INSTALLATION

The Model 350AST Series Backflow Pre

-

venter may be installed outdoors only if the 

device is protected against freezing condi

-

tions. Exposure to freezing c

o

nditions will 

result in improper function or damage to the 

device. The  installation  location  must  be 

kept above 32°F. All the basic installation 

instructions apply.

PLACING THE DEVICE IN SERVICE

1. Start with both shut-off valves closed.

Slowly open the inlet shut-off valve

until the backflow preventer is com

-

pletely pressurized.

2. When the unit has been pressurized,

vent any trapped air by slightly open

-

ing each of the four test cocks.

3. Slowly open the downstream shut-off

valve. The Model 350AST Series  As

-

sembly is now in service.

4. After the Model 350AST Series has

been properly installed, test the device

(see “TEST PROCEDURES”). If the

device fails the test, remove the first

and second check valves and thor

-

oughly flush the device. Clean rubber

and seats of all debris and place unit

back in service.

OUTDOOR INSTALLATION

Model 350AST

VERTICAL INSTALLATION

Vertical installation is acceptable in applica

-

tions where inlet and outlet piping are flowing 

vertically upwards. All the basic installation 

instructions apply to such installations. Con

-

sult factory for approval status.

INDOOR INSTALLATION

Model 350ASTBG 

PROTECTIVE

ENCLOSURE

DIRECTION OF FLOW

12"  MIN.

 30"  MAX.

DIRECTION OF FLOW

DIRECTION OF FLOW

12"  MIN.

 30"  MAX.

INDOOR INSTALLATION

Model 350ASTBG

LEAD-FREE*

*This product contains a weighted average lead content less than 0.25% for wetted surfaces.

(Patent No. 8,997,772) 

!

WARNING:

 Cancer and Reproductive Harm - www.P65Warnings.ca.gov

!

ADVERTENCIA:

 Cáncer y daño reproductivo - www.P65Warnings.ca.gov

!

AVERTISSEMENT:

 Cancer et néfastes sur la reproduction - www.P65Warnings.ca.gov

Summary of Contents for 350AST Series

Page 1: ... make field testing possible INDOOR INSTALLATION Indoor installation is preferred in areas that are subject to freezing conditions All the basic installation instructions apply to such installations OUTDOOR INSTALLATION The Model 350AST Series Backflow Pre venter may be installed outdoors only if the device is protected against freezing condi tions Exposure to freezing conditions will result in im...

Page 2: ...the valve you may see both needles drop simultaneously during test due to disc compression The high side needle should eventually hold 2 psi below low side needle if check in not fouled TEST NO 2 TIGHTNESS OF 2 CHECK VALVE REQUIREMENT The static pressure drop across check valve 2 shall be at least 1 0 psid If test cock 4 is not at the highest point of the check valve body then a vertical tube must...

Page 3: ...ify flow direction arrow 2 Gate valves not fully open 2 Turn handles counterclockwise 3 Low supply pressure 3 Attach pressure gauge to test cock 1 and verify pressure ZURN WILKINS 1747 Commerce Way Paso Robles CA 93446 Phone 855 663 9876 Fax 805 238 5766 www zurn com 5 Remove the 2 check by locating one of the two spring loaded plate retainers around the face of the check Pinch the sides of the sp...

Page 4: ...3446 Phone 855 663 9876 Fax 805 238 5766 4 Proper performance is dependent upon licensed qualified personnel performing regular periodic testing according to ZURN WILKINS specifications and prevailing governmental industry standards and codes and upon following these installation instructions Failure to do so releases ZURN WILKINS of any liability that it might otherwise have with respect to that ...

Reviews: