Chapter 6 Alarm List
S.N.
Alarm Name
Alarm Level and Output Relay
Alarm Description
27
Bat Over-Temp
Default level: Minor
Default relay: 0
The battery working temperature is higher
than
Batt.OverTemp.
28
TmpL Shut-down
Default level: Major
Default relay: A5
The environment temperature is too low
(default alarm threshold: -25°C), so all the
loads are disconnected.
29
1st Shut-down
Default level: Major
Default relay: A5
When the battery voltage is lower than
LVD1
Volt.
, the less-important loads are shut down.
30
2nd Shut-down
Default level: Major
Default relay: A5
When the battery voltage is lower than
LVD2
Volt.
, all the loads are shut down.
31
DC SPD Broken
Default level: Major
Default relay: A3
The DC surge arrester is faulty.
32
DC Breaker Alm
Default level: Mask
Default relay: 0
Some breaker is faulty.
33
Batt.Test Fail
Default level: Minor
Default relay: A4
The battery test is terminated despite that its
duration does not reach
Test Max.Hours
.
34
Batt. On Load
Default level: Minor
Default relay: A4
The battery is discharging.
35
Env Under-Temp
Default level: Minor
Default relay: 0
The environment temperature is lower than
Env.UnderTemp
.
36
Env Over-Temp
Default level: Minor
Default relay: 0
The environment temperature is higher than
Env.OverTemp
.
37
Env Under-Hum
Default level: Mask
Default relay: 0
Not detected
38
Env Over-Hum
Default level: Mask
Default relay: 0
Not detected
39
Smoke Alarm
Default level: Major
Default relay: 0
The sensor detects the smoke.
40
Flood Alar
Default level: Major
Default relay: 0
The sensor detects the entrance of water.
41
Door Magnet Alm
Default level: Minor
Default relay: 0
The door with the door magnet switch is
opened. Some object intrudes.
42
E.T.Invalid
Default level: Mask
Default relay: 0
The environment temperature detection is
invalid.
43
E.H.Invalid
Default level: Mask
Default relay: 0
The environment humidity detection is invalid.
6-3
SJ-20121116145308-001|2012-12-05 (R1.0)