Environment Indices
The environment indices set requirements on the physical parameters,
power supply, grounding, temperature, humidity and cleanness, which are
given in Table 4.
T
A B L E
4
E
N V I R O N M E N T
I
N D I C E S
Environment Indices
Requirements
Dimension (mm)
Single cabinet (mm): W700
×
D800
×
H800
PWS cabinet (optional): W700
×
D600
×
H400
Weight (kg)
4-carrier 1–sector: 155
4-carrier 3-sector: 211
4-carrier 6-sector or 8-carrier 3-sector: 422
Physical
Index
Load-bearing of
the floor (kg/m
2
)
>377
Primary power
supply input
150 V~300 V for 200 V AC or 90 V ~138 V for 100
V AC
Secondary power
supply input
-
42.3 V ~
-
56.5 V if -48 V DC is used
Power
supply
Power
consumption
Varies with the configuration (refer to Table 5.1-2)
Grounding
Joint grounding resistance
≤
1
Ω
Temperature
Long-term: -
5°C~50°C
Short-term: -20°C~60°C
Humidity
Long-term:
15%~80%
Short-term:5%~95%
Cleanness
Dust granule diameter <5
μ
m, dust granule
density
≤
13
°
10
4
granules/m
3
(dust granules
should be non-conductive, non-magnetic and non-
corrosive)
Note:
Temperature and humidity values are measured 2m above floor and 0.4m in front
of equipment that has no fender at the front or back.
By “short-term” it means less than continuous 48 hours or less than cumulative 15
days in a year.