  INSTRUCTION MANUAL – 4 to 8 ZONE FIRE ALARM PANEL   

 

 

Approved Document No: GLT.MAN-119

 

 

 

PAGE 6

 

Issue : 1         Author: NRPJ      Date: 22/11/2006

 

 

Setting a Sounder Activation Delay 

 

On the Premier Elite there is the option to delay the sounder activation in the event 
of a fire. This might be useful in schools or clubs where the responsible person 
might want to verify the alarm, before having a “mass evacuation” of the building. A 
false alarm can be reset before the sounders operate. If it is a true alarm, the 
sounders can be started before the timer finishes by pressing the DELAY 
OVERRIDE BUTTON. 

 

To set a delay open the panel door using Alan Key provided and set switch 7 (

SW7

using a terminal screw driver to the delay required 

 
 
 

SW7 Setting 

External 
sounder delay in 
minutes 

0 No 

delay 

1 1 

minute 

2 2 

minutes 

3 3 

minutes 

4 4 

minutes 

5 5 

minutes 

6 6 

minutes 

7 7 

minutes 

8 8 

minutes 

9 9 

minutes 

When a delay is set, the panel will show GENERAL DISABLEMENT and DEL 
(sounder DELay) 

Summary of Contents for Premier Elite

Page 1: ...Instruction Manual 4 8 zone F A C P ...

Page 2: ...ay 7 Class Change Input 7 Display Controls 8 Display 9 Controls 10 Alarm Condition Resetting an alarm 11 What to do in the event of a fire 11 Resetting from an alarm condition 11 Fault display fault finding 12 Fault Finding 12 Supply fault 12 Zone Fault 13 Sounder Circuit Fault 13 Earth Fault 14 System Fault 14 Disablement 15 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED 15 Test Mode 16 TO PROGRAMME Z...

Page 3: ... 4 zone panel 6 zone panel or an 8 zone panel Each version has 2 sounder circuits an alarm relay and a fault relay The sounder circuits can have a programmable delay set There is an option to add a zonal output board which can be used to drive zonal relays or a hard wired repeater panel There is no configuration simply connect the detectors sounders and apply power The Premier Elite range also inc...

Page 4: ...lead The ve of the other battery is connected to the black battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied Although there are many sizes of suitable battery the sizes we usually recommend are 12V 2Ah for standard backup or 12V 7Ah for extended backup 72 hour or more and the enclosure has been designed to hold these two battery size...

Page 5: ...trictions The diode also known as a continuity diode passes power to the downline detectors and call points if a detector head is removed for any reason Zone Short Circuit Protection The Premier Elite 4 8 zone panel has a higher zone output current than the 1 2 zone panels This is to allow them to drive larger zones and zone powered beam detectors etc In order to protect the panel in the event of ...

Page 6: ...ss evacuation of the building A false alarm can be reset before the sounders operate If it is a true alarm the sounders can be started before the timer finishes by pressing the DELAY OVERRIDE BUTTON To set a delay open the panel door using Alan Key provided and set switch 7 SW7 using a terminal screw driver to the delay required SW7 Setting External sounder delay in minutes 0 No delay 1 1 minute 2...

Page 7: ...lly energised so that it gives a signal in the event of total power failure Mains Battery back up It is rated at 1Amp SELV The relay remains operated until the fault has been cleared Class Change Input The class change input on a Premier Elite 4 8 zone F A C P will remotely operate the sounder circuits The Class change terminals should be connected to a normally open contact that closes when the s...

Page 8: ...one External Sounder Delay Override After all detectors and manual call points have been returned to normal turn the key switch to the CONTROLS ENABLED position and press button 1 to stop the fire sounders Press button 2 to silence the internal fault buzzer and then press button 3 to RESET the system If the panel is showing a fault condition turn the key switch to the CONTROLS ENABLED position and...

Page 9: ...fault in the wiring of one or both of the sounder circuits GEN FLT SYSTEM FLT CONSTANTYELLOW CONSTANTYELLOW A processor fault has occurred To reset turn keyswitch on then back off If problem persists consult your dealer GEN FIRE ONLY CONSTANTRED A manual evacuation has occurred The sounders will be active GEN FIRE ZONE FIRE CONSTANTRED CONSTANTRED A fire has occurred in the zone indicated The soun...

Page 10: ...el s internal buzzer in a fault or alarm condition 3 RESET Used to return the panel to its normal condition after an ALARM condition Reset will not clear faults 4 LED TEST To check that all indicator LEDs are working Use as part of the daily weekly fire alarm inspection Engineer ENGINEER Used to access Disablement mode or Test Mode Delay Override DELAY OVERRIDE Used to start sounders immediately i...

Page 11: ... suitable fire extinguisher 5 If a larger fire is found leave the building immediately and contact the fire brigade 6 If no fire is found make a note of the detector that signalled fire and look for anything nearby that could be the cause of the activation eg cooking or use of a hot air gun etc 7 Record findings in the fire alarm log book Resetting from an alarm condition After the relevant action...

Page 12: ...sible person All faults in the Premier Elite are NON LATCHING IE they can not be reset with the reset button They will clear automatically when the fault has been fixed The exception is a SYSTEM FAULT which means that the processor may have crashed and may or may not have restarted correctly Fault Finding Supply fault A power supply fault is indicative of one or more of the following faults Loss o...

Page 13: ... the zone Check for shorts to the cable screen Check that none of the heads have become damaged remove one at a time As a panel check remove cable fit EOL at the panel If the fault clears the panel is working correctly Sounder Circuit Fault A Sounder Fault is indicative of one or more of the following faults Sounder Open Circuit fault Check that the correct end of line resistor 10K has been fitted...

Page 14: ...t The voltage between battery Ve and earth should be 14 16 volts If it is not the voltage should indicate what is shorting to earth System Fault A system fault is an abnormal microprocessor running condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault inte...

Page 15: ... The panel is now in SELECT DISABLEMENT MODE Press scroll button again Zone 1 DISABLEMENT LED will be lit Continue to press scroll until the desired Zone or sounder is lit Press the Engineer button The GENERAL DISABLEMENT LED will be lit constantly indicating that this zone or sounder is now disabled If more than one zone needs to be disabled then press scroll again until the required zone is sele...

Page 16: ... test the Alarm will be processed in the normal way The testing of the zone in test will temporarily be suspended until the Alarm s from the other zones are reset At this point zone retesting may resume To Programme Zone In Test NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press engineer switch until the General Zone test LED is o...

Page 17: ...on the fire alarm panel door This can either be used in two ways 1 As a stand alone board that has zonal 29 Volt outputs suitable for connecting relays etc 2 It can be used to drive a hard wired repeater panel The panel would need the following connections to the repeater V Supply Voltage 0V Supply ground GA General Alarm signal CF Common Fault Signal TN Buzzer Active Signal tone It will also need...

Page 18: ... the equation Battery Size Standby time in Amp Hours 1 25 x TALM x IALM TSBY x ISBY Where TALM Maximum time in hours required for the alarm hour is most common time IALM Total Alarm Current in amps for all alarm devices connected to the alarm circuits TSBY Standby time in hours for the system after mains failure normally 24 48 or 72 hr ISBY Quiescent current in amps of control panel in fault condi...

Page 19: ...DER ACTIVATION DELAY 0 9 MINUTES IN 1 MIN INCREMENTS ZONE END OF LINE DEVICE 1N4002 DIODE CATHODE STRIPE TO SOUNDER END OF LINE DEVICE 10 K RESISTOR CHARGER VOLTAGE 28 4V 25o C NO BATTERY CONNECTED ZONE SHORT CIRCUIT PROTECTION 100mA CHARGER SHORT CIRCUIT PROTECTION Batteries less than 21V TOTAL CHARGER OUTPUT 1 1 Amp Enclosure Specifications DESCRIPTION VALUE ENCLOSURE SIZE 355 x 275 x 100 mm TOP...

Page 20: ...4 to 8 ZONE FIRE ALARM PANEL Approved Document No GLT MAN 118 PAGE 20 Issue 1 Author NRPJ Date 15 11 2006 Log Book MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED ...

Page 21: ...d Document No GLT MAN 118 PAGE 21 Issue 1 Author NRPJ Date 15 11 2006 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDINGS CATEGORY OF FALSE ALARM FURTHER ACTION REQUIRED SIGNED ...

Page 22: ... 8 ZONE FIRE ALARM PANEL Approved Document No GLT MAN 118 PAGE 22 Issue 1 Author NRPJ Date 15 11 2006 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE COMPLETED INITIALS ...

Reviews: