21
Default Thermostat Set Point Programming
Global default set points can be established from the
GEN II
controller.
The following procedure will provide a 75°F (23°C) Cool and 70°F (21°C) Heat occupied set point
along with Unoccupied 58°F (14°C) Heat and 85°F (29°C) Cool set point for every thermostat in the
system. This handy feature minimizes visits to the thermostats. To establish these default set
points:
1.
EH
jumper (A) - place the jumper over both pins.
2. Press the
SET
and
DN
button (N) simultaneously to engage default set points.
3. Remove the EH jumper, and place on one pin to put controller back into normal operation.
4. To view the unoccupied set points place the Night / Day switch (L) to the NIGHT position.
Following a poll, the thermostat backlights will turn off; and the unoccupied set points will be
displayed.
Time Clock
The GCLK is a 24vac 7-Day programmable time clock offered by Zonex Systems, exclusively for
the GEN II control system. This digital time clock will enable the control system to operate with
“Global” Occupied and Unoccupied schedules in a 7-day format. The GCLK is powered from the
GEN II
controller power supply, and there is a backup battery to protect the time clock program for
up to 100 hours.
Installation
The GCLK must be installed on an interior wall next to the
GEN II
controller. Both the
GEN II
controller and GCLK time clock must be easily accessible to monitor status and to make program
and function changes.
1. Remove the clear dust cover lens and loosen two screws on opposite corners of the clock
module.
2. Remove the housing that surrounds the time clock and the wire terminal cover.
3. Remove the clock module by pulling straight out from the base. Install the backing plate to the
wall with 3 screws (provided).
4. The GCLK is powered from TR1 and TR2 on the
GEN II
controller to terminals 1 and 2 on the
time clock terminal base.
5. The Normally Open switch contacts on the time clock 3 and 5 are wired to the TC terminals on
the
GEN II
controller.
6. Press the clock module back into place in the base, making certain that it is seated correctly.
7. Install the wire terminal cover and the clock housing with the 2 screws.
8. Install the clear dust cover lens in place.
Programming