OPERATING INSTRUCTION

OPERATION

Using the Up and Down button, select your required set 

point:

  

UP

 - Increases set point.

DOWN

 - Decreases set point.

Confirm “AUTO” icon appears above the third button on the 

thermostat to maintain zone comfort based on thermostat set 

point, room temperature and duct temperature.

FUNCTION BUTTONS

AUTO

 - 

Configures controller for AUTO mode or OFF mode

           

    (Hold Auto/Off for 15 seconds to turn SAMOD Off/On)

DUCT

 - Pressing this button displays supply air temperature

MENU

 - Accesses system configuration functions

DUCT TEMPERATURE

To check the duct temperature press “DUCT” and the current 

temperature in the duct will be displayed.

LOCKING SAMOD CONTROLLER

The SAMOD controller can be locked hiding MENU functions 

and preventing set point from being changed greater than 2 

degrees above or below selected set point.  To lock SAMOD 

controller, press and hold DUCT button for 10 seconds.  To 

unlock, press DUCT button for 10 seconds; MENU will be 

visible and temperature set point can be changed.

CALIBRATION

Press MENU button and scroll to CALIBRATE using the 

Up/Down buttons, when highlighted, press SELECT. Use the 

Up/Down to set the desired room temperature, press EXIT to 

save.

SETUP AUXILIARY HEAT/REHEAT

Press MENU button and scroll by pressing the Up/Down 

buttons through menu options.  When SET AUX HEAT option 

is highlighted, press SELECT.  Two options are offered, 

BASEBOARD or REHEAT. 

 

If BASEBOARD is desired press SELECT button to select 

desired temperature dead band by scrolling through 2, 3 or 4 

degrees, when selection is highlighted, press EXIT. Once 

desired HEAT DEAD BAND is set, press EXIT.  Follow the 

same steps but highlight Reheat if desired.  

This will complete the setup for Auxiliary / Reheat.

TEMPERATURE FORMAT

Press MENU button and scroll to TEMPERATURE FORMAT 

using the Up/Down buttons, when highlighted, press 

SELECT. Use the Up/Down buttons to choose F° or C°, press 

SAVE when selection has be made.

DAMPER ADJUSTMENT

The ST series zone dampers are factory set for full open and 

close operation. Each damper is equipped with adjustable 

stops for field setting the maximum open and minimum close 

positions if desired.

The SAMOD is an Auto Changeover thermostat that modulates a zone damper based on supply air and room temperature.  

System logic dictates system mode of operation.  When duct temperature is 3 degrees or more below room displayed 

temperature on the SAMOD thermostat, the mode is set as Cool.  When duct temperature is 7 degrees or greater than room 

temperature as displayed on SAMOD thermostat, then mode is set for Heat.  If duct temperature is neither 3 degrees below 

nor 7 degrees above room temperature displayed on SAMOD thermostat, then mode is set for Vent for continuous air 

circulation.

UP

DOWN

SET POINT

AUTO / OFF

DUCT TEMP

MENU

ROOM TEMP