INSTALLATION

 

WHEN INSTALLING THIS PROD

UCT…

 

Read  these  instructions  carefully.  Failure  to  follow  the  instructions 
could damage the product or cause a hazardous condition. Ensure that 
the  installer  is  a  trained,  experienced  service  technician.      After 
completing  installation,  use  these  instructions  to  check  product 
operation.

 

LOCATION

 

The Zone Dampers are installed typically near the furnace/air handler 
plenum and in the air duct takeoff to the zone.  Always make sure the 
dampers  are  accessible  for  wiring,  checkout,  duct  cleaning  and 
replacement of damper or motor if ever needed.

 

DAMPER SIZE

 

To ensure proper operation, the ZD must be properly sized for the  air 
duct.  To  ensure  proper  fit,  damper sizes  are  built slightly  smaller. 

¼” 

less  than  the  listed  dimensions.  If  the  damper  is  forced  into  an 
undersized air duct, the excess pressure jams the damper blades and 
causes improper operation.

 

HUMIDIFICATION

 

Do  not  install  dampers  in  heating  systems  where  spray  or  atomizing 
type humidifiers are installed in the furnace plenum or air supply duct. 
Excessive  lime  or  mineral  deposits  accumulate  on  damper  blades 
and cause improper operation.

 

For humidification, use  evaporative type  humidifiers or  return air type 
humidifiers.

 

INSTALLATION CONSIDERATIONS

 

Install Zone Dampers (ZDS) or (ZDB) into a squared air duct. Frame 
misalignment may jam the damper blades.  Do not weld dampers to air 
ducts.

 

 

INSTALLING A ZONE DAMPER

 

Ensure the ZD is correctly sized to the air duct and select a ZD location 
near the furnace plenum.

 

1.  

Cut a  4-inch (102-millimeter) opening in one side (shorter dimension) 

of  the  air duct at the location selected. Ensure the  opening is cut fully to 
the top and bottom air duct seams.

 

2.  

Slide the ZDS into the cut opening of the air duct. Ensure the electric 

actuator is mounted toward the top of the air duct.

 

3.  Secure  the  ZDS  mounting plate  to  the  air  duct  with  the  sheet  metal 
zip screws provided.

 

 

CAUTION

 

Locate and install dampers in an easily accessible location for Service 
and Checkout.

 

Never force dampers into undersized air ducts. Excess pressure will jam 
damper blades.

 

Ensure high limit setting is 200

q

F (93

q

C) or lower. Higher settings can 

damage electric actuator.

WIRING

 

 

BEFORE WIRING 

– MAKE SURE ALL POWER IS DISCONNECTED 

TO PREVENT SHOCK AND EQUIPMENT DAMAGE.

 

ALL  WIRING  MUST  CONFORM  TO  NEC  STANDARDS  AND  ALL 
APPLICABLE LOCAL CODES.

 

The  ZD  damper  is  the  simplest  damper  in  the  industry  to  wire.   The 
ZD requires only two (2) wires for it 24  Volt AC,  power-closed, spring 
return open operation.

 

The  two  wires  from  the  motor  wire  to  a  normally  open  zone  control 
panel  to  terminals  M1  (Common)  and  M6  (Closed).    See  Wiring 
Diagram 1.

 

For  other  type  of  controls the  two  leads  go  direct to  a  24  Volt  power 
source  and  one  of  the  motor  leads  is  interrupted  by  a  switch.    See 
Wiring Diagram 2.

 

One  24VAC,  40VA  Transformer  can  power  up  to  five  (5)  damper 
motors.

 

To slave more than one motor together wire the motors in  parallel.   A 
total  of  five  (5)  motors  should  be  on  one  40VA  transformer.   When 
require  more  than  five  motors  and  isolation  relay  and  additional 
transformers may be required.

 

WIRING DIAGRAM 1

 

 

 

M6/CLOSE 

M4/OPEN 

M1/COMMON

 

 

When 

replacing 

older 

wire 

dampers,     wire     as    shown    and 
jumper  M2-M5  terminals  on  control 
panel.

 

 
 

WIRING DIAGRAM 2

 

 
 

 

Switch

 

 

24VAC

CONVERTING ZD from Power Closed to Power Open

 

Tools required - flat tip (3/16x7") screwdriver (magnetized or adhesive tape)                          

             

 

 

1.         Set the damper on a flat surface with the motor on the top of damper.

 

 

2. 

Note the position of the damper linkage (crank arms/drawbar) on the opposite 
side of motor as shown in Power Closed drawing at right.

 

3. 

Loosen the slotted set screw on the coupling located between the faceplate 
and damper frame.  This allows the motor to be removed.

 

 

4. 

Disengage (gently pry up on snap fit crank arm base) and remove the linkage 
assy connecting the blades.

 

5.         Rotate damper blades counter clockwise to closed position

 

 

6. 

Reattach (snap fit crank arms) linkage assy, crank arms are now aligned at 
apx 7 o'clock position as shown in Power Open drawing at right.

 

7. 

Reattach the motor and tighten the set screw. Apply power to ensure the damper 
powers open and spring returns closed.

 

 

 

 

 

Crank arms shown                             Crank arms shown 
  in Open Position                                in Closed Position 
 