Example scenario #1:

 5 minute setting ON 

A fan call is activated  -> damper opens and a 
timer begins to track time damper is open -> if fan 
runs for 5 minutes the damper will be open for 5 
minutes and then close. The damper will not open 
again during a fan or heat call until the hour resets. 

 

Example scenario #2:

 10 minute setting ON 

A fan call is activated -> damper opens for 5 
minutes and the fan call drops -> 5 minutes still 
remain in the hour for the damper to be open -> 
later in the hour there is a heat call -> the damper 
opens for the remaining 5 minutes then closes. The 
damper will not open again during a fan or heat 
call until the hour resets. 
 

Example scenario #3:

 20 minute setting ON 

A heat call is activated -> The damper opens for 10 
minutes and the heat call drops -> 10 minutes still 
remain in the hour for the damper to be open -> 
There is no fan or heat call the rest of the hour -> 
the FX1 will force the damper to open the last 10 
minutes of the hour to satisfy the 20 minute setting 
for that hour. 

Ventilation Minutes Per Hour 
The ventilation setting dial on the board is configurable from 

 45 minutes in 5 minute increments. As well, the FX1 can 

be  set  to  OFF  and  ON,  when  set  to  OFF  the  FX1  will  not 
open  the  damper  and  when  set  to  ON  the  DAMPER  will 
always be open and when there are no active calls coming 
in to the HVAC unit the FX1 will run the fan. 
 
Power LED 
The  power  LED  will  illuminate  any  time  the  FX1  has  a 
24VAC  power  signal  coming  to  it  and  the  self-resetting 

thermal fuse hasn’t tripped.

 

 
Ventilation LED  
Anytime the FX1 is powering open the fresh air damper the 
ventilation LED will be illuminated. 
 
Power 

  The  FX1  is  to  be  powered  by  the  equipment 

transformer in order to operate properly. 
 
Fresh Air Damper 
The  FX1  is  designed  to  work  Power  Open  Spring  Closed 
dampers with motors that have a power rating of 6 watts or 
less.  Although  dampers  that  draw  higher  power  may  work 
they  are  not  recommended  as  the  equipment  transformer 

may not have enough power to properly actuate the motor’s 

higher power requirements. 
 
TROUBLESHOOTING 
The  FX1  is  a  very  simple  control  to  troubleshoot.  The  only 
other device needed is a simple Volt/Ohm meter.   
 
Almost all problems can be traced to an external component 
or wiring to the FX1.   While the FX1 has been designed to 
operate  under  extreme  voltage  conditions  and  is  fuse 
protected,  like  any  computer  the  micro-processor  can  hang 
up and not operate properly. Should the FX1 hang up or not 
work  properly  turn  off  the  power  to  the  panel  for  several 
seconds  until  the  power  LED  goes  out,  then  turn  the  power 
back  on  to  see  if  the  panel  resets.    In  many  instances  this 
resolves the problem.   
 
The  first  check  is  for  24VAC  power  to  the  panel.    When 
there  is  power  the  power  LED  will  be  illuminated.    If  not 
check the transformer and the power supply to it.   
 
Damper Not Closing 
If  the  fresh  air  damper  is  not  closing  and  there  is  not  an 
active HVAC call it may be that the Fresh Air requirement for 
the hour has not been met by active HVAC calls and the FX1 
had to initiate a fan call and open the damper to satisfy the 
fresh  air  requirement.  Insure  that  there  are  no  HVAC  calls 
and using the Ventilation Minutes Per Hour Dial turn it to off. 
At this point the ventilation 

LED should turn off and the unit’s 

fan should shot off and the fresh air damper should close. 
 
Damper Motor Checkout Procedure 
 
First  end  all  HVAC  calls  and  check  that  the  FX1  ventilation 
LED  is  no  longer  illuminated,  at  this  point  your  damper 
should  be  closed,  if  not  disconnect  the  damper  wires  from 
the  controller  and  the  damper  should  spring  to  the  shut 
position. If the damper does not appear to be opening when 
it should you can disconnect it and apply 24VAC directly to 
the  2  wires  going  to  it and  it  should  power  open,  if  at  this 
point it does  not open check  for voltage  at the point where 
the  wires  attach  to  the  pigtail  coming  off  the  fresh  air 
damper. 

 

 